Home

Panasonic U-72MF1U9E Service & Technical Guide

image

Contents

1. 1 1 T 1 4 T PCB assy ES See 55002 eem GSP avs ance 5202 51 PBS 0089 000 000 owes r BLK DISCHI DISCH2 DISCH3 CNOI5 CN01I CN229 CN230 o Fa 2 wr 81 2 133 DU CP CN03 i YeL BLU aw D ur MOVI rep MOV2 gu Movs Bu 289 PPO reda Fy a Bs mE F L SEU 2 R BLK 2 8 q 1 04 meh Aa F003 CN002 5865 s f x S 8 N SES E 8188 B588 8558 5 2 EXL1 m EXG EXG2 AIR TEMP 125V 0 5 _ Web d oL d 111 Ma 20 82825 9 vil Ba 9 S 8 NAL 2 028 2
2. ll gt o fo Ue On 19 S Bracket Unscrew the tapping screws and remove the bracket 1 4 1 D 55 85 o Tapping screws 4 pcs J Reinstall the bracket with i the tapping screws ree 180 degrees upside down Only 3 Way connect wire fix with a clip Design of 3WAY VRF SYSTEM 7 Optional Parts F1 Type QQ Solenoid valve relay kit 2 1 oo oo oo oo Solenoid valve relay kit Put
3. K1 Type Model S 07MK1U6 Clamping Connection for Solenoid S 09MK1U6 strap Valve Kit for 3WAY S 12MK1U6 Power wiring field suppli Conduit Remote control wiring field supplied and Inter unit control wiring field supplied K1 Type Clamping Connection for Solenoid Model S 18MK1U6 strap S 19MS1U6 S 24MK1U6 HHE Power wiring field supplied f Earth screw Remote control wiring and Inter unit control wiring field supplied Conduit field supplied Necessary to install the External Electronic Expansion Valve Kit Optional CZ P56SVK1U 2 30 3 Electrical Wiring 3 5 Important Note When Wiring for Y1 Type Connect the wires referring to the diagram Note that the control wirings Low Voltages shall be segregated from the power supply wires High Voltage as follows 1 Connect the Inter unit control wiring to U1 U2 terminals and the remote control wire to R1 R2 Then place and fix the two clasps so that the clasps shall cover both the remote control wires the Inter unit control wiring and the 3 way wiring harness as shown in the magnified drawing 2 Connect the grounding conductor of the incoming power supply to the earth ground screw
4. Design of 3WAY VRF SYSTEM 4 Installation Instructions 4 8 Transporting the Outdoor Unit When transporting the unit have it delivered as close to the installation site as possible without unpacking Use a hook for suspending the unit Fig 2 12 When hoisting the outdoor unit pass ropes or straps under the bottom plate as shown in the figure at right When hoisting the angle between the rope and top panel must be 70 or greater so that the rope does not come into contact with the fan guard Use 2 lengths of rope 25 ft long or longer When passing the ropes through the square holes of the bottom plate Place the rope in the outer edge of the square holes Use protective panels or padding at all locations where the rope contacts the outer casing or other parts to prevent scratching In particular use protective material such as cloth or cardboard to prevent the edges of the top panel from being scratched Be careful of the fan There is danger of injury if the fan starts to turn during inspection Be sure to turn OFF the remote power switch before beginning inspection 4 9 Installing the Outdoor Unit 1 Use anchor bolts M12 or 15 32 or similar to securely anchor the unit in 1 place Fig 2 13 Vibration insulator 2 Be sure the rubber vibra
5. 9 Left side 2 11 64 1 18 47 64 2 13 5 16 Space for creation of hole on site Max diameter 01 57 64 18 5 8 Front view ec 164 EX 17 51 9 1 16 13 64 58 S 96 _ i Knockout hole Se 1 33 64 S o Enlarged view of I TIt 19182 5 Table of Measurements for Refrigerant Tube Connection Position of S Equivalent Size in mm installation b d e f 9 61 64 G Ton 0 1 8 10 25 32 12 29 32 3 35 64 5 63 64 8 17 64 257 274 328 90 152 210 6 37 64 6 27 32 12 29 32 3 35 64 5 63 64 8 17 64 Position of refrigerant 167 174 328 90 152 210 8 Ton connection Z view Measurements for 8 Ton assume that the supplied connection tubing is used 4 12 1 Outdoor Unit 74 Ceiling panel dimensions 3WAY VRF SYSTEM Unit Specifications 1 4 Multiple Unit Installation Example 35 35 unit in Equivalent Ceiling panel dimensions Ceiling panel dimensions quivalen 2
6. Contents 3 Control of 3WAY VRF SYSTEM Main Operating Functions Wireless Remote Controller Timer Remote Controller Simplified Remote Controller System Controller Schedule Timer Intelligent Controller CZ 256ESMC1U Communication Adaptor CZ CFUNC1U Remote Sensor 10 LonWorks Interface CZ CLNC1U Refer to the 2WAY SYSTEM TECHNICAL DATA TD831157 Control of 3WAY VRF SYSTEM Contents 3WAY VRF SYSTEM Unit Specifications 4 3WAY VRF SYSTEM UNIT SPECIFICATIONS 1 Outdoor Unity u uuu n 4 2 4 2 AIR Registration Values erc 4 11 1 3 Dimensional Data 4 12 1 4 Multiple Unit Installation Example Ad M REG FA aud AER DEP Ra ar 4 13 1 5 Retrigerant Flow Diagram CS 4 15 1 6 Noise Criterion Curves 4 16 2 4 Way Cassette Type U1 Type 3 4 Way Cassette 60x60 Type Y1 Type 4 1 Way Cassette Type D1 Type 5 Low Silhouette Ducted Type F1 Type 6 Slim Low Static Ducted Type M1 Type 7 High Static Pressure Ducted Type E1 Type 8 Ceiling Type T1 Type 9 Wall Mounted Type K1 Type 10 Floor Standing Type P1 Type 11 Concealed Floor Standing Type R1 Type 12 Intaking Fresh Air of 4 Way Cas
7. nit 1 Room 2 Room 3 Room 4 indoor unit 1 indoor unit 2 indoor unit 3 indoor unit 4 bui Air condition DB WB 91 0 72 0 78 0 64 0 78 0 64 0 78 0 64 0 78 0 64 0 oolin 9 load BTU h 50 000 30 000 30 000 18 500 Air condition DB WB 37 0 35 0 69 0 55 0 69 0 55 0 69 0 55 0 69 0 55 0 eatin 9 Max load BTU h 55 000 35 000 35 000 20 000 Actual tubing length 296 ft 197 ft 230 ft 263 ft 296 ft Equivalent length with consideration for curves etc 355 2 ft 236 4 ft 276 0 ft 315 6 ft 355 2 ft Equivalent length after size up correction 276 5 ft 157 7 ft 197 3 ft 236 9 ft 276 5 ft Equivalent length after size up correction is used for the calculation of actual capacity Preliminary selection Outdoor unit Room 1 Room 2 Room 3 Room 4 indoor unit 1 indoor unit 2 indoor unit 3 indoor unit 4 Type Selected model 96 72 Type 54 Type 36 Type 36 Type 18 50 000 30 000 30 000 18 500 Load cooling heating BTU h 55 000 35 000 35 000 20 000 168 000 54 600 36 000 36 000 19 000 Rated t ling heat BTU h 4 ated capacity coolingheating BTU h 189 000 61 400 39 000 39 000 21 000 147 532 93 54 600 00 35 781 01 34 941 99 18 000 59 S Corrected capacity coolingih ating BTU h 146 812 33 61 768 00 3923400 3923400 21 126 00 54 600 00 35 781 01 34 9
8. Flare nut Service port cap Use two adjustable wrenches as shown in the figure removing the liquid tube valve flare nut 1 Do not apply a wrench to the valve cap when removing or installing the flare nuts Doing so may damage the valve 2 If the valve cap is left off for a long period of time refrigerant an adjustable wrench to the hexagonal part at the top of the valve If force is applied to this part gas leakage will occur leakage will occur Therefore do not leave the valve cap off 3 Applying refrigerant oil to the flare surface can be effective in preventing gas leakage however be sure to use a refrigerant oil which is suitable for the refrigerant that is used in the system This unit utilizes R410A refrigerant and the refrigerant oil is ether oil synthetic oil However hub oil synthetic oil can also be used Precautions for brazing Be sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process Be sure to use a damp cloth or other means to cool the valve unit during brazing Work method Pressure reducing valve regulator Remote valve Field supply tube y Y Brazing locations Taping mE 1 Guo 2 3 sure to use nitrogen Oxygen CO2 CFC must be used Use a pressure reduc
9. 7 2 2 Indoor Unit Control PCB Switches and Functions Refer to the 2WAY SYSTEM TECHNICAL DATA TD831157 Section 8 CAPACITY TABLE J 8 1 1 Capacity Ratio of Outdoor Unit 8 2 2 Cooling Capacity of Indoor Unit succi era ai tun 8 10 Outline of 3WAY VRF SYSTEM Contents 1 OUTLINE OF 3WAY VRF SYSTEM MEL I P M 1 2 2 Features OF SWAY VRF SYSTEM ouais cita ad IUS MAE END 1 4 3 Salt Air Damage Resistant Specifications 1 7 1 Line up Indoor units Type Outline of 32WAY VRF SYSTEM 4 Way Cassette 01 Type S 24MU1U6 S 36MU1U6 4 Way Cassette 60 X 60 Y1 Type S 18MY1U6 1 Way Cassette D1 Type lt BX S 07MD1U6 gt lt S 09MD1U6 S 12MD1U6 Low Silhouette Ducted F1 Type Ee S 07MF1U6 S 09MF1U6 ey S 12MF1U6 ey S 15MF1U6 ey S 18MF1U6 ge S 24MF1U6 gest S 36MF1U6 gest S 48MF1U6 gest S 54MF1U6 Slim Low Static Ducted M1 Type S 07MM1U6 S 09MM1U6 S 12MM1U6 S 15MM1U6 ey S 18MM1U6 High Static Pressure Ducted E1 Type S 36ME1U6 S 48ME1U6 Ceiling 1
10. Using a tube cutter cut the joints at the diameter required to match the outside diameter of the tubing you are connecting This is usually done at the installation site The tube diameter depends on the total capacity of the outdoor unit Note that you do not have to cut the joints if it already matches the tubing end size For size selection of the tube diameter refer to the installation instructions provided with the outdoor unit Avoid forceful cutting that may harm the shape of the joints or tubing Inserting the tubing will not be possible if the tube shape is not proper Stopper boss Cutting point e Cut off as far away from stopper as possible e After cutting the joints be sure to remove burrs on the inside of the joints If the joints have been squashed or dented badly reshaped them using a tube spreader Make this as long as Make sure there is no dirt or other foreign substances inside the distribution possible joint Insertion length of the connecting tube 2 47 Design of 3WAY VRF SYSTEM 7 Optional Parts The distribution joint can be either horizontal or vertical In the case of horizontal the L shaped tubing must be slanted slightly upward 15 to 90 Direction of Distribution Joint 15 to 30 upward slant Outdoor unit Outdoor Outdoo
11. 2 33 4 4 Installing the Outdoor Unit in Heavy Snow Areas 2 33 4 5 Precautions When Installing in Heavy Snow 5 2 33 4 6 Dimensions of Wind Ducting Reference diagram for air discharge chamber field supply 2 34 4 7 Dimensions of Snow Ducting Reference diagram for snow proof ducting field 2 35 4 8 Transporting the Outdoor cum cu akawa 2 36 4 9 Installing the Outdoor Unit LLL ea soa scence 2 36 4 10 Remove the Brackets Used for Transport a 2 37 2 11 TUDING u piii dots bred 2 37 4 12 Prepare the Miis pre PET rH 2 38 443 COMMIS CH TS TWN ca S 2 38 Indoor Unit Refer to the 2WAY VRF SYSTEM TECHNICAL DATA TD831157 5 HOW TO PROCESS TUBING sassa ass 2 40 5 1 Connecting the Refrigerant Tubing n 2 40 5 2 Connecting Tubing Between Indoor and Outdoor 2 41 5 3 Insulating the Refrigerant Tubing scooter tomate a Snap ud ne epe Leben asse Dres nua 2 42 5 4 The Tube tait au Ke na ER AR n d bd 2 43 5 5 FINISHING Wie MN qayqa quqa qquqawayqup
12. J 1 1 l su 1 2 2 Features of SWAY SYSTEM E n cx 1 4 3 Salt Air Damage Resistant Specifications 1 7 Section 2 DESIGN OF SWAY SYSTEM J 2 1 1 Model Selecting and Capacity 2 2 2 System Design 2 18 Electrical VIG 2 24 4 11 1 11 11151 0 MASERU INS Cc ERE 2 32 HOW TO PROCESS TUBING a 2 40 6 AIRPURGING scoret mM 2 44 oe rene n E EEEE 2 47 Section 3 Control of SWAY SYSTELM J 3 1 1 Main Operating Functions 2 Wireless Remote Controller 3 Timer Remote Controller 4 Simplified Remote Controller 5 System Controller 6 Schedule Timer 7 Intelligent Controller CZ 256ESMC1U 8 Communication Adaptor CZ CFUNC1U 9 Remote Sensor 10 LonWorks Interface CZ CLNC1U Refer to the 2WAY SYSTEM TECHNICAL DATA TD831157 Section 4 3WAY SYSTEM UNIT SPECIFICATIONS 4 1 O tdoor Meu mga comets 4 3 2 4 W
13. 2 6 155 InstallatieryrSIandardsu rer 2 8 1 6 Straight Equivalent Length of Joints 2 9 1 7 Sae Of density E oom 2 10 1 8 Calculation of Actual Capacity of Indoor Unit innocentes 2 11 1 9 Capacity Correction Graph According to Temperature Condition 2 15 1 10 Capacity Correction Graph According to Tubing Length and Elevation Difference 2 16 2 System C 2 18 MES ccs a a m 2 18 2 2 Example of Tubing Size Selection for Extension and Additional Charge Amount 2 20 2 3 Installing Distribution Joint 2 23 cA Electrical si ITI ILLI 2 24 3 1 General Precautionis 2 24 3 2 Recommended Wire Length and Wire Diameter for Power Supply System 2 24 3 3 Wiring System DIagrarfiS RR EE OE 2 25 3 4 Important Note When Wiring for Common 2 28 3 5 Important Note When Wiring for Y1 Type 2 31 A Installation Instructions issue ceni menos nia a ill VE E Eg ER gra 2 32 E O tdoor Unit gt S 2 32 4 1 Selecting the Installation Site for Outdoor Unit a 2 32 4 2 Removing Fin Guard for Heat Exchanger 2 33 4 3 Shield for Horizontal Exhaust
