1. PES Innovative PA Operating Instructions Mains Water Top UP Set Compact Page 1 of 9 Contents CONTO MIS s T TE O l PROGUCE Description a a a 2 COMPONE MIS a 2 eO E E N A E E E E I 3 Contorno 3 SA o O sesso acai A E E A 3 CV CLIPEO Dead lic 4 NA II O II A 5 Controle mil peratiOn os 5 A RN 6 Internal Jumper Setas raices 6 Ml WO OUING isietacers ss ceva toutetiad a eee ees 7 9b OLS SIUM Ler 1G daras cal ia til cd mtorr tes 9 Cono MN O A E E 9 ESPE aa 9 Page 2 of 9 Product Description Automatic mains water top up for rainwater tanks with leak detection feature and pump dry run protection Components 1 Ball Valve 2 30cm Braided Steel Flexi Hose with Isolation Valve To mains water feed 3 Solenoid Valve 4 Tundish with Bracket DN 40 Overflow DN 50 Outlet 5 Control Unit 6 Level Probe 7 Schuko European Mains Plug This 1s supplied in order to allow you to connect a pump to the European style mains socket on the front of the unit Handling and Storage Pre installation Do not leave outdoors in the rain It is not waterproof This is not an armoured or heavy duty appliance it will not survive impact and drops crushing etc Do not leave on the floor If damaged do not use it Do not store with or upon cement sand plaster etc These materials will corrode the circuit board and cause cosmetic damage Do not install in a location subject to freezing temperatures
2. meeting the requirements of BS EN 13076 Please refer to the separate Tundish Installation Sheet for correct installation of the Tundish If in doubt you should consult an approved and qualified plumber Page 4 of 9 Level Probe The supplied conductivity Level Probe is used as a minimum water level detector in the rainwater tank The standard length of cable supplied is 15m Fix the Level Probe in the tank so that it is suspended approximately 0 3 to 0 4 metres above the bottom depending on the shape of the tank and position of pump inlet If in doubt you MUST consult an approved and qualified plumber The height of the Level Probe determines the minimum water level of the tank at which the pump will run The Level Probe works by conductivity when the Level Probe s contacts are immersed in water a circuit is completed and the control unit detects this Note The level probe s cable can be extended to a maximum of 30m OPERATIONAL ADVICE NOTE Ensure that the tank is entirely free of debris before installing a pump and this controller Plastic swarf from manufacturing and other debris will quickly clog any filters and may get caught in the pump s impellers prematurely shortening the operational life of the system and invalidate pump and other component warranties Maintenance Advice It is good practice to clean the probe at intervals of three years or when checking the tank Page 5 of 9 Operation Test but
3. This may include outbuildings and uninsulated loft spaces Page 3 of 9 Installation Control Unit We recommend installation to be carried out by a qualified electrician The Control Unit must be mounted indoors in a dry place it can be wall mounted using the supplied fittings NOTE It is not a waterproof unit DO NOT install in a tank turret We strongly recommends wiring the unit on an RCD protected circuit in accordance with current best practice and regulatory requirements as defined by BS 7671 current IEE wiring regulations and Part P of Building Regulations where applicable If in doubt consult a qualified electrician We realize there are a wide variety of pumps supplied in the UK rainwater market some with 2 pin schuko and some with 3 pin UK plugs A 2 pin schuko plug can plug directly into the plug socket on the face of the unit If your pump has a 3 pin UK plug there are two options available Change the pump s plug to a 2 pin schuko plug one is supplied with this kit Use an earthed 2 pin schuko to 3 pin UK socket adapter to plug into the Control Unit s pump socket not supplied SAFETY NOTE European style Schuko plugs are not protected with a fuse therefore it is vital the controller is installed on a 10A fused outlet to protect both the pump and controller If in doubt you MUST consult a qualified electrician Tundish The Tundish acts as an air gap to prevent backflow into the mains water supply
4. ed that there is no power to the unit Setting shut off during top up probe is reached Jumper setting 1 The pump will turn off 15 seconds after the beginning of a top up cycle The Solenoid Valve will close 1 minute after the water level reaches the Level Probe If the water level doesn t reach the Level Probe within 30 minutes the unit alarms Jumper setting 2 The pump will turn off 10 minutes after the beginning of a top up cycle The Solenoid Valve will close 20 minutes after the water level reaches the Level Probe If the water level doesn t reach the Level Probe within 45 minutes the unit alarms Troubleshooting Symptom Possible Faults Solid Red LED Controller has alarmed and shut down Flashing red LED Controller has been stopped manually Top up cycle is too frequent causing pump to be shut off during demand for water Top up cycle activates often even when no water is drawn Controller does not function no lights Solenoid is blocked Solenoid has failed Solenoid functions normally tundish overflows Solenoid functions normally tundish does not overflow but tank does not fill No fault Too small a top up time is selected Possible tank failure or fault leak in supply pipes from pump Internal fuse failure Controller or associated Page 7 of 9 Press Reset then test solenoid by pressing Test button If solenoid clicks but no water flows check the supply pipe
