Contents
1. time the UPS is used it is strongly recommended to charge batteries for at least four hours in order to ensure maximum capacity To do so simply plug the unit into an AC outlet 2 When you use the included software connect either the serial or the USB cable between the computer and the corresponding port on the UPS Note If the USB port is used the serial port will be disabled They cannot be used simultaneously The computer with the PowerPanel Business Edition S W connects to the USB port or to the serial port on the UPS It can control the operating schedule battery test outlet etc and get information on the UPS status However other computers with PowerPanel Business Edition S W can only get UPS status information via a LAN connection 3 With the UPS unit off and unplugged connect your computer monitor and any externally powered data storage device Hard drive Tape drive etc onto the outlets DO NOT plug a laser printer copier space heater vacuum cleaner paper shredder or other large electrical device into the UPS The power demands of these devices will overload and possibly damage the unit 4 To protect a fax telephone modem line or network cable connect the telephone or network cable from the wall jack outlet to the jack marked IN on the UPS Then connect a telephone or network cable from the jack marked OUT on the UPS to the modem computer telephone fax machine or network device INSTALLING YOUR
2. with 10 Amps maximum over current protection in accordance to CE requirements CAUTION The AC outlet where the UPS is connected should be close to the unit and easily accessible CAUTION Please use only VDE tested CE marked mains cable e g the mains cable of your equipment to connect the UPS to the AC outlet CAUTION Please use only VDE tested CE marked power cables to connect any equipment to the UPS CAUTION When installing the equipment ensure that the sum of the leakage current of the UPS and the connected equipment does not exceed 3 5mA CAUTION This is permanently connected equipment and only qualified maintenance personnel may carry out installations CAUTION Do not unplug the unit from AC Power during operation as this will invalidate the protective ground insulation CAUTION DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT Under no circumstances this unit should be used for medical applications involving life support equipment and or patient care CAUTION DO NOT USE WITH OR NEAR AQUARIUMS To reduce the risk of fire do not use with or near aquariums Condensation from the aquarium can come in contact with metal electrical contacts and cause the machine to short circuit CAUTION DO NOT USE WITH LASER PRINTERS The power demands of laser printers are too large for this unit DO NOT INSTALL THE UPS WHERE IT WOULD BE EXPOSED TO DIRECT SUNLIGHT OR NEAR A STRONG HEAT SOURCE DO NOT BLOCK OFF VENTILATION OPENIN
3. CyberPower Reliability Quality Value User s Manual Professional Rack Mount LCD Series PR750ELCDRT1U PR1000ELCDRT1U K01 0000143 01 IMPORTANT SAFETY INSTRUCTIONS This manual contains important instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate the UPS CAUTION The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection DO NOT plug the UPS into an outlet that is not grounded If you need to power drain this equipment turn it off and unplug the unit CAUTION The battery can power hazardous components inside the unit even when the AC input power is disconnected CAUTION The UPS should be near the connected equipment and easily accessible CAUTION To prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area free of conductive contaminants Please see specifications for acceptable temperature and humidity range CAUTION To reduce the risk of an electric shock do not remove the cover except to service the battery There are no user serviceable parts inside except for the battery CAUTION To avoid electrical shock turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer component CAUTION To reduce the risk of fire connect the UPS to a circuit
4. GS AROUND THE HOUSING DO NOT CONNECT DOMESTIC APPLIANCES SUCH AS HAIR DRYERS TO UPS OUTPUT SOCKETS INSTALLING YOUR UPS SYSTEM UNPACKING The box should contain the following 1 UPS unit x 1 2 User manual x 1 3 Phone line x 1 4 PowerPanel Business Edition software CD x 1 5 USB A B type cable x 1 6 Rack mount Brackets x 2 7 Emergency Power Off Cable gray x 1 8 Serial Interface Cable DB 9 x 1 9 Power Cord x 5 AUTOMATIC VOLTAGE REGULATOR AVR The PR750ELCDRT1U PRIOOOELCDRT1U can stabilise utility power inconsistances The utility power may be damaging to important data and hardware but Automatic Voltage Regulation helps the computer not experience utomatic Voltage Re dangerous voltage levels The Automatic Voltage Regulator regulates low or gh uti vera cori and sak its high voltages to keep equipment working at safe AC power levels drops below 150 volts or exceeds 300 vols 220 230 240V without switching to battery mode Your equipment can operate normally even during power problems such as shout brownouts and blackouts The units powerful sealed lead acid batteries will provide power only if the incoming voltage drops below 150V or increases above 300V SYSTEM BLOCK DIAGRAM Filter Surge Suppressor Output Input Charger AC DC Normal Mode ns E Battery Mode HARDWARE INSTALLATION GUIDE 1 Battery charge loss may occur during shipping and storage For the first