14. 5 6 5 Remote Controller Test Run Settings J J 5 12 6 Caution for Pump DOWTLiI uu rn une nean a nno aswa wawa wau EE EEUU ARR RR KR 5 12 7 Meaning of Alarm Messages T T 5 13 Test Run 1 Preparing for Test Run 1 Preparing for Test Run Before attempting to start the air conditioner check the fol lowing 1 The control wiring is correctly connected and all electrical connections are tight 2 The transportation pads for the indoor fan have been removed If not remove them now 3 The power has been connected to the unit for at least 5 hours before starting the compressor The bottom of the compressor should be warm to the touch and the crank case heater around the feet of the compressor should be hot to the touch Fig 5 1 4 If only 1 outdoor unit is installed close the service valve on the balance tubes and open the service valve on the other 3 tubes suction discharge and liquid tubes Fig Fig 5 1 5 2 If 2 or 3 outdoor units are installed open the service valves on all 4 tubes suction discharge liquid and bal ance tubes Fig 5 2 b Request that the customer be present for the trial run Explain the contents of the instruction manual then have the customer actually operate the
15. 96 Extension indoor units 1 LG LD LE1 LE2 LF Elevation difference H 16 4 ft Elevation difference H 16 4 ft 36 18 09 36 36 18 LH 48 18 18 Design of 32WAY VRF SYSTEM 2 System Design Additional refrigerant charge before extension diameter A per 1 ft oz ft B Lb 93 8 65 6 0 602 39 501 062 X 5925 12 n 98 029 2 4 13 98 02 2 4 7 98 092 5925 s ___ 0 279 2 746 0 279 3 661 Total oz 296 775 Additional refrigerant charge after extension Liquid tube Tubing length ft Additional refrigerant charge A x B oz diameter A per 1 ft oz ft B Total oz 43 934 Calculation of additional refrigerant charge for the entire 3WAY system Additional refrigerant charge for entire 3WAY VRF system Refrigerant charge at outdoor unit Additional refrigerant charge 881 341 1222 oz after extension Before extension 458 297 755 oz Remark When planning an extension model be sure to include the values of the Table 2 1 1 Page 2 5 Necessary Amount of Refrigerant Charge per Outdoor Unit _ Design of 32WAY SYSTEM 2 System Design Always check the gas WARNING density limit for the room in which the unit
16. S108NAS 114183530 S108WAS 9NI 1002 2 ONILVSH LINO YOOCLNO ZO ATIVE Ada 2 84 IA8d 20 ZAIG LAJA AGH EAIS ZAIS 1408 JAYS EHI ZHISIG exa 1 zexa 19 3 uiv 810N2 901N2 100N2 dr 31719 TWNIWYSL LINA ans LINA ZIOA 4 11 1 LEET 04818 1 918195161 111 1 2 22081025 88 2131 CELI EEEO LEEI 11812181110 880 1 21 ggg i ZLO v10AH PLO EHe 1 1119 2119 323H29 d N Y 00 c6 0Sc8 C V 38 8000100 Ol 000 OL 3ILVN3H2S dr 3lV ld JAVNIWH3L PCB and Functions Contents 7 PCB AND FUNCTIONS 1 Outdoor Unit Control PCB J 7 2 1 1 Outdoor Unit Control PCB 709663 7 2 1 2 Outdoor Unit Filter PCB FIL CHDX14053 7 3 1 3 Outdoor Unit HIC Board HIC CHDX14053 7 3 1 4 Functions for CR CHDZ09663 7 4 2 Indoor Unit
17. 1105515 434713 08 08 1119815 1081 03 SOT1XQH2 114 Y0L13YdY3 2114108125313 3unsS3ud 120 110 4 00 200AU 3572 30010 390148 LIN 102 002 v4 03LYY3d0 HOLOM H3M d 8 3unsS3Hd 3510 Z LAON 1041802 1NVH3DIHJ3H NOILINS 4 SSVvdA8 Ad8 LADA ADU LAIS SAWA JAYS YOLOW 4000110 YOLOW H0SS3HdNOD am JAYS 013 10118143530 5708 5 10114143530 S 108AAS ____ 053 51085 9NI 1002 9NIIV3H LINA Liek 046181 1915191612131 450 450 veg 862 462 550 550 mem emm mmm HO 562 080 090 wed 7 10 N3 800 1600 20 dv 3lV d NNI WH3I LINA ans 1180 DL BODON OL Schematic Diagram U 72MF1U9 U 72MF1U9E OI LVYWAHOS LL9 08 8 c V 38 22281228 As en ELH ZIOA 250 952 555 952 2 9 mnm meg mg E 11082 61048 gt 1 210 VLOAW 1 PLO LLOAY 333H3 NOI1dlu2S30 S 108NAS 8000110 geese dv 3lV d WNIWH3I Electrical Data 1 Outdoor Uni 2 Electric Wiring Diagram U 96MF1U9 U 96MF1U9E
18. 2 the number of outdoor units on the outdoor main unit control PCB set the No of outdoor units DIP switch 5006 to ON ON aa 3 units 1 23 OFF 3 Onthe outdoor main unit control PCB check that the system address rotary switch 8002 is set to 1 and that the DIP ON ON switch S003 is set to 0 These are the settings at the time of factory shipment 1 2 OFF 4 Tosetthe number of indoor units that are connected to the outdoor unit to 13 on the outdoor main unit control PCB set the ON ON No of indoor units DIP switch S005 to 1 g and set the rotary switch 5004 to 3 1 2 3 OFF 5 Turn on power to all indoor and outdoor units in the system 6 Short circuit the automatic address pin at the outdoor main unit CN100 for 1 second or longer then release it Communication for automatic address setting begins 1 To cancel again short circuit the automatic address pin 100 for 1 second longer then release it The LED that indicates automatic address setting is in progress turns OFF and the process is stopped Be sure to perform automatic address setting again Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF l 7 Next turn the power ON only for the indoor and outdoor units of the next different system Repeat steps 1 5 in the same way
19. I3 e Voltage rating V 230 43 2 Cooling kW 15 5 i k 5 5 33 UNIT DIMENSIONS c 7 A 90 2 A 47 3 Heating W 17 2 91 2 Starting 160 COMPRESSOR Type Q ty Inverter driven Rotary type x 1 Fixed Speed Scroll type 1 Fixed Speed Scroll type x 1 kW 2 7 3 75 1 96 7 4 liters 1 96 7 4 liters 25 32 25 32 Ibs kg R410A 25 9 11 8 Defrost method Heat exchanger FAN DEVICE E k l Propeller fan x 1 CFM 5 650 kW 0 7 8P TUBING S y 7 8 022 22 Brazing Refrigerant t bing in mm 05 8 015 88 Brazing Balance tube in mm 03 8 09 52 Flare nut PE eG al ew ees TL Cooling 14 113 F DB Heating 4 59 WB Operation sound Hi Connection tubing Connection tubing 01 18 028 58 03 4 019 05 21 1 8 028 58 03 4 019 05 Primary accessories 07 8 922 22 23 4 019 05 07 8 022 22 03 4 019 05 5 8 Motor output Type Refrigeration oil Charge amount Crankcase heater Capacity control Refrigerant amount at shipment Refrigerant control p gal 2962 3 03 4 019 05 05 8 015 88 Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Rated conditions Performance electrical characteristics values an
20. NC 5 k m MODEL U 72MF1U9 U 72MF1U9E SOUND LEVEL 54 5 dB A y Cooling Heating Quiet mode 51 5 CONDITION 3 3 ft front at height of 4 9 ft 70 CUM o EN X 3 e 3 8 Sod eS 1 2 sx 40 D NS 30 roximate 5 acis audible limit for continuous 8 20 noise Overall 63 15 2 50 Frequency at center of octave band Hz 3WAY VRF SYSTEM Unit Specifications MODEL U 96MF1U9 U 96MF1U9E SOUND LEVEL dB A Quiet EN 52 0 e Standard mode Cooling Heating CONDITION 33ftinfrontatheightof49f 7777 Quiet mode 70 E 1 1 d ia C S SN B k 2 5 EN A E sa 3 gt 4 5 Approximate tox i NUS S minimum audible m limit for continuous 8 20 nose M 6 Overall 63 125 250 500 1000 2000 4000 8000 Frequency at center of octave band Hz Test Run Contents 5 TEST RUN 1 Preparing for Test Run 5 2 2 Test Run Procedure sen xiii rode caia cx nda dca rur Vie rU DL DID ARX Era a REGERE E QU EVER VEEER UE EEEEXEP MEER KR 5 3 3 Main Outdoor Unit PCB Setting J 5 4 4 Auto Address Setting viisiin d dua CY aS sassa iN KR RE a EUER
21. Bud was 1468 zaoa ms avs SdH Sdl I I 2 8 88 88 88 88 20 3 18 3 128 ZHISIC zo 1110 Bn h Al 3 50000 990000 BORED s I s sl 58 8 SdH Sd1 E m 19 2810 240510 IHOSIQ 710 YAYO 8 Ada 184 1320 2 08 1 28 20 Add LAON ZH IH ong 5 cw 039 one ong mg 039 NYD 13 me 02 UHN mg eng LHW QHD 21318 am 038 zas eng 13 08 1102813 1081NO2 1325 hhi 13 Jug cda am uw rr ene 35 qe me 612 dudes iaeo Udea 1112 212 2 9 5 tou 20 EE RR anan 330 330 9000100 JHL 30 5538009 7 00 466 0848 2 V 48 SLINA 9000110 JHL 30 838101 2005 QuvOS 11103813 1081 03 NO 9 11135 MS 310N 9005 NVYOVIG 9NIJIM 91915313 31 14 dinn 805 3000110 01 MOON OL 31 14 TVNINH3L
22. CZ P224BH1U USE For Indoor unit Capacity after distribution joint is 22 4kW or less Suction Tube Discharge Tube Liquid Tube 210 186 235 G Pen G H H G 4 q HEEF lt A 8 A D H HI Distribution aH Joint gt 41 G 2 1 JTL Hi Reducing f Joints Insulation Insulation Insulation Unit mm CZ P680BH1U USE For indoor unit Capacity after distribution joint is greater than 22 4kW and no more than 68 0kW EE Unit mm Suction Tube Discharge Tube Liquid Tube 590 300 H Ext DEF G FED EM EE BEA HE p IH GFE EFG HI N FE ES C D 340 Vn 7 7 E 2 G Insulation Insulation Insulation Insulators for both the Suction tube and the Discharge tube are the same Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter So the both Distribution joints can fit into different tubes Since the diameter of the tube ends for both Suction and Discharge tube are different take care not to connect the distribution joint different See the marks on the above figures CZ P1350BH1U USE For indoor unit Capacity after distribution joint is greater than 68 0kW and no more than 135 0kW Suction Tube Discharge Tube Liquid Tube H E p IH G
23. S 12MT1U6 S 18MT1U6 S 24MT1U6 Wall Mounted K1 Type S 07MK1U6 S 09MK1U6 S 12MK1U6 S 18MK1U6 S 19MS1U6 S 24MK1U6 Floor Standing P1 Type Concealed Floor Standing R1 Type 21 S 07MP1U6 S 07MR1U6 J S 09MP1U6 S 09MR1U6 S 12MP1U6 S 12MR1U6 2 S 15MP1U6 S 15MR1U6 J S 18MP1U6 S 18MR1U6 I S 24MP1U6 S 24MR1U6 Necessary to install the External Electronic Expansion Valve Kit Optional CZ P56SVK1U Outline of 3WAY VRF SYSTEM 1 Line up Outdoor units Type 72 Capacity BTU h kW 72 000 21 1 Cooling Heating 81 000 23 7 U 72MF1U9 p Air intake U 72MF1U9E intake Maximum dimensions Outdoor Unit 35 intake Ceiling panel dimensions discharge unit in Type 96 Capacity BTU h kW 96 000 28 1 Cooling Heating 108 000 31 6 U 96MF1U9 Air intake U 96MF1U9E 5 Z Air OF V intake NW Maximum dimensions Ceiling panel dimensions discharge Outdoor Unit unit in Outdoor unit model name ended with letters Refer to the Section 1 Salt Air Damage Resistant Specifications 1 3 2 Features of SYSTEM 2 1 Outline of 3WAY SYSTEM System example
24. o The heating capacity when frost defrost operation is considered is calculated by multiplying the heating capacity found from the capacity graph by the correction coefficient from the table above W 8 Ton 130 5 8 100 N ratio 828388 Indoor air in Design of 32WAY VRF SYSTEM ake temp F DB UD oss 0 95 1 0 Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Rated performance values Cooling capacity Power consumption Heating capacity Power consumption BTU h CET kW BTU h kW kW 1 10 Capacity Correction Graph According to Tubing Length and Elevation Difference Capacity change characteristics lt Cooling gt Base capacity 92 90 88 86 84 82 80 78 76 4 change rate wo a e e Elevation difference ft 8 131 l 1 1 310 33 66 98 Equivalent length ft lt Heating gt Base capacity change rate 5 9 9 a k O Elevation difference ft 1 1 1 1 1 1 1 E 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492 Equivalent length ft NOTE The positive side for the elevation difference indicates that
25. is blinking CODE 5 11 4 Auto Address Setting 5 Remote Controller Test Run Settings 6 Caution for Pump Down Request concerning recording the indoor outdoor unit combination Nos After automatic address setting has been completed be sure to record them for future reference List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location next to the nameplate using a permanent marking pen or similar means that cannot be abraded easily Example Outdoor 1 Indoor 1 1 1 2 1 3 Outdoor 2 Indoor 2 1 2 2 2 3 These numbers are necessary for later maintenance Please be sure to indicate them Checking the indoor unit addresses Use the remote controller to check the indoor unit address If 1 indoor unit is connected to 1 remote controller 1 Press and hold the button and T button for 4 seconds or longer simple settings mode 2 The address is displayed for the indoor unit that is connected to the remote controller Only the address of the indoor unit that is connected to the remote controller can be checked 3 Press the button again to return to normal remote controller mode If multiple indoor units are connected to 1 remote controller group control 1 Press and hold the button and T button for 4 seconds or longer simple settings mode 2 ALL displayed on the remote controller Nex