5. it breaker is of a suitable rating 16A Type B recommended also test wiring insulation and earth If the supply circuit is proved to have no fault contact your supplier for replacement Unplug the pump and test separately The control unit can supply up to 10A at 240v to the pump It may be damaged if this specification is exceeded Page 9 of 9 Specification Control Unit Dimensions W x H x D 97 x 163 x 62 mm Weight 0 5 kg Supply voltage AC 230 240 V 50 Hz Power consumption max 5 VA Internal fuse 32 mA Pump power outlet socket AC 230 240 V max 10 A Mains Plug Fuse T 10 A Operating temperature range Ambient 0 C to 40 C Protection class H DIN 57 700 Protection IP 20 EN 60529 Noise suppression According to EN 50081 1 Noise immunity According to EN 50082 1 Level probe Supply voltage AC 6 V Probe current 1 2 mA Cable length 15m max 30m Dimensions of probe L x 87 x 30 mm Weight 0 2 kg Principle of operation Conductivity Medium Clean water Solenoid valve Dimensions W x H x D 95 x 80 x 100 mm Weight 0 5 kg Supply voltage AC 230 240 V 50 Hz Power consumption max 5 5 VA Connection cable 3 m Mounting position Any Medium Clean water Nominal pressure 12 bar Flow rate at 4 bar inlet pressure and open outlet approx 50 l min Function Closed when de energised Connection Inlet 34 BSP union nut with in line filter Outlet 42 BSP female th
6. read Protection IP 65 EN 60529
7. rocess takes place automatically Safety Shutdown During a top up cycle if the water level in the tank has not reached the level probe after 30 minutes of topping up the unit will shut off the pump and close the solenoid The red alarm LED lights to indicate that there is a leak or blockage in the delivery to the tank a failure of the tank itself or a problem with the solenoid valve Page 6 of 9 LEDs Green Solid Normal Operation Solenoid Valve closed Pumps runs as usual Water level sufficient Green Flashing Top up cycle in progress Solenoid Valve open topping up Pump switched off during top up Red Solid Safety shutdown Top up failed Red Flashing Control Unit stopped manually stop reset button has been pressed Internal Jumper Settings This can be adjusted to increase the duration of the top up cycle and should be set by 3P in advance or otherwise adjusted by a qualified electrician or electronic technician The power supply MUST be disconnected before opening the Control Unit there are hazardous voltages inside For larger tanks and flow rates the jumper can be moved from the default position 1 to position 2 This position tops up much more water into the tank In position 2 the pump shut off delay and alarm delays are also increased accoridngly If in doubt please consult a qualified electrician or electronic technician Attention The Control Unit must only be opened when it has been ensur
8. ton Control Unit Operation Pressing this when the Solenoid Valve is closed will momentarily open and close the Solenoid Valve Rainwater Top up Manager Power LED Test Button Stop Reset button Alarm LED Closes the solenoid valve and shuts off power to the pump Unused LED The Alarm LED will flash Stop Reset Button Pump Controller Socket l Unused Buton A second press will reset the controller to its usual working state gt Power Connection Solenoid Valve nnection Connection Level Probe Connection When the Control Unit is powered up High Water Level If the Level Probe is below the water level in the tank then the green LED remains on there is power to the pump socket so a connected pump will run and the solenoid valve is closed not topping up Low Water Level If the water level falls below the level probe a top up cycle will begin The green LED flashes and the Solenoid Valve opens to allow mains water to flow through the Tundish into the rainwater tank During the top up cycle the pump will be turned off Once the water level reaches the Level Probe again the pump is again allowed to run The solenoid valve will remain open for a further minute before closing The top up cycle is now complete and the green LED changes from flashing to solid Self Maintenance The Control Unit will momentarily open and close the Solenoid Valve three times a week to prevent blockages This p
9. work and flexi hose for blockages If supply 1s clear but solenoid does not function replace solenoid call technical support If solenoid does not click check wiring from solenoid to controller for possible damage If OK replace solenoid call technical support The supply pipe from tundish to tank is blocked Clear blockage and retest Check tundish to tank pipework by visually looking for top up water entering the tank If no water is present suspect failure in pipework If water 1s present suspect tank failure Press the stop reset button to reset the controller Follow the Internal Jumper Settings instructions to change the jumper to position 2 Consult a qualified electrician before opening the Control Unit Shut down controller and pump and check tank water level periodically during dry weather If water level drops suspect tank failure Otherwise switch on controller and pump and check for leaks in outlet pipes from pump and possible leaks of toilet float valves etc Have the controller s internal fuses checked by a qualified electrician and replaced if necessary If the unit fails again contact your supplier for replacement Have the supply circuit checked by a qualified Pump does not run top up and other functions seem ok For all other faults contact your supplier wiring has tripped the mains circuit breaker or RCD Pump failure Controller Damaged Page 8 of 9 electrician Check circu