5. PACITY is shown as a bar chart each segment indicates approximately a 20 of battery capacity LOAD CAPACITY Load CAPACITY is shown as a bar chart each segment indicates approximately a 20 of load capacity DEFINITIONS FOR ILLUMINATED LCD INDICATORS continued Line mode UPS Status Display Capacity Display Digital Value Display Select SW Kg ies Load Battery Input Output Run of of Press Cap Cap Voltage Voltage Time Load Battery aS eee ee eee Ea a test Battery Mode UPS Status Display Capacity Display Digital Value Display Select SW Load Battery Input Output Run of of 2 K AR Press Voltage Voltage Time Load Battery a a a e o ep D S T S E retum pee te n einai Sound ion Press gt 4sec again sound enable veroad X ov v vj V illuminated X Not illuminated either LCD SETUP FUCTIONS General Mode a Press the Display Toggle button to check the UPS status tems Sit Load Capacity Battery Capacity b Press and hold the Display toggle button for 4 seconds If the machine is in the Battery Mode with active alarm it will become silent If the machine is in the Line Mode a self diagnostic test will take place c If the Display toggle button remains untouched for over 30 seconds the LCD backlight will turn off automatically Set up Mode Step 1 Hold the Display toggle button for 10 seconds to en
6. Step 4 To save the value and return to general mode press and hold the toggle for 4 seconds Note If the machine is left idle for over 30 seconds during setup it will turn off the backlight and return to general mode automatically Note If user wants to return to the general mode without saving changes there are two methods 1 Wait for the backlight display to turn off or 2 By pressing and holding the Display toggle key for 10 seconds CYBERPOWER GREENPOWER UPS TECHNOLOGY GreenPower UPS CyberPower s GreenPower UPS Circuit Design is a solution to this Power Loss When the Utility Power is operating normally GreenPower UPS works in a Bypass Mode Our GreenPower UPS design conducts power only through the Relay and still provides normal output voltage Bypassing the transformer reduces power consumption thereby conserving energy and saving money When the utility power is abnormal the UPS will operate under Battery or AVR Mode Under this condition GreenPower UPS and a traditional UPS would operate about the same On average utility power operates 88 of the time and the CyberPower GreenPower Technology will work in its money energy saving Bypass Mode TECHNICAL SPECIFICATIONS Moda O PR750ELCDRT1U PR1000ELCDRT1U Capacity VA 750VA 1000VA Capacity Watts 500 670 Nominal Input Voltage 220Vac 240Vac Input Voltage Range 160Vac 290Vac Input Frequency Range 50 60 Hz 3 Hz
7. UPS SYSTEM continued 5 Press the power switch to turn the UPS on The Power On indicator light will illuminate If an overload is detected an audible alarm will sound and the UPS will emit one long beep In order to reset it turn the unit off and unplug some equipment from outlets Make sure your equipment carry a load current within the unit s safety range refer to the technical specifications and then turn the unit on 6 Your UPS is equipped with an auto charge feature When the UPS is plugged into an AC outlet the battery will be automatically charging even when the unit is switched off 7 To always maintain an optimal battery charge leave the UPS plugged into an AC outlet at all times 8 Before storing the UPS for an extended period of time turn the unit OFF Then cover it and store it with the batteries fully charged Recharge the batteries every three months or so to ensure good battery capacity and long battery life further this might also prevent damage to the unit from an unlikely battery leakage 9 The unit provides one serial port and one USB port to allow connection and communications between the UPS and any attached computer The primary computer the one with PowerPanel Business Edition S W installed is the computer that you will use to control the UPS and make any changes to its operation When there is a power failure the connected to the USB or Serial Port computer may be asked by the UPS for a gracef