26. 5 F alarm 6 L alarm N Alarm No Example LED 1 blinks 2 times then LED 2 blinks 17 times The cycle then repeats Alarm is P17 Blinking Possible cause of malfuncti Alarm ossible cause of malfunction message Serial Remote controller is detecting Error in receiving serial communication signal communication error signal from indoor unit Signal from main indoor unit in case of group control lt E01 gt errors Ex Auto address is not completed Mis settin 3 Error in transmitting serial communication signal E02 Indoor unit is detecting error signal from remote controller and system controller lt lt E03 gt gt Indoor unit is detecting error Error in receiving serial communication signal signal from main outdoor unit When turning on the power supply the number of connected E04 indoor units does not correspond to the number set Except R C address is 0 Error of the main outdoor unit in receiving serial communication signal from the indoor unit lt E06 gt Improper setting of indoor unit or Indoor unit address setting is duplicated E08 remote controller Remote control address connector RCU ADR is duplicated ipo lt lt E09 gt gt Duplication of main remote controller During auto address setting Starting auto address setting is prohibited number of connected units does This alarm message shows that the auto address connector CN100 E12 not correspond to number set is shorted while
27. 6 8 U 72MF1U9 U 96MF1U9 5 U 72MF1U9E U 96MF1U9E 5 S ale 12 OO se els zle Top view 14 O E E 8 gt 16 OO ZN 31 1 8 7 7 8 31 1 8 Installation hole pitch 70 1 8 nstallation hole pitch Installation hole pitch MS 2L N lt N Left side Front view Right side 113 Ceiling panel dimensions Equivalent 35 4 35 4 35 tonnage 6 Ton 8 Ton Ceiling panel dimensions Ceiling panel dimensions U 72MF1U9 U 96MF1U9 md gt U 72MF1U9E U 96MF1U9E 5 5 18 Ton sx sx Top view 20 Ton OO 59455 gt 5 22 s 5 24 Ton _ 31 18 _ _ 7 7 8 _ 31 1 8 7 7 8 _ 31 18 Installation hole pitch Installation hole pitch Installation hole pitch 109 1 16 Installation hole pitch 41 Left side 82 9 16 74 1 16 31 19 64 4 13 re Front view Right side 3WAY VRF SYSTEM Unit Specifications 1 Outdoor Unit Position of center of gravity U 72MF1U9 U 96MF1U9 MODEL U 72MF1U9E U 96MF1U9E 15 3 8 13 1 4 _ _ SE X 836 gt 5 2 8c o S 5 1784 18 7 8 5 218 2 452
28. 015 88 1 99 03 4 219 05 2 78 07 8 022 22 3 93 Table 2 6 Indoor Unit Tubing Connection Size 11 40 Unit in mm Indoor unit type 7 9 12 15 18 19 24 36 48 54 Distribution Suction tubing 05 8 015 88 joint solenoid Discharge tubing 91 2 912 7 valve kit tubing iquid tubing 03 8 09 52 Solenoid valve Gas tubing 91 2 012 7 05 8 015 88 kit Indoor unit tubing connection Liquid tubing 01 4 06 35 03 8 09 52 1 For the solenoid valve kits use type 160 with parallel specifications Branch the tubing before and after the solenoid valve kits Table 2 7 Refrigerant tubing Existing tubing can be used Tubing size in mm Material O Material 1 2H H 91 4 06 35 t1 32 10 8 03 8 09 52 t1 32 t0 8 01 1 8 028 58 15 128 t1 0 01 2 012 7 13 64 11 1 05 8 015 88 15 128 11 0 o1 1 2 938 10 over t3 64 t1 15 t1 32 t0 8 01 1 4 031 75 03 4 019 05 over 15 128 11 0 1 5 8 041 28 over t3 64 t1 20 07 8 022 22 15 128 11 0 When bending the tubes use bending radius that is at least 4 times the outer diameter of the tubes In addition take sufficient care to avoid crushing or damaging the tubes when bending them Design of 32WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 5 Installation Standards Relationship between A C units and refrigera
29. NN 6 SN 2 52952515 sx 5 g 2 E gt 5 31 1 8 17 718 _ 31 1 8 7 7 8 31 1 8 Installation hole pitch Installation hole pitch Installation hole pitch Le 109 1 16 Installation hole pitch view Unit in Outdoor unit model name ended with letters U9E Refer to the Section 1 3 Salt Air Damage Resistant Specifications 1 5 Outline of 3WAY VRF SYSTEM 2 Features of SYSTEM Capacity control The compressor combination DC inverter compressor constant speed compressor allows smooth capacity control from 0 6 Ton to 24 Ton Realization of smooth capacity control In case of 24 Ton system from 0 6 Ton to 24 Ton Capacity Ton Capacity control is possible smoothly with a DC compressor The right graph shows the 20 ci image of the operating combination of compres Lae sors in case of 24 Ton system In actual operation 16 e the combination will be changed by operating 12 DC1 DC2 DC3 condition operating time amount priority of com 8 DC2 DC3 AC1 pressor and so on DC2 DC3 AC1 AC2 4 DC1 DC3 AC1 AC2 AC3 DC2 Comp HP Unit1 main Unit2 sub1 Unit3 sub2 24 Ton U 96MF1U9 U 96MF1U9E Type x 3 Unit 2 Unit 3 DC2 AC2
30. Outline of 32WAY VRF SYSTEM If indoor outdoor units need servicing a ball units to let other units stay running System limitations valve field supply cuts off non operational T d N 7 7 Since all pipings are concentrated Ld tea CONCENTRATION into one pipe shaft you can minimize KER piping space and construction labor gt gt i i 4 r2 bd L gt lt E 34 Panasonic makes it possible to link outdoor unit together for a large capacity 24 Ton N Solenoid 4 zi Pad at 421 valve kit Indoor unit Maximum number of combined outdoor units 3 Maximum tonnage of combined outdoor units 24 Ton Maximum number of connectable indoor units 40 Indoor outdoor unit capacity ratio 50 130 Maximum actual piping length 492ft Maximum level difference when outdoor unit is lower 164 131 ft Maximum total piping length 984 ft ADDITION If your indoor capacity load changes in the future it s easy to add
31. Securely affix the 3 way wiring harness with the remote control wiring U1 type Power wiring field supplied Connection for Clamping Solenoid Valve Kit clip for 7 e d A Remote control wiring Remote control wiring and Inter unit control wiring field supplied Conduit LL and Inter unit control wiring field supplied Conduit field supplied D A Earth screw Power wiring field supplied Conduit field supplied Clamping clip Clamping clip Earth screw Power wiring field supplied Remote control wiring and Inter unit control wiring field supplied Connection for Solenoid Valve Kit for 3WAY 2 28 3 Electrical Wiring Important Note When Wiring for Common Type Continued Design of 3WAY VRF SYSTEM E1 T
32. 026 g dE cise 6190 1 8 03 1 107 S 123 C094 FUSE BOOT 0155 5 O Oo 2001 1 JP010 WHT 5007 mni m e 16104 st 100 c I oa or e T Se Es 102 8 8 E E ue gt a Ls qh dm i E i x lt 2002 Ter 2 095 5 99 g _ g PDV 012 3 z a VA006 i og 0122 888 b 12 34 1620 1 xol 2 16018 300 EA 2008 RED site x r j WHT DT 00 2 4 RY012 Wu w m 01020 CN300 P D m SAVE cnos2 7003 5 es D CN028 3 m 6 2006 228 WHT 5 5 8 s 5 RED 5 E RYOIS 5 x ge 02 2 GND 4 8 Z GND Le 3 g 2 80 S UEB UR T SNOW cm 5 TE 9 022 o2 035 025 o 5 8 gt RY019 fos e 5 s E 2 959 a3 2 1 E 5 g 5 c 3 a 14 2 un g 5 01625 4 og 3 202 SWR 5013 925 BLK 8 B z Tes amp 87 1629 1627 MESE St 1 e o w oq ISI IS 2 z z zu I L 8 L AC IN 2 1 e D 2005 I l 1 x x lt
33. 03 4 219 05 1 Brazing 05 8 215 88 Brazing 03 8 29 52 Brazing 03 8 09 52 Flare nut Refrigerant tubing 3 3 3 3 5 a S 3 Drain port External air temperature operation range Operation sound Hi Cooling 14 113 F DB Heating 4 59 WB 54 5 Quiet mode 51 5 Connection tubing 97 8 022 22 93 4 019 05 Primary accessories Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications 1 If the size of tubing LA is less than 16 4 feet it is recommended that the tubing diameter be larger than 97 8 022 22 Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 2 3WAY VRF SYSTEM Unit Specifications 1 Outdoor Unit Unit Specifications 2 3WAY SYSTEM Control Outdoor Unit lt 8 gt U 96MF1U9 U 96MF1U9E PERFORMANCE 1 O BTU h kW Heating capacity 108 000 31 6 82 9 16 2097 Ceiling dimension 35 5 3 55 UNIT DIMENSIONS 3 c Net weight kg 672 305 Color Munsell code Silky shade 1Y 8 5 0 5 ELECTRICAL RATINGS a on 230 Power factor
34. 113 Ceiling panel dimensions 4 35 4 Ceiling panel dimensions 35 Ceiling panel dimensions 35 Ceiling panel dimensions 36 1 4 Installation hole pitch 37 1 2 Maximum dimensions 31 1 8 Installation hole pitch 109 1 16 Installation hole pitch Top view Unit in Fig 2 8 31 1 8 Installation hole pitch 7 7 8 7 7 8 Design of 3WAY VRF SYSTEM 4 Installation Instructions 4 2 Removing Fin Guard for Heat Exchanger After installation of the outdoor unit detach the fin guard for heat exchangers as following steps 1 Cutoutthe fin guard entirely attached to the panel and remove it from the outdoor unit Pay careful attention not to damage the fin when cutting out the fin guard 2 If there is a case where easy to touch the sharp aluminum fin of the outdoor unit be sure to attach a snow proof ducting to the unit It is recommended that the outdoor unit be located away from the touched with hands 4 3 Shield for Horizontal Exhaust Discharge It is necessary to install an air discharge chamber field supply to direct exhaust from the fan horizontally if it is difficult to provide a minimum space of 7 ft between the air discharge outlet and a nearby obstacle Fig 2 9 In regions with heavy snowfall the outdoor unit should be provided with a solid raised platform and snow proof ducting field supply Fig 2 10 4 4 Installing the Outdoor Unit
35. 2 tt co L 40 87 9 l Tk XL LE XC Front view Right side view Front view Right side view Note Can be installed so that the air direction is to the front right left or rear direction 3 unit installation 113 35 35 35 4 4 31 1 8 28 Top view Before installation of snowfall protection duct Snowfall protection duct Board Field supply Snowfall protection duct Field supply Field supply unit in e 5 5 I T T 35 Ceiling panel dimensions Ceiling panel 9 1 2 9 1 2 Board e 2 1 8 7 8 Air discharge chamber Field suppl Air discharge chamber Field supply ply Field supply y Air discharge chamber Field supply Snowfall protection Snowfall protection duct Field supply duct Field supply 191 3 Snowfall protection duct IA Field supply 23 lt 22222 22 g 8 1 8 8 8198 541 ro y St ue Right side view Front view
36. 3 Salt Air Damage Resistant Specifications Specifications Relevant Parts Outer box side plate drain pan between the stud Material Hot dip zinc coated steel sheet Standard Specifications Polyester powder double coating both sides 240 Outline of 32WAY VRF SYSTEM Salt Air Damage Resistant Specifications Outdoor unit model name ended with letters Polyester powder double coating both sides 2120 Base frame Hot dip aluminum zinc coated steel sheet No treatment Polyester powder double coating both sides Z1204 m Fan guard Resin Polypropylene No treatment No treatment Fin Aluminum No treatment Zinc rich treatment Tube Copper No treatment Zinc rich treatment whole Heat Exchanger Tube plate Hot dip zinc coated steel sheet No treatment Zinc rich treatment whole Propeller fan Resin No treatment No treatment Aluminum No treatment Urethane coating gt 304m Hot dip zinc coated steel sheet No treatment Urethane coating 2 304m Motor Motor maker s standard spec Motor maker s spec for salt air damage resistant urethane coating Installation frame Hot dip zinc coated steel sheet Polyester powder double coating both sides 2120 Polyester powder double coating both sides Z1204m Electrical component box Hot dip zinc coated steel s
37. 481 88 29 3358 30 1 4 We olor 5 853 767 222220 2 Weight 573 683 zx ibs k 260 310 A e 8 s kg 260 310 2 2 31 1 8 Installation hole pitch Op 35 Ceiling panel dimensions 8 1 2 82 9 16 74 1 16 D 5 N y Right side 31 7 64 34 9 16 Front view unit in 3WAY VRF SYSTEM Unit Specifications 1 Outdoor Unit 1 5 Refrigerant Flow Diagram U 72MF1U9 U 72MF1U9E Solenoid High pressure switch valve HP a INV LPS Low pressure sensor To be brazed pinch after oil is inserted 1 portion Thermistor position Oil separator Y Accumulator Oil drain Balance tube Pal 93 8 flare connection 281 Solenoid valve D B Strainer N lt Suction tube 03 4 Brazing For LP zt zt a Hes High Pressure sensor For HP s Discharge tube 1 05 8 Brazing he 2 2 Narrow tube away 03 8 Brazing pe Solenoid Solen
38. move the sockets to the side system 1 setting 13 units setting 8002 S003 S004 x77 ON ON OFF 8005 ON b No 2 sub unit No 3 sub unit No of S006 Unit S007 i Unit outdoor units ON Unit S007 S007 8 units E Pd Lr T number oN 1 1 UN setting 23 i setting 9 seung M OFF unit No 1 1 2 OFF untNo 2 2 OFF unit No 3 1 2 3 OFF i Leave the socket that Outdoorunit Unit o 22 Unit system 1 No 1 is used to short circuit No 3 Main the terminal plug Inter outdoor unit Sub CN003 control wiring Inter unit control Inter outdoor unit control wiring Indoor unit 1 1 1 2 1 3 1 13 Remote 1 Remote control T communication wirin controller g No 2 Neo 1 main unit settings Refrigerant System address No of indoor units circuit system 2 setting 9 units setting 3002 S003 S004 ON ON m 2 OFF S005 ON ON a _ 2 sub unit settings No of S006 Unit Unit S007 outdoor N ON number 1007 ON number ON ON units 2 units Bg setting EP a 9 setting N 9 setting 1 2 3 QFF unit No 1 Li OFF u
39. setting switch a Use caution when making the settings S007 1 The unit with the unit No set to 1 is If there are duplicated system addresses mnn unit All other units are sub or if the settings for the Nos of the indoor Outdoor unit control gt Y units are not consistent an alarm will Unit No setting switch Set the No of outdoor units occur and the system will not start S006 Y These settings are not made on the Outdoor unit control gt Set the No of indoor units indoor unit PCB Unit No setting switch S004 and S005 re the inter unit control wires connecte NO CASE 1 Check the link wiring to more than 1 refrigerant system Outdoor unit control PCB Unit No setting switch Set the system address S002 and S003 Y Note It is not necessary to remove Refer to Fig 5 4 When multiple outdoor main units exist disconnect the terminals the socket that is used to extended from the shorted plugs CN003 at all outdoor main unit short circuit the terminal plugs PCBs except for 1 Alternatively move the sockets to the OPEN side from the outdoor sub unit PCBs Is it possible fo turn ON the power only for the 1 refrigerant YESLCASE 2 system where the test run will be gt Y performed NO Turn ON the indoor and outdoor unit power for that refrigerant system only Y Will automatic address E Make necessary corrections Short circuit the automatic address be
40. the outdoor unit is installed at a higher position than the indoor units The negative side indicates the opposite 1 1 1 1 1 1 1 1 131 164 197 230 262 295 328 361 394 427 459 492 1 Sample calculations System 8 Ton 164ft equivalent length 49ft elevation difference The cooling capacity and heating capacity for this system are found as shown below e Cooling operation From the graph the base capacity change rate is found to be 92 0 96 000 BTU h x 92 0 88 320 BTU h 28 1kW x 92 0 25 8kW Capacity change rate is 92 0 Cooling capacity is 88 320 BTU h 28 1 kW e Heating operation From the graph the base capacity change rate is found to be 97 2 Because the calculation result exceeds 97 2 the capacity change rate is 97 2 108 000 BTU h x 97 2 105 000 BTU h 31 6kW x 97 2 30 7kW Heating capacity is 105 000 BTU h 30 7 kW Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator m If the maximum tubing length L1 exceeds 295 ft equivalent length increase the tubing size of the main liquid gas tubes LM by one rank However the upper limit for the gas tube size is e1 3 8 m Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths Refer to Table 2 11 to increase the tubing size However the maximum allowable tubing length must not be exceeded The amount of additional refrigerant charge is determined from the liquid tube size on
41. 1 96 7 4 liters 25 32 25 32 Ibs R410A 25 9 11 8 R410A 25 9 11 8 Electronic expansion valve Reverse cycle defrost outdoor unit cycle defrost Aluminum plate fin Copper tube FAN DEVICE Air circulation CFM 5 650 5 650 5 650 in WG qa 2 10 0 7 8P Protective devices TUBING 2 2 C O in mm 1 1 4 931 75 Brazing in mm 01 1 8 928 58 Brazing in mm in mm A a 4 1 F Connection tubing Connection tubing Connection tubing 01 18 028 58 03 4 019 05 01 1 8 028 58 03 4 019 05 01 1 8 028 58 03 4 019 05 07 8 022 22 03 4 019 05 078 022 22 03 4 019 05 07 8 022 22 03 4 019 05 03 4 019 05 05 8 015 88 03 4 019 05 05 8 015 88 03 4 019 05 05 8 015 88 Primary accessories o UJ Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 10 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1 2 AHRI Registration Values HI Low Heating Heating Low COP Capacity Capacity BTU h B
42. 3 3 Discharge tube Liquid tube 5 3 3 Refrigerant tubing 5 m 3 333 3 5 Mi Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 4 3WAY VRF SYSTEM Uni i j 1 Outdoor Unit WAY VRF SYS Unit Specifications Unit Specifications 4 PERFORMANCE 2 ee Cooling capacity BTU h kW Heating capacity BTU h kW in in 5 5 33 UNIT DIMENSIONS Ceiling dimension 35 2 3 8 n 890 60 Net weight kg 573 260 672 305 Color Munsell code ELECTRICAL RATINGS w NEUES enl Voltage rating 230 mm c 2 35 8 Cooling 13 1 91 6 39 1 Heating 14 4 92 3 A 152 COMPRESSOR Inverter driven Rotary type x 1 Type T Ped Speed Sero ype x Motor output kW 4 1 2 7 3 75 Refrigeration Type 5 g 1 40 5 3 liters 1 96 7 4 liters Crankcase heater W 25 32 Capacity control Pp wy l Refrigerant amount at shipment Ibs kg R410A 25 9 11 8 Refrigerant control Defrost method Heat exchanger Aluminum plate fin Copper tube FAN DEVICE aS ee Type Q ty Propeller fan x 1 Air circulation CFM 5 650 External static pr
43. 72MF1U9E U 96MF1U9 U 96MF1U9E unit in mm Air unit iri U 72MF1U9 U 96MF1U9 Vs U 72MF1U9E U 96MF1U9E 6 8 8 15 8 0 Refrigerant tube gas tube brazed connection 3 4 019 05 7 8 022 22 5 8 Refrigerant tube discharge tube brazed connection 5 8 015 88 3 4 019 05 gt i a 3 Refrigerant tube liquid tube brazed connection 3 8 09 52 3 8 09 52 Air Air 58918015 4 Refrigerant tube balance tube flared connection 3 8 09 52 3 8 09 52 intake intake gt E Installation holes 4 19 32 x 25 32 elongated holes anchor bolts M12 or 15 32 or larger 6 Refrigerant port front knock out hole and slit m ET Y 7 Refrigerant port bottom slit hole intake Ney view Electrical wiring port front 02 23 64 01 7 64 knock out holes for conduit connection 31 1 8 7 9 Electrical wiring port 22 23 64 o1 1 2 knock out holes for conduit connection piten 40 Pressure outlet port for high pressure 5 16 07 94 Schrader type connection Ceiling panel dimensions 4 Pressure outlet port for low pressure 95 16 07 94 Schrader type connection 42 Knock out hole for connecting pressure gauge optional Air 4 discharge 8 1 2 82 9 16 74 1 16 22988 S
44. 92 8 90 2 A Heating kW 8 60 91 2 N 136 COMPRESSOR O KW Inverter driven Rotary type x 1 Fixed Speed Scroll type x 1 W ibs kg FANDEVCE 77 00 nwa KW Protective devices High pressure switch overcurrent CT method TUBING _ _ Suction tube 07 8 022 22 1 Brazing Discharge tube 03 4 219 05 Brazing Liquid tube 03 8 09 52 Brazing in 100121 F Operation sound Hi dB A 55 0 Quiet mode 52 0 Connection tubing 1 1 8 028 58 93 4 019 05 97 8 022 22 93 4 019 05 93 4 019 05 95 8 015 88 Refrigeration oil 1 96 7 4 liters 8 0 Refrigerant tubing gt 5 8 3 5 35 3 3 Primary accessories Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications 1 If the size of tubing LA is less than 16 4 feet it is recommended that the tubing diameter be larger than 1 1 8 028 58 Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 3 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specificati
45. 98 96 9 98 S 66 9 5 66 33100 96 1 5 0 5 0 _ S anal T 33 nE 66 98 98 131 131 1 1 1 1 1 1 1 1 1 1 1 1 L L L 1 1 1 Ll I 1 l 1 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492 0 33 66 98 131 164 197 230 262 295 328 361 394 427 459 492 Equivalent length ft Equivalent length ft The positive side for the elevation difference indicates that the outdoor unit is installed at a higher position than the indoor units The negative side indicates the opposite The capacity loss that is caused by the tubing length can be reduced by increasing the sizes of the discharge tubes and suc tion tubes Refer to Table 2 9 and make the appropriate changes However be sure that the total length does not exceed the maximum The only sizes which can be increased are the LM main tube with the largest diameter gas tubes and the changes are limited to those shown in Table 2 9 In addition note that the additional refrigerant charge is determined only by the narrow tube size Table 2 9 Equivalent Length Correction Coefficient when the Size of the Discharge Tubes and Suction Tubes LM is Increased Standard tubing diameter 91 2 g5 8 93 4 97 8 1 1 8 gas tube in mm 612 7 015 88 219 05 922 22 028 58 Tubing diameter after change 05 8 03 4 07 8 1 1 8 01 3 8 gas tube in mm 015 88 019 05 022 22 028 58 034 92 Equivalent length correction coe
46. Control PCB Switches and Functions Refer to the 2WAY SYSTEM TECHNICAL DATA TD831157 PCB and Functions 1 Outdoor Unit Control PCB 1 1 Outdoor Unit Control PCB CR CHDZ09663 S002 S004 A ADD CN100 pin OAC CN105 pin MODE CN101 pin AP CN102 pin Alarm LED LED1 2 STOP CN104 pin CHK CN023 pin RUN CN103 pin S006 TEST CN022 pin Terminal plug S010 EMG CN002 plug Control circuit fuse F003 S007 OC CN001 plu Low pressure sensor memory IC RC CN006 plug IC018 High pressure sensor RC1 CN106 plug Outdoor air temp Comp discharge 3 temp Gas temp sensor at heat exchanger 1 2 Comp discharge 2 temp Comp discharge 1 temp Liquid temp sensor at heat exchanger 1 2 CT2 CT3 Power LED D53 Gas temp and Liquid temp sensor at heat exchanger 3 CTL1 CTL2 Oil detection sensor Suction temp rtt ege 4 1121 ii ries i HIC2 HIC1 PCB and Functions 1 Outdoor Unit Control PCB 1 2 Outdoor Unit Filter PCB FIL CHDX14053 7250 D 304 250 14 E 1 3 Outdoor Unit HIC Board HIC CHDX14053 0147 1 2818100700 0 55 PCB and Functions 1 Outdoor Unit Control PCB 1 4 Functions for CR CHDZ09663 Automatic address setting CN100 2P plug white Automatic address setting pin Short circuit this pin for 1 second or longer to automatically set the
47. a service space of 7 7 8 or more in front of the installing site e Never conduct drilling or welding on the sheet metal Place the solenoid valve kit so that it does not hinder draining Service space e Do not cover air holes 7 7 8 or more 3 Valve Dimensions and Hanging Method e There are 2 types of solenoid valve kits type 56 and type 160 The corresponding indoor unit model Solenoid Valve Kit Indoor Unit Capacity CZ P56HR1U 7 18 Type capacities are shown in the table at right CZ P160HR1U 24 48 Type N e Gas tube ID 1 2 5 8 Discharge tube ID 1 2 5 JI Lf 88 sS s PE 3 tube ID 1 4 3 8 N SHE y Liquid tube ID 3 8 Hanging hook Front side Suction tube ID 5 8 Holes for suspension bolt 215 32 5 55 64 4 21 64 4 21 64 5 55 64 K 39 3428 erre SE lop 2 Q N H y 9 Cover of electrical components NOTE unit in This figure shows the unit with suspension fittings attached 2 52 Design of 3W
48. before connecting the power supply conductors to 11 L2 of the terminal block 3 Securely affix the two power supply conductors L1 L2 in the wiring channel by the clamping strap as shown Take care not to damage the control wirings by the clasp Do not leave the control wirings loose Design of 3WAY VRF SYSTEM Connection for Solenoid Valve Kit for 3WAY Remote control wiring field supplied LR Power wiring field supplied field supplied Earth screw Clamping clip Entirely cover the control 22 wirings Remote Inter unit zz 3WAY connection 1 Remote control wiring and Inter unit control wiring field supplied 2 31 4 Installation Instructions 4 1 Selecting the Installation Site for Outdoor Unit AVOID heat sources exhaust fans etc damp humid or uneven locations indoors no ventilation location DO choose a place as cool as possible choose a place that is well ventilated allow enough room around the unit for air intake exhaust and possible maintenance use lug bolts or equal to bolt down unit reducing vibration and noise Installation Space Install the outdoor unit where there is enough space for ventilation Otherwise the unit may not operate properly Fig 2 7 shows the minimum space requirement around the outdoor units when 3 sides are open and 1 side 15 shuttered