8. a D jE Cees GS O AC INPUT gt The unit provides a total of six outlets with battery backup and surge protection They ensure that connected equipment will keep an uninterrupted operation over a period of time during a power failure Critical Non critical lt is possible to program the unit in a way so that the outlet block marked as non Critical 4 ports will stop the provision of power to connected equipment after a certain period of time thus making more runtime available for the equipment connected on the outlets marked as Critical 2 ports In other words the user can establish runtime priority for certain connected equipment maximizing its availability during a prolonged power outage This type of control takes place with the use of the provided PowerPanel Business Edition S W 6 AC Inlet Connect the AC Power cord to a properly wired and grounded outlet 7 Input Circuit Breaker This circuit breaker serves to provide input overload and fault protection 8 USB port to PC This is a connectivity port allowing communication and control among the UPS and the connected computer You should install on your computer the PowerPanel Business Edition software appropriate to the operating system you are using 9 Serial Port This is a connectivity port allowing communication and control among the UPS and the connected computer You should install on your co
9. auto sensing On Battery Output Voltage On Battery Output Frequency Transfer Time Typical Overload Protection Surge Protection and Filtering Lightning Surge Protection a Physical Dimensions cm Weight kg Battery SS ee aa Sealed Maintenance Free Lead Acid 6V 9 0AH x 4 Battery Hot Swappable External Battery Warning Diagnostics Indicators Audible Alarms On Battery Low Battery Overload Operating Temperature 32 F to 104 F 0 C to 40 C Operating Relative Humidity 0 to 95 Non Condensing Communication PowerPanel Business Software TROUBLE SHOOTIMG Circuit breaker has tripped due to an overload Outlet does not provide power to equipment Unit has been damaged by a surge or spike Non critical outlets have turned off automatically due to an overload Batteries are not fully The UPS does not charged perform expected runtime Batteries are degraded The on off switch is designed to prevent damage by rapidly turning it off and on The unit is not connected to an AC outlet The UPS will not turn on The battery is worn out Mechanical problem The cable is connected to the wrong port PowerPanel Personal Edition is inactive The unit is not providing battery power The serial cable is not the cable that was provided with the unit Turn the UPS off and unplug at least one piece of equipment Wait 10 seconds reset the circuit breaker by depressing the butt
10. etal objects from your hands Only use tools with insulated handles DO NOT lay tools or other metal parts on top of the battery or any battery terminals Wear rubber gloves and shoes Determine if the battery is grounded If so remove ground source CAUTION CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK The likelihood of such a shock will be greatly reduced if such grounding is removed during installation and maintenance 0 BRON BATTERY REPLACMENT PROCEDURE Disconnect the black and red wires from the battery Remove the front panel Remove the two retaining on the right side screws of the cable protection cover and then remove the cover itself Remove the retaining screw Put the new battery packs back into the compartment Tighten up the screws and replace the cable protection cover and the front panel Recharge the unit for at least 8 hours to ensure that the UPS performs to the expected runtimes REMINDER The used batteries are hazardous wastes and must be disposed through recycling Most retailers that sell lead acid batteries collect used batteries for recycling as required by the local regulations DEFINITIONS FOR ILLUMINATED LCD INDICATORS Input voltage meter This meter measures the AC voltage from the wall outlet The INPUT voltage readout is used to identify the input voltage information When the UPS connects to any equipment the AVR can provide a stable 220 230 240V power output In
11. mputer the PowerPanel Business Edition software appropriate to the operating system you are using 10 SNMP HTTP Network slot Remove the cover panel to install an optional SNMP allowing your UPS be controlled and monitored via a network connection 11 EPO Emergency Power Off port Allow for an emergency UPS Power Off from a remote location BATTERY REPLACEMENT Allow for an emergency UPS Power Off from a remote location Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the batteries Servicing the batteries should only be performed by professionals For further information please contact your dealer or email to service cyberpower eu com Make a note for the replacement battery pack number RBP422 regarding PR750ELCDRT1U and PR1000ELCDRT1U models BATTERY REPLACEMENT continued CAUTION Use only the specified type of battery HR9 6 BB for PR750ELCDRT1U PR1000ELCDRT1U Contact your dealer for replacement batteries CAUTION The battery may represent the risk of electrical shock Do not dispose of batteries on fire since they may explode Follow all local ordinances regarding the proper disposal of batteries CAUTION Do not open or mutilate the batteries Released electrolyte is harmful to the skin and eyes and may be toxic CAUTION A battery can present a high risk for short circuits and electrical shocks Take the following precautions before replacing the battery Remove all watches rings or other m