49. for outdoor unit 1 Location Install the ball valve at the main tube of the distribution joint Iure darse Outdoor unit for extension Ball valve for extension Distribution joint Planned expansion Balance tube Suction tube Discharge tube Von eS e n Main tube Main tube of distribution joint h Less than 1 3 ft 1 Liquid tube To indoor unit 2 Installation requirements Be sure to install the ball valve up grade to prevent the inadvertent flow of oil Install the ball valve at the shortest distance within 1 3 ft from the main tube If the diameter of the ball valve is smaller than that of the main tube use a reducer or the like to reduce the size of the tubing at that location If the ball valve is installed at the outdoor unit including extension for outdoor unit face the service port of the valve toward the outdoor unit side see above illustration dotted line and allow a distance of over 1 6 ft from the outdoor unit If the ball valve is installed between the indoor unit including extension for indoor unit and the main tube face the ball valve toward the indoor unit side see above illustration dotted line Use a field supply ball valve 2 8 Design of 32WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 6 Straight Equivalent Length of Joints Design the tubing system by referring to the following table fo
50. in Heavy Snow Areas AVOID 22222 In locations where wind blown snow can be a problem snow proof ducting field supply should be fitted to the unit and direct exposure to the wind should be avoided as much as possible Fig 2 11 The following problems may occur if proper countermeasures are not taken Fallen snow Without snow With snow The fan in the outdoor unit may stop running causing the proof ducting proof ducting unit to be damaged Without platform High platform There may be no air flow Fig 2 10 The tubing may freeze and burst The condenser pressure may drop because of strong wind and the indoor unit may freeze 4 5 Precautions When Installing in Heavy Snow Areas a The platform should be higher than the maximum snow depth Fig 2 10 b The 2 anchoring feet of the outdoor unit should be used for the platform and the platform should be installed beneath the air intake side of the outdoor unit c The platform foundation must be solid and the unit must be secured with anchor bolts d When installing on a roof subject to strong wind countermeasures must be taken to prevent the unit from being overturned Design of 3WAY VRF SYSTEM 4 Installation Instructions 4 6 Dimensions of Wind Ducting Reference diagram for air discharge chamber field supply unit in Ceiling panel Ceiling panel 33 1 4 35 1 4 Maximum bracket dimensio
51. outdoor temperature conditions 2 Page 2 13 x Correction coefficient for tubing length and elevation difference 8 Page 2 14 However if the outdoor unit corrected cooling capacity 5 is greater than 10096 then the outdoor unit corrected cooling capacity 5 is considered to be 100 Corrected cooling capacity of each indoor unit 5 Rated cooling capacity for that indoor unit x Correction coefficient for indoor temperature conditions at that indoor unit 2 Page 2 14 x Distribution ratio based on tubing length and elevation dif ference at that indoor unit 3 Page 2 14 However the corrected cooling capacity of each indoor unit is found as shown below If 2 lt 100 and 2 x 3 gt 100 Corrected cooling capacity for that indoor unit 5 Rated cooling capacity for that indoor unit If 2 210096 Corrected cooling capacity for that indoor unit b Rated cooling capacity for that indoor unit x 2 Design of 32WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Heating Outdoor unit corrected heating capacity 5 Outdoor unit rated heating capacity x Correction coefficient for model 1 Page 2 11 x Correction coefficient for outdoor temperature conditions 2 Page 2 15 x Correction coefficient for tubing length and elevation difference 3 Page 2 14 x Correction coefficient for frosting defrosting 4 Page 2 13 However if the outdoor unit corrected heating capacity 5 is greater
52. performed in Heating mode i pin CN100 on the outdoor main unit PCB YES Turn OFF the indoor and for 1 second or longer then release it CASE 3B outdoor unit power Is it OK to start the compressors 15 it OK to start the compressors 1 LED 1 and 2 blink alternately Check the alarm contents about 2 or 3 minutes Turn ON the indoor and Turn ON the indoor and Make necessary i5 outdoor unit power power correction Are LEDs 1 and 2 on the i Short circuit the mode change pin Short circuit the automatic Refer to Table of Self Diagnostic ee PCB OFF CN101 on the outdoor main unit PCB address pin CN100 on the Functions and Description of Alarm Displays YES At the same time short circuit the outdoor main unit PCB for automatic address pin CN100 for 1 1 second or longer Turn OFF the indoor second or longer then release it then release it 3 Y 3 and outdoor unit power Start indoor and outdoor unit Start indoor and outdoor unit cooling operation heating operation Check the alarm LED 1 and 2 blink alternately LED 1 and 2 blink alternately contents 2 A minimum of 5 hours must have passed after the power was turned ON to the outdoor unit NO 8 All indoor units operate in all refrigerant systems where the power is ON Are LEDs 1 and 2 on the outdoor unit PCB OFF Check that test run preparation is OK Do not allow the short circu
53. qoe 39 9 OFF OFF ON 40 0 ON ON ON TENTATIVE
54. same way as for Case 2 Turn the indoor and outdoor unit power ON at all systems To perform automatic address setting in Cooling mode on the outdoor main unit control PCB in the refrigerant system where you wish to set the addresses short circuit the mode change 2P pin CN101 At the same time short circuit the automatic address pin CN100 for 1 second or longer then release it Be sure to perform this process for one system at a time Automatic address settings cannot be performed for more than one system at the same time 1 Communication for automatic address setting begins the compressors turn ON and automatic address setting in Cooling mode begins All indoor units operate To cancel again short circuit the automatic address pin CN100 for 1 second or longer then release it 1 The LED that indicates automatic address setting is in progress turns OFF and the process is stopped Be sure to perform automatic address setting again Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor main unit control PCB turn OFF At the outdoor main unit in the next different system short circuit the automatic address pin CN100 for 1 second or longer then release it 1 Repeat the same steps to complete automatic address setting for all units Operation from the remote controllers is now possible Automatic address setting in Cooling mode cann
55. system 6 Be sure to give the instruction manual and warranty cer e Ci q O D tificate to the customer 7 When replacing control PCB be sure to make all the L same settings on the new PCB as were in use before replacement Balance tube The existing EEP ROM is not changed and is connected Liquid tube to the new control PCB Discharge tube ON Power must be turned ON at least 5 hours before attempting test run Power mains switch Suction tube Fig 5 2 Test Run 2 Test Run Procedure 2 Test Run Procedure Recheck the items to check before the test run Items to Check Before the Test Run 1 Turn the remote power switch on at least 5 hours before the test in order to Have the outdoor sub NO units been connected energize the crankcase heater VEG 2 Turn the outdoor service valves Outdoor unit control PCB cem D 4 locations to the full open positions et the unit address Unit No
56. than 100 then the outdoor unit corrected heating capacity is considered to be 10096 Corrected heating capacity of each indoor unit 5 Rated heating capacity for that indoor unit x Correction coefficient for indoor temperature conditions at that indoor unit 2 Page 2 14 x Distribution ratio based on tubing length and elevation difference at that indoor unit However the corrected heating capacity of each indoor unit is found as shown below If 2 lt 10096 and 2 x 3 gt 100 Corrected heating capacity for that indoor unit b Rated heating capacity for that indoor unit If 2 gt 10096 Corrected heating capacity for that indoor unit 5 Rated heating capacity for that indoor unit x 2 Characteristic graphs are shown on the pages listed above next to each correction item Find each correction coefficient from the appropriate conditions 4 Calculating the actual indoor unit capacity based on the indoor outdoor corrected capacity ratio Calculate the actual capacity of each indoor unit from the values found in 3 for the corrected outdoor unit capacity and the corrected capacity of each indoor unit Cooling capacity Corrected indoor outdoor capacity ratio during cooling Ruc Total corrected cooling capacity of all indoor units in that system Corrected outdoor unit cooling capacity If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of
57. the 3 way connect wire through the eyelet K1 Type For wall mount type K1 type install the solenoid valve relay kit on the wall Important Installation behind the wall or ceiling is required that the maintenance should become capable Solenoid valve relay kit Solenoid valve relay kit Design of 3WAY VRF SYSTEM 7 Optional Parts T1 Type Common use IX 9 8 Only for 3 Way connect E wire fix with clip A Em ge 3 Way wiring connector Model S 12MT1U6 IN S 18MT1U6 14 Solenoid Valve Relay AE 0800 O e Open the knock out hole and install the eyelet 01 3 16 supplied with the indoor unit Then put the 3 way connect wire through the eyelet Model S 24MT1U6 Solenoid Valve Relay Kit Open the knock out hole and install the eyelet 01 3 16 supplied with the indoor unit Then put the 3 way connect wire through the eyelet
58. the time of shipment For details refer to Table 7 4 S010 DIP switch 3P blue Backup operation switch If an INV compressor has malfunctioned turn CT1 ON and Back Up SW ON to operate the outdoor unit using only the constant speed compressor If a constant speed compressor has malfunctioned turn CT2 ON and Back Up SW ON to operate the outdoor unit using only the INV compressor Disconnect the wiring from the constant speed compressor PCB and Functions 1 Outdoor Unit Control PCB Terminal plug 3P plug black For communications circuit impedance matching connecting socket 3P black is attached to the terminal plug at the time of shipment from the factory n the case of link wiring which combines the inter unit control wiring for multiple systems into a single communications circuit leave the connecting socket in place at only one of the outdoor units and move the socket from the SHORT side to the OPEN side at all other outdoor units If multiple connecting sockets are left in place communications trouble will occur LED1 2 LED red x 2 D72 D75 LED 1 and 2 blink alternately while automatic address setting is in progress Display the alarm contents for alarms which were detected by the outdoor unit Power LED LED red Power indicator D53 Indicates the DC 5V power on the outdoor unit control PCB Run 2P plug white Start pin CN103 Short circuit this pin and appl
59. to complete automatic address settings for all systems 8 Operation from the remote controllers is now possible To perform automatic address setting from the remote controller perform steps 1 5 then use the remote controller and complete automatic address setting Refer to Automatic Address Setting from Remote Controller Test Run 4 Auto Address Setting Case Automatic Address Setting in Heating Mode Indoor and outdoor unit power cannot be turned ON for each system separately In the following automatic setting of indoor unit addresses is not possible if the compressors are not operating Therefore perform this process only after completing all refrigerant tubing work Automatic Address Setting from Outdoor Unit 1 Perform steps 1 4 in the same way as for 2 5 Turn the indoor and outdoor unit power ON at all systems 6 To perform automatic address setting in Heating mode on the outdoor main unit control PCB the refrigerant system where you wish to set the addresses short circuit the automatic address pin CN100 for 1 second or longer then release it Be sure to perform this process for one system at a time Automatic address settings cannot be performed for more than one system at the same time Communication for automatic address setting begins the compressors turn ON and automatic address setting in Heating mode begins All indoor
60. unit 2 Corrected heating capacity of each indoor unit In other words the correction coefficient 6 for the corrected capacity ratio is 1 Design of 32WAY VRF SYSTEM 2 System Design 3 Increasing the size of the refrigerant tubing m Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths Refer to Table 2 11 to increase the tubing size However the maximum allowable tubing length must not be exceeded The amount of additional refrigerant charge is determined from the liquid tube size only Table 2 10 Correction coefficient for equivalent length when the size of the gas tube LM is increased Standard tube diameter 01 2 95 8 93 4 97 8 g1 1 8 gas tube in mm 012 7 015 88 019 05 922 22 028 58 Tube diameter after change 95 8 93 4 97 8 g1 1 8 g1 3 8 gas tube in mm 015 88 019 05 222 22 028 58 934 92 Equivalent length correction 0 4 0 5 coefficient When increasing the size of the suction and discharge tubing LM multiply by the correction coefficient from Table 2 11 and calculate the equivalent length for section LM Tubing equivalent length after size increase Standard tubing equivalent length x Equivalent length correction coefficient 2 2 Example of Tubing Size Selection for Extension and Additional Charge Amount Sample calculation for the system below M
61. units operate I Tocancel again short circuit the automatic address pin CN100 for 1 second or longer then release it The LED that indicates automatic address setting is in progress turns OFF and the process is stopped Be sure to perform automatic address setting again Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the main unit control PCB turn OFF Vv 7 Atthe outdoor main unit the next different system short circuit the automatic address pin CN100 for 1 second longer then release it Vv Repeat the same steps to complete automatic address setting for all units Vv 8 Operation from the remote controllers is now possible To perform automatic address setting from the remote controller perform steps 1 5 then use the remote controller and complete automatic address setting Refer to Automatic Address Setting from Remote Controller Test Run 4 Auto Address Setting Case Automatic Address Setting in Cooling Mode Indoor and outdoor unit power cannot be turned ON for each system separately In the following automatic setting of indoor unit addresses is not possible if the compressors are not operating Therefore perform this process only after completing all refrigerant tubing work Automatic address setting can be performed during Cooling operation Automatic Address Setting from Outdoor Unit 8 Perform steps 1 4 in the
62. valve and turn off the vacuum pump Please confirm that the gauge pressure is under 14 7 psig 755 mmHg 5 Torr after 4 to 5 minutes of vacuum pump operation Charging additional refrigerant Use a cylinder designed for use with R410A e Charging additional refrigerant calculated from the liquid tube length as shown in Section Additional Refrigerant Charge page 2 5 using the liquid tube service valve Fig 2 33 e Use a balance or scale to measure the refrigerant accurately e f the additional refrigerant charge amount cannot be charged at once charge the remaining refrigerant in liquid form by using the suction tube service valve with the system in Cooling mode at the time of test run Fig 2 34 e Close the valve on the cylinder containing R410A Finishing the job 1 With a flathead screwdriver turn the liquid tube service valve counter clockwise to fully open the valve 2 Turn the all service valve counter clockwise to fully open the valve 3 Close all stop valves and loosen the Lo knob of the manifold valve 4 Loosen the charge hose connected to all service port then remove the hose 5 Replace all valve caps at all service ports and fasten them securely This completes air purging with a vacuum pump The air conditioner is now ready for a test run 2 46 Pressure gauge Design of 3WAY VRF SYSTEM Manifold valve Liquid Suction tube Outdoor unit Discharge tube L
63. 0811802 i sH rj A 525 UN i H us euis ELI 112 15181818 PEETI 81612141 0081012101819 1 1 Life 316 i H 4i 111111 8 BRRERERE oan i i pH Hh ele amana F Do CET DAMA na 18181 1 038 Do nal 21H G qa 330 3301 330 2 2005 330 NO NO 34014 4008 440 NO 440 1 2005 440 440 NO Y MS SLINA 3000110 JHL 40 5939007 5110 4000 10 JHL 30 838101 BEBE NN ZOOS 9005 ang LIND 5 0 0 429 0848 2 48 QuvOS 1119919 1081 03 NO 11135 MS 310N 9NISIM 318134 3000110 01 YOON OL 1 r Hd C 409 02 062 ATddNS YIMOd Electrical Data 1 Outdoor Uni 390HS 514153573 NV AG 31113 38 AVN 3SIMH3HIO OL LYVIS ANY 430 SUV 8 2 d JHL NO 5 0 371 3 1 TIY NHI JNO2 8 9 d 9NISNVHO NAHM HOLIMS A dddnS YAMOd NIVW AHL 440 wmau B 0 TVNINW831 80123NNO3 HO1SIWH3H1I NINHVWV H3WHO4SNVH1l 1 YOLSIWYSHL Jld dO1VIQV3 ANIS 1V3H 2I IHB8AH 09 08 1119812 JIH 6507 IX0H2 21H 012934
64. 1 1 8 028 58 03 4 019 05 Connection tubing 078 022 22 03 4 019 05 07 8 022 22 03 4 019 05 07 8 022 22 03 4 019 05 03 4 019 05 05 8 015 88 03 4 019 05 05 0 015 88 o 8 Refrigerant tubing gt Primary accessories Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 9 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications 9 288 000 84 4 324 000 94 9 82 9 16 2097 UNIT DIMENSIONS 113 2870 _ id 672 305 672 305 Color Munsell code ______ Silky shade 1Y 8 5 0 5 ELECTRICAL RATINGS V Running amperes Cooling Power input Power factor 208 69 5 23 3 92 8 76 2 230 64 7 23 3 90 2 71 0 I Running amperes Power input 25 8 25 8 Power factor A Type Q ty Inverter driven Rotary type x 1 Inverter driven Rotary type x 1 Inverter driven Rotary type x 1 Fixed Speed Scrolltypex 1 Fixed Speed Scrolltypex 1 Fixed Speed Scroll type x 1 KW Type FV68S Ether oil Charge amount 1 96 7 4 liters
65. 41 99 18 000 59 7 t ling heat BTU h 4 B EHI 56 752 81 36 048 20 3604820 19 410 57 Total corrected capacity of indoor units cooling heating 143 323 59 161 362 40 Ruc 143 323 59 147 532 93 0 971 lt 1 Outdoor unit changes The corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system As a result the actual capacity of Ruh 161 362 40 146 812 33 1 099 gt 1 each indoor unit is less than the maximum load Therefore the outdoor unit is increased by one rank Outdoor unit Room 1 indoor unit 1 Room 2 indoor unit 2 Room 3 indoor unit 3 Room 4 indoor unit 4 Selected model Type Total corrected capacity of indoor units cooling heating 143 323 59 161 362 40 Ruc 143 323 59 168 609 06 0 850 lt 1 Ruh 161 362 40 173 189 02 0 932 lt 1 2 18 96 96 Type 54 Type 36 Type 36 Type 18 Load cooling heating BTU h Rated capacity cooling heating BTU h Ped 2 poen bed 5 Corrected 7 Actual capacity cooling heating BTU h bed 2 System Design Indoor unit changes Design of 3WAY VRF SYSTEM The indoor unit in room 4 where the corrected indoor unit capacity is less than the maximum load is increased by one rank Outdoor
66. 5 8 a m OUR QON WT LOU i 4 2 8 12 18 2 DB gU 29 ae _ og lO 007 rei Re 33885007 EU RE 1005 77 032 051 057 8 8 s 2 388 TF 4 ae 029 03 056 gt 8 8 B 8 1032 g 117 5 8 e lt 8 1635 mm E 5 5 555 CX agg gt 8 08022 20 aios 2 885 888 8 072 SD SS Qn L L e amp 2 5 Cg TEST CK G o 5 Se x 1624 0221 t 8 2897 ae 038 Log ors SCT SUB_COOL hps aN LPS 45 om WD 228 om BEN 08009 gp WH RUN STOP amp Li 2 8 5 C173 C166 Ej aer 1621 3 Ar 01033 00082 UN QD Loot L021 me amp 8 2 8 400 E 8 1020 8 ciao 2 w gt C228 5 85 2 CI28 CN096 4 e8 2 0164 WHT 5 amp 12 5 gt 2 10106 227 CN200 IC34 2 106 8 5003 5002 8 109 E 129 JP030 E 8 E LS 102030 NO OF I U 10105 C222 88 em E iuao anh O 5 gat ot B his Q8 85 NP EE 5005 RED 5004 5 28 i _ x m T F 0 U ADD N0 0F 0 U Cont 4 ar amp 058 WB E N
67. 8 size is selected based on the table of main ne 91 1 8 01 1 8 o1 1 8 tube sizes after the branch Tubing size Discharge tubing 028 58 028 58 028 58 E f f f 03 4 03 4 03 4 2 Ifthe total capacity of the indoor units con Liquid tubing 019 05 019 05 019 05 nected to the tube ends is different from the total capacity of the outdoor units then the Table 2 4 Outdoor Unit Tubing Connection Size 2 main tube size is selected based on the total BTU h 72 000 96 000 capacity of the outdoor units kW 21 1 28 1 For LA LB and LF in particular 4 o7 g Suction tubing 219 05 022 22 Brazing connection Disch 05 8 03 4 Ischarge 015 88 019 05 tubing Brazing connection 1 If the size of tubing LA is less than 16 4 feet 09 52 09 52 it is recommended that the tubing diameter be Liquid tubing 2919 10935 es larger than 97 8 022 22 Flare connection 2 the size of tubing LA is less than 16 4 feet 93 8 09 52 it is recommended that the tubing diameter be Balance tubin g Flare connection larger than 91 1 8 028 58 Unit in mm 2 6 1 Model Selecting and Capacity Calculator Table 2 5 Amount of R efrigerant Charge Liquid tubing size in mm Amount of refrigerant charge oz ft Design of 3WAY VRF SYSTEM 01 4 06 35 0 279 93 8 99 52 0 602 91 2 912 7 1 88 95 8
68. AY VRF SYSTEM 7 Optional Parts How to use the fittings Suspension bolt 3 8 or M10 field supplied Nut field supplied 3 8 or M10 M4 screw M4 x 15 32 Suspension hook M4 screw M4 x 15 32 supplied Never use a long screw other than the accessory screw This may bore a hole through the tube surface causing refrigerant leakage Install the hanging hook with supplied 4 screws M4 X 15 32 taking care of the positioning Wrong positioning will become unfitted center of gravity position causing injuries or product damage 4 Wiring Tubing and Heat Insulation 1 Refrigerant tubing Cool with damp cloth or other means when brazing the joint with a torch Otherwise the solenoid valve will be damaged Liquid tube NOTE Suction tube e When brazing be sure to perform nitrogen replacement inside the tube so that oxidation coating does not form inside the tube Then stop performing when nitrogen replacement is completed The solenoid valve however will be damaged if nitrogen is applied during while brazing e Heat sensitive components protect from flame and heat conduction e Comply with all Local Code Requirements e Clean base metals throughly e Use proper ventilation to carry fumes away from the work area e Use a high quality silver based solder of at least 15 silver e Heat the base materials broadly and uniformly e Take precautions not to overheat the device which could damage sensi
69. FE EFG HI A EEEF E F FE cem FED CA B AC DEF 340 1 Insulation Unit mm Insulation Design of 3WAY VRF SYSTEM 7 Optional Parts e Size of connection point on each part Shown are inside diameters of tubing 3 Making Branch Connections e Using a tube cutter cut the joints at the diameter required to match the outside diameter of the tubing you are connecting This is usually done at the installation site The tube diameter depends on the total capacity of the indoor unit Note that you do not have to cut the joints if it already matches the tubing end size For size selection of the tube diameter refer to the installation instructions provided with the outdoor unit Avoid forceful cutting that may harm the shape of the joints or tubing Inserting the tubing will not be possible if the tube shape is not proper Cut off as far away from stopper as possible e After cutting the joints be sure to remove burrs on the inside of the joints If the joints have been squashed or dented badly reshaped them using a tube spreader Make sure there is no dirt or other foreign substances inside the distribution joint e The distribution joint can be either horizontal or vertical In the case of horizontal the L shaped tubing must be Stopper bo
70. Hd A ddns YIMOd Electrical Data 1 Outdoor Uni Schematic Diagram U 96MF1U9 U 96MF1U9E 390HS 919153713 NV A8 031113 38 AVN 3SIMH3HLIO OL 19915 ANY 330 NO 5031 3HL 11 WNHI NOD 8 9 d 9NIS9NVHO NAHM HOLIMS A dddnS 93 0 NIVW 430 NYAL TWNIWH3L a YOLSIWYSHL 219 214 87374 3H1 Y31714 3S 0N 2 LAN SSVdA8 Ad8 QuVOB WNINYSL 80193NNO2 ANIS 1V3H 93513 1102812 1 8380 LOZ OOZ 74 32NV v8 35 5 35 1 8d BOIS af 3I QIUBAH G31V83d0 lt JAVA 2510 2130 Qquvo8 1119812 JIH ESOP 1XOH2 21H YOLIVAY 8013Y1N03 YOLON 1228 1081800 1933914333 03908 1109912 331713 5071 2 114 YOLIOVd 9 211410812313 3 NS 9N NOILONS 1428 QuvO8 1110812 1081402 H9IH 2 LHd 9 1N3880283A0 30553840 1218 SAWA JAYS JAYS AV 138 20 1 1048 00 200AH H3lV3H SSVI Z LH uora31084 uoss3udmoo 267 YOLOW 3 9000100 OW4 YSNYOSSNVYL LNSYYND 24113 30010 390138 08 AH3A023H 110 3010 YOSS3YdNOD 2010 51081 5 1141832530 51081 5