12. on and then turn the UPS on Batteries are discharged Recharge the unit for at least 4 hours Contact CyberPower Systems about replacement batteries at service cpsww com au Push the toggle button to make the uncritical outlets turn on Recharge the battery by leaving the UPS plugged in Contact CyberPower Systems about replacement batteries at service cpsww com au Turn the UPS off Wait 10 seconds and then turn the UPS on The unit must be connected to a 220 230 240v outlet Contact CyberPower Systems about replacement batteries at service cpsww com au service cpsww com au cable is not connected cable that came with the unit Try another port on your computer Shutdown your computer and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit You must use the cable included with the unit for the Software For more information visit www cpsww com au or contact CyberPower Systems Australia E MAIL service cpsww com au CEM FAL 10
13. ter the UPS Set Up Mode Step 2 By pressing the Display toggle users can switch between setup functions Some User Configurable functions are as follows a b C e Delay Time The time delay between switching from Battery Mode to Line Mode There are 9 different settings The default setting is 0 minutes Battery Pack Numbers PR750ELCDRI1U PR1000ELCDRT1U do not support this function and the LCD always shows 0 Static Frequency Tolerance There are 4 settings 1 2 4 6 and the default setting is 6 Functional description The setting may be adjusted to the quality of the electricity in use Slew Rate Also known as Dynamic Frequency Tolerance There are 5 different settings 0 25 0 5 1 2 4 Hz Sec The fault value is 4HZ sec Functional Description Slew Rate indicates the tolerance of a device in accepting frequency variance Lower Slew Rate results in less tolerance but better protection for the connected load and vice versa Low Battery Shutdown Voltage This function will adjust the UPS shutdown point according to the battery s remaining capacity These programmable items are sorted by unit as in the following table ltems O o Delay Time Battery Pack Numbers Static Frequency Tolerance Slew Rate Low Battery Shutdown Voltage Step 3 Press and hold the display toggle button for 4 seconds When the icons blink the value of each item can be changed by slightly pressing the toggle
14. the event of a complete loss of power severe brownout or over voltage the UPS relies on its internal battery to back up to supply a consistent 220 230 240V output Output voltage meter This meter measures the output voltage from the UPS Estimated Run Time This displays the estimated UPS runtime based on current load When runtime becomes shorted the battery capacity will decrease battery capacity bar indicator will be falling Normal mode icon This icon illuminates when the UPS is working under normal conditions Battery icon When there is a severe brownout or blackout this icon will appear followed by an alarm two short beeps indicating that the UPS is now working using its internal batteries Once the batteries are run out of power over a period of time a constant alarm will sound If this happens and main power has not been restored it is recommended that you save your files and turn off your equipment manually as soon as possible Silent mode icon This icon appearing indicates that the buzzer will not be beeping while in battery operating mode During Silent mode the unit s alarm does not sound until the Battery Capacity falls to lt 20 Over load icon This icon will appear followed by an alarm indicating that an overload condition has been reached To recover from the overload condition start unplugging your equipment from the UPS outlets until the icon disappears and the alarm stops BATT CAPACITY BATT CA
15. ul shutdown following a possible pre programmed time period delay indicated within the controlled S W 10 EPO Emergency Power Off Port Use the provided gray cable to connect to a special EPO contact switch Follow the appropriate circuit diagram below to wire the cable to your EPO configuration The EPO remote switch is a switch installed in an outside area connected to the unit via an ordinary RJ 11 phone line In case of an emergency it can be used to immediately cut off power from the UPS unit BASIC OPERATION FRONT PANEL DESCRIPTION 1 Multifunction LCD Readout An LCD that shows various UPS information using icons and messages 2 Power On Indicator Indicates that the AC utility input power s condition is normal and that the UPS outlets are providing power free of surges and spikes 3 Power Switch Master on off switch for equipment connected to the UPS 4 LCD Readout Toggle Button Used to select among a variety of information the LCD can display BASIC OPERATION continued REAR PANEL DESCRIPTION 5 Battery Backup and Surge Protected Outlets P 10 aD D NONCRITICAL LOAD Di Oee x BAe f g