71. RE Set to 1 1 2 OFF ON 7 System 21 20N IWA Set to 1 12242 OFF ON 0 System 30 1 amp 20N R 5 Setto 0 1 2 OFF Examples of the No of outdoor units settings S006 No of outdoor units Outdoor unit setting S006 3P DIP switch blue ON 1 unit factory setting 1 ON AY 0 T 2 3 OFF ON 2 units 20 WA 12 27 53 OFF ON ON 3 units 1 amp 820N 8 T 2 3 OFF Address setting of main outdoor unit S007 Unit No setting Address setting of outdoor unit S007 3P DIP switch blue Unit No 1 main unit ON TE OFF Address setting of sub outdoor unit Unit No setting Address setting of outdoor unit 5007 3P DIP switch blue ON ON Unit No 2 sub unit 20N 3 128 OFF ON ON Unit No 3 sub unit 1 amp 20N 3 123 OFF Test Run The sub unit control PCB contains the same switches as the main unit control PCB for No of indoor units No of outdoor units and system address However it is not necessary to set these switches Test Run
72. TECHNICAL DATA Panasonic 410 U 72MF1U9 U 72MF1U9E U 96MF1U9 U 96MF1U9E Model No Outdoor Unit Class 72 96 Model Name U 72MF1U9 U 96MF 1U9 U 72MF1U9E U 96MF1U9E Refrigerant R410A is used in the outdoor units Salt Air Damage Resistant Specifications 3WAY VRF System Indoor Units Class 7 9 12 15 18 19 24 36 48 54 U1 4 Way Cassette S 12MU1U6 S 18MU1U6 S 24MU1U6 S 36MU1U6 Y1 4 Way Cassette 60x60 S 12MY1U6 S 18MY1U6 D1 1 Way Cassette S 07MD1U6 S 09MD1U6 S 12MD1U6 F1 Low Silhouette Ducted S 07MF1U6 S 09MF1U6 S 12MF1U6 S 15MF1U6 S 18MF1U6 S 24MF1U6 S 36MF1U6 S 48MF1U6 8 54 M1 Slim Low Static Ducted S 07MM1U6 S 09MM1U6 S 12MM1U6 S 15MM1U6 S 18MM1U6 E1 a Pressure S 36ME1U6 S 48ME1U6 T1 Ceiling S 12MT1U6 S 18MT1UG S 24MT1U6 K1 Wall Mounted S 07MK1U6 S 09MK1UG S 12MK1UG S 18MK1U6 S 19MS1U6 S 24MK1U6 P1 Floor Standing S 07MP1U6 S 09MP1U6 S 12MP1U6 S 15MP1U6 S 18MP1U6 S 24MP1U6 concealed Floor S 07MR1U6 S 09MR1U6 S 12MR1U6 S 15MR1U6 S 18MR1U6 S 24MR1U6 Standing Necessary to install the External Electronic Expansion Valve Kit Optional CZ P56SVK1U 85464869258000 REFERENCE NO TD831158 00 IMPORTANT Please Read Before Starting This air conditioning system meets strict safety and operating standards As the installer or service person it is an imp
73. TU h BTU h 17F Ducted 72 000 81 000 47 000 U 72MF1U9 E Non Ducted 69 500 77 500 42 000 Mixed Non Ducted and Duced 70 500 79 000 44 500 Cooling Capacity Outdoor Unit Indoor Unit Models Types Ducted 95 000 106 500 69 000 U 96MF1U9 E Non Ducted 93 000 103 000 58 500 Mixed Non Ducted and Duced 94 000 104 500 63 500 Ducted 139 000 157 000 93 500 WU 144MF1U9 E Non Ducted 137 000 151 000 83 500 Mixed Non Ducted and Duced 138 000 154 000 88 500 Ducted 164 000 184 000 114 000 WU 168MF1U9 E Ducted 160 000 178 500 98 000 Mixed Non Ducted and Duced 162 000 181 000 106 000 Ducted 213 000 WU 192MF1U9 E Ducted 206 000 Mixed Non Ducted and Duced 209 500 Ducted 203 000 228 000 136 000 WU 216MF1U9 E Non Ducted 198 000 221 000 120 000 Mixed Non Ducted and Duced 200 500 224 500 128 000 Ducted 230 000 265 000 159 000 WU 240MF1U9 E Non Ducted 221 000 246 000 136 000 Mixed Non Ducted and Duced 225 500 255 500 147 500 Ducted 288 000 WU 264MF1U9 E Non Ducted 269 000 Mixed Non Ducted and Duced 278 500 Ducted 281 000 312 000 194 000 WU 288MF1U9 E Non Ducted 275 000 293 000 165 000 Mixed Non Ducted and Duced 278 000 302 500 179 500 3WAY VRF SYSTEM Unit Specifications 1 Outdoor Unit 1 3 Dimensional Data U 72MF1U9 U
74. a raised platform that is higher than drifting snow Provide snow vents When Connecting Refrigerant Tubing Ventilate the room well in the event that is refrigerant gas leaks during the installation Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas Keep all tubing runs as short as possible Use the flare method for connecting tubing Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run When performing piping work do not mix air except for specified refrigerant R410A in refrigeration cycle It causes capacity down and risk of explosion and injury due to high tension inside the N WARNING refrigerant cycle Refrigerant gas leakage may cause fire Do not add or replace refrigerant other than specified type It may cause product damage burst and injury etc Do not leak refrigerant while piping work for an installation or re installation and while repairing refrigeration parts Handle liquid refrigerant carefully as it may cause frostbite When Servicing Turn the power OFF at the main power box mains before opening the unit to check or repair electrical parts and wiring Keep your fingers and clothing away from any moving parts Cle
75. ack S003 2P DIP blue 5003 setting Outdoor system address S002 setting 1P 10s digit 2P 20s digit 1 refrigerant 1 0 OFF OFF system only 1 1 OFF OFF 2 2 OFF OFF 3 3 OFF OFF 4 4 OFF OFF 5 5 OFF OFF 5 6 OFF OFF 7 7 OFF OFF 8 8 OFF OFF 9 9 OFF OFF 10 0 ON OFF 11 1 ON OFF 2 ON OFF 18 3 ON OFF 14 4 ON OFF 15 5 ON OFF Link wiring 16 6 ON OFF M 7 ON OFF 18 8 ON OFF 19 9 ON OFF 20 0 OFF ON 21 1 OFF ON 22 2 OFF ON 23 3 OFF ON 24 4 OFF ON 25 5 OFF ON 26 6 OFF ON 27 7 OFF ON 28 8 OFF ON 29 9 OFF ON 30 0 ON ON Table 7 2 Setting the Number of Indoor Units Table 7 3 Setting the Number of Outdoor Units S004 Rotary switch red S005 2P DIP blue S006 DIP switch blue Number of 5005 Setting Number of S006 Setting Indoor Units 2004 Setting 2 3 Indoor Units 1 2 3 1 1 OFF OFF OFF 1 ON OFF OFF 2 2 OFF OFF OFF 2 OFF ON OFF 3 3 OFF OFF OFF 3 ON ON OFF 7 4 OFF OFF ON 9 9 OFF OFF OFF 19 5 Table 7 4 Setting the Outdoor Unit address 1 Unit S007 Setting 19 9 ON OFF OFF Address 2 3 20 0 OFF ON OFF ON OFF OFF 21 1 OFF ON OFF 2 ON OFF qeu a 3 ON ON OFF 29 9 OFF ON OFF OFF OFF ON 30 0 OFF OFF ON 31 1 OFF OFF ON m
76. acteristics inside surface is glossy and smooth edge is smooth tapered sides are of uniform length 2 40 Design of 3WAY VRF SYSTEM Deburring Before After MM ASSAY Copper tubing Flare nut Copper tubing Flare tool Fig 2 21 5 TO PROCESS TUBING Caution Before Connecting Tubes Tightly 1 Apply a sealing cap or water proof tape to prevent dust or water from entering the tubes before they are used 2 Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together This is effective for reducing gas leaks Fig 2 22 3 For proper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Fig 2 23 Adjust the shape of the liquid tube using a tube bender at the installation site and connect it to the liquid tubing side valve using a flare Cautions During Brazing Replace air inside the tube with nitrogen gas to prevent copper oxide film from forming during the brazing process Oxygen carbon dioxide and Freon are not acceptable Do not allow the tubing to get too hot during brazing The nitrogen gas inside the tubing may overheat causing refrigerant system valves to become damaged Therefore allow the tubing to cool when brazing Use a reducing valve for the nitrogen c
77. addresses at the indoor units that are connected to that outdoor unit and are within the same system The system address is 1 at the time of shipment Automatic address setting is necessary even for communications lines in a single system where the inter unit control wiring does not cross to any other systems While automatic address setting is in progress the 2 LEDs LED1 2 red on the outdoor unit control PCB blink alternately Short circuiting this pin while automatic address setting is in progress will stop the automatic address setting operation S002 Rotary switch 10 positions black Outdoor system address setting switch The setting is 1 at the time of shipment It is not necessary to change the setting if wiring is connected only to an outdoor unit and indoor units in a single system and the inter unit control wiring does not cross multiple systems f wiring links the inter unit control wiring for multiple systems to the same communications lines then a different address must be set for each refrigerant tubing system f wiring links multiple systems a maximum of 30 systems up to 64 indoor units can be connected This setting can be set up to 39 however control will be for 30 systems even if the setting is set to higher than 30 An alarm will be displayed if system addresses are duplicated For details refer to Table 7 1 S003 DIP switch 2P blue Switches for setting system address 10
78. all indoor units in that system Ruc 1 then Actual cooling capacity of each indoor unit 7 Corrected cooling capacity of each indoor unit 5 In other words the cor rection coefficient 6 based on the corrected indoor outdoor capacity ratios for each indoor unit is 1 If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units in that sys tem Ruc 1 then Actual cooling capacity of each indoor unit 7 Corrected cooling capacity of each indoor unit 5 x 0 25 x Ruc 0 75 Ruc In other words the correction coefficient 6 based on the corrected indoor outdoor capacity ratios for each indoor unit is the underlined part in the formula above Heating capacity Corrected indoor outdoor capacity ratio during heating Ruh Total corrected heating capacity of all indoor units in that system Corrected outdoor unit heating capacity If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of all indoor units in that system Ruh 1 then Actual heating capacity of each indoor unit 7 2 Corrected heating capacity of each indoor unit 5 In other words the correction coefficient 6 based on the corrected indoor outdoor capacity ratios for each indoor unit is 1 If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor u
79. an up the site after you finish remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced Do not clean inside the indoor and N WARNING outdoor units by users Engage authorized dealer or specialist for cleaning In case of malfunction of this appliance do not repair by yourself Contact to the sales dealer or service dealer for a repair Do not touch the air inlet or the sharp aluminum fins of the outdoor unit You may get injured Ventilate any enclosed areas when installing or testing the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas Confirm after installation that no refrigerant gas is leaking If the gas comes in contact with a burning stove gas water heater electric room heater or other heat source it can cause the generation of poisonous gas Do not touch the air inlet or the N sim sharp aluminum fins of the outdoor unit You may get injured Do not sit or step on the unit you may fall down accidentally Do not stick any object into the Check of Density Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out its density will not exceed a set limit The refrigerant R410A which is used in the air conditioner is safe without the toxicity or combustibility of ammonia and is not restr
80. apaqqaphassquthaqaqqa punqa 2 43 6 PURGING L uuu e 2 44 Air Purging with a Vacuum Pump for Test Run Preparation 2 44 7 Optional Partg LLULLU d ada A RATED OR EO IR dd 2 47 7 1 Distribution Joint TANG aussen n e boc e ca laa do lace gon en bae x dc ea i RUE 2 47 7 2 Solenoid Valve Kit Tor SWAY VRF System rd e On ERU Doo E ania 2 51 2 1 Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 1 Operating Range Heating and Cooling Operating range Outdoor air intake temp F WB 5 5 6 7 8 9 Indoor air intake temp F DB Cooling Heating 113 a 104 idi 59 3 50 a 86 LL 77 68 Operating 45 59 2 8 8 5 5 14 5 9 5 5 O 4 32 5 50 59 68 77 86 95 55 Indoor air intake temp F 14 57 50 59 68 77 86 Indoor air intake temp F WB Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 2 Procedure for Selecting Models and Calculating Capacity Selection Procedure Select the model and calculate the capacity for each refrigerant system according to the procedure shown below Calculation of the indoor air co
81. ay Cassette Type U1 Type 3 4 Way Cassette 60x60 Type Y1 Type 4 1 Way Cassette Type D1 Type 5 Low Silhouette Ducted Type F1 Type 6 Slim Low Static Ducted Type M1 Type 7 High Static Pressure Ducted Type E1 Type 8 Ceiling Type T1 Type 9 Wall Mounted Type K1 Type 10 Floor Standing Type P1 Type 11 Concealed Floor Standing Type R1 Type 12 Intaking Fresh Air of 4 Way Casstte Type and Slim Low Static Ducted Type Refer to the 2WAY VRF SYSTEM TECHNICAL DATA TD831157 Section 5 TEST RUN u uu 5 1 1 Preparing r di prm 5 2 086 n 5 3 3 Main Outdoor Unit PCB 5 4 4 Auto Address Setting 5 6 5 Remote Controller Test Run Settings 5 12 6 Calton for PUMP 5 12 7 Meaning of Alarm Messages aa 5 13 Section 6 ELECTRICAL DATA U anna nona no Rana u T 6 1 Outdoor Unit m ua naa na 6 2 2 Indoor Unit Refer to the 2WAY SYSTEM TECHNICAL DATA TD831157 Section 7 PCB AND FUNCTIONS assssasasssasswasawawssanawsqansasasa 7 1 Outdoor Unit GConltel POB
82. be used for R410A Flaring oil Yes No For systems that use R22 apply mineral oil Suniso oil to the flare nuts on the tubing to prevent refrigerant leakage For machines that use R407C or R410A apply synthetic oil ether oil to the flare nuts Using tools for R22 and R407C and new tools for R410A together can cause defects 3 2 Use R410A exclusive cylinder only Valve Single outlet valve with siphon tube Liquid refrigerant should be recharged with the cylinder standing on end as shown New refrigerant R410A cannot be used for earlier models 1 Compressor specifications are different If recharging a R22 or R407C compressor with R410A durability will significantly decrease since some of the materials used for compressor parts are different 2 Existing tubing cannot be used especially R22 Completely cleaning out residual refrigerating machine oil is impossible even by flushing 3 Refrigerating machine oil differs R22 Since R22 refrigerating machine oil is mineral oil it does not dissolve in R410A Therefore refrigerating machine oil discharged from the compressor can cause compressor damage R22 refrigerating machine oil Mineral oil Suniso oil R407C refrigerating machine oil Synthetic fluid ether oil R410A refrigerating machine oil Synthetic fluid ether oil Contents Section 1 OUTLINE OF 3WAY SYSTEM
83. bing length elevation difference 0 9009 0 9461 0 9311 0 9159 0 9009 was 1 0491 1 0245 1 0000 Bietbutoniatio CE 1 0335 1 0167 1 0000 o 4 Frosting defrosting 0 8900 1 0171 0 9939 0 9706 0 9474 Result of 2 x 3 1 0565 1 0397 1 0228 1 0060 Correction coefficient applied to indoor unit 1 190007 0 9706 094741 1 0000 1 0000 1 0000 1 0000 168 609 06 54 600 00 35 781 01 34 941 99 23 684 09 S Corrected capacity BTU h 2 173 189 02 61 768 40 39 234 00 39 234 00 27 162 00 NEN 1 0000 1 0000 1 0000 1 0000 6 Correction coefficient for corrected capacity ratio 1 0000 1 0000 1 0000 1 0000 54 600 00 35 781 01 34 941 99 23 684 99 7 Actual capacity BTU h 61 400 00 39 000 00 39 000 00 27 000 00 1 This varies depending on the values of 2 and 2 x Distribution ratio in 3 2 Corrected outdoor unit capacity Rated outdoor unit capacity x 1 x 2 x 3 x 4 The actual capacity is calculated as shown below Cooling Ruc 54 600 00 35 781 01 34 941 99 23 684 99 168 609 06 0884 lt 1 Therefore Actual cooling capacity of each indoor unit 2 Corrected cooling capacity of each indoor unit In other words the correction coefficient 6 for the corrected capacity ratio is 1 Heating Ruh 61 768 40 39 234 00 39 234 00 27 162 00 173 189 02 0 967 lt 1 Therefore Actual heating capacity of each indoor
84. cient during frosting defrosting 1 4 Outdoor intake air temp FWB RH85 coeticien 097 097 087 oso 094 091 089 087 087 87 089 os 038 oss 10 To calculate the heating capacity with consideration for frosting defrosting operation multiply the heating capacity found from the capacity graph by the correction coefficient from the table above Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Graph of indoor unit capacity characteristics 2 2 Indoor unit cooling capacity characteristics Indoor unit heating capacity characteristics indicates the rating point indicates the rating point 120 110 100 90 57 59 60 62 64 66 68 69 71 73 75 77 Indoor air intake temp F WB 90 L 1 L 1 1 1 1 1 1 1 1 1 59 60 62 64 66 68 69 71 73 75 77 78 80 Indoor air intake temp F DB Rate of cooling capacity change 96 Rate of heating capacity change Graph of capacity change characteristics resulting from tubing length and elevation difference 1 2 3 Cooling Heating Base capacity Base capacity 1 92 90 88 86 84 82 80 78 76 T change rate M p 131 L 94 131 l 9
85. cuit H13 Compressor No 2 discharge temp sensor disconnected H15 Low pressure switch is activated H06 Oil sensor fault Comp No 1 oil sensor Disconnection etc Comp No 2 oil sensor H27 Continued 7 Meaning of Alarm Messages Test Run Alarm messages displayed on system controller Serial Error in transmitting serial Indoor or main outdoor unit is not operating correctly communication communication signal Mis wiring of control wiring between indoor unit main outdoor unit C05 errors and system controller Mis setting Error in receiving serial Indoor or main outdoor unit is not operating correctly communication signal Mis wiring of control wiring between indoor unit main outdoor unit and system controller CN1 is not connected properly Activation of Protective device of sub indoor When using wireless remote controller or system controller in protective unit in group control is activated order to check the alarm message in detail connect wired P30 device remote controller to indoor unit temporarily 1 Alarm messages in lt lt gt gt do not affect other indoor unit operations 2 Alarm messages in lt gt sometimes affect other indoor unit operations depending on the fault 5 15 Electrical Data Contents 6 ELECTRICAL DATA Umit saison a 6 2 1 Electric Wining Diagram U 72MF1U9 U 72MF1U9E 6 2 2 Electric Wi
86. d More than 7 7 8 Indoor unit is directed downward 3 Electrical Wiring 3 1 General Precautions on Wiring 1 2 Before wiring confirm the rated voltage of the unit as shown on its nameplate then carry out the wiring closely following the wiring diagram Provide a power outlet to be used exclusively for each unit and a power supply disconnect circuit breaker and earth leakage breaker for overcurrent protection should be provided in the exclusive line To prevent possible hazards from insulation failure the unit must be grounded Each wiring connection must be done in accordance with the wiring system diagram Wrong wiring may cause the unit to misoperate or become damaged Do not allow wiring to touch the refrigerant tubing com pressor or any moving parts of the fan Unauthorized changes in the internal wiring can be very dangerous The manufacturer will accept no responsi 7 9 Design of 32WAY VRF SYSTEM bility for any damage or misoperation that occurs as a result of such unauthorized changes Regulations on wire diameters differ from locality to lo cality For field wiring rules please refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all rel evant rules and regulations To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as fol lows The remote control wiring and the inter uni
87. d RYO23 RY022 RY026 RY021 RY020 RY017 RY016 gt 2 w ei 148 148 7 7 4 4 2 lt 3 t l 9 006 005 PS 8 x t 1_ 5 CN228 3 3 A j 6 3 1 3 LAE 18 S 5 CR CHOZ09663 El 5 1FA4B1B125400 0 i i 1 5007 006 005 5004 003 5002 Test Run 4 Auto Address Setting 4 Auto Address Setting Basic wiring diagram Example 1 If link wiring is not used The inter unit control wires are not connected to multiple refrigerant systems Indoor unit addresses can be set without operating the compressors No 1 main outdoor unit settings of indoor units 10 units setting System address 5004 System 1 setting 0 5002 5003 S005 ON 2 sub unit 3 sub unit HT 2 3 OFF Unit Soo7 Unit Soo7 S006 S007 outdoor ON ow Unit number number number oN units 3 units 8 8 setting P setting R 9 setting n m setting oFF Unit No 1 obe No 2 42 31 OFF Unit No 3 2 3 OFF Leave the socket that is used to short circuit 7 ni the terminal plug nit nit Outdoor Unit No 1 CN003 No 2 No 3 Main Inter outdoor unit Sub Inter out
88. d operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 6 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications 6 PERFORMANCE ii eS Cooling capacity BTU h kW 216 000 63 3 BTU h kW 243 000 71 1 in 82 9 16 1887 UNIT DIMENSIONS in 113 2870 n mm e 77239 573 260 573 260 573 260 Silky shade 1Y 8 5 0 5 ELECTRICAL RATINGS V A Power factor i A i W 17 4 17 4 k x 6 COMPRESSOR Refrigeration oil Eves Ether ol 9 1 40 5 3 liters 1 40 5 3 liters 1 40 5 3 liters 25 25 Capacity control 3 33 45 4 15 9 97 3 49 5 46 4 42 5 15 9 93 8 c W kg Refrigerant amount at shipment Ibs k R410A 25 9 11 8 R410A 25 9 11 8 R410A 25 9 11 8 Aluminum plate fin Copper tube Propeller fan x 1 Propeller fan x 1 External static pressure in WG 0 0 0 kW 0 7 8P 0 7 8P Protective devices High pressure switch overcurrent CT method i Liquid tube in F Primary accessories Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Electronic expansion valve Reverse cycle de
89. der joint system do not make fur ther branches in the tubing Do not use the header joint system on the outdoor unit side If there are height differences between indoor units or if branch tubing that follows a distribution joint is connected to only 1 unit a trap or ball valve must be added to that distribution joint When adding the ball valve locate it within 15 3 4 of the distribution joint If a trap or ball valve is not added do not operate the system before repairs to a malfunctioning unit are completed The refrigerant oil sent through the tubing to the malfunctioning unit will accumulate and may damage the compressor 2 Design of 32WAY VRF SYSTEM Tube branching methods horizontal use Arrow view D Arrow view ES View as seen view C from arrow Header joint system Indoor Install at a positive angle Install at a positive angle 15 30 Solidly welded shut X Horizontal ine Types of vertical trap specifications When using ball valve Main tubing BV purchased separately J Indoor unit 1 Indoor unit more than 2 units If only 1 unit is connected a ball valve is also needed on this side Ball valve When not using ball valve Main tubing re orizonta Indoor unit Each unit is connected to tubing that is either level or is directed downward Branch tubing is directed upwar
90. ditions inside the ceiling exceed DB 86 F and RH 7096 increase the thickness of the gas tubing insulation material by 1 step Insulation Balance tubing If the exterior of the outdoor unit valves has been finished Four tubes arranged together with a square duct covering tape Suction tubing make sure you allow Discharge tubing sufficient space to use the valves and to allow the panels to be attached and Balance tubing removed Taping the flare nuts Insulation Liquid tubing Wind the white insulation tape around the flare nuts at Fig 2 25 the gas tube connections Then cover up the tubing Sealer Insulation tape white connections with the flare insulator and fill the gap at the 2 ied union with the supplied black insulation tape Finally e Fiano insulator Supplied fasten the insulator at both ends with the supplied vinyl insulator Unit not supplied clamps Fig 2 26 insulator Heat resistant 248 F or above nut Vinyl clamps supplied Fig 2 26 2 42 Design of 3WAY VRF SYSTEM 5 HOW TO PROCESS TUBING 5 4 Taping the Tubes 1 At this time the refrigerant tubes and electrical wiring if local codes permit should be taped together with armoring tape in 1 bundle To prevent the condensation from overflowing the drain pan keep the drain hose separate from the refrigerant tubing 2 Wrap the armoring tape from the bottom of the outdoor unit to the
91. door capacity ratio based on the corrected outdoor unit capacity and the total corrected capacity of all indoor units in the same system Use the result to calculate the capacity correction coefficient for the indoor units 2 11 2 15 e Multiply the corrected capacity of each indoor unit by the capacity correction coefficient to calcu late the actual capacity for each indoor unit 2 12 Recheck of the actual capacity for each indoor unit f the capacity is inadequate reexamine the unit combinations Example 1 Increasing the outdoor unit capacity Example 2 Increasing the indoor unit capacity Increasing the tubing size Design Create tubing design which minimizes the amount of additional refrigerant charge as much as possible ooa S 2 4 2 6 e If tubing extension for additional unit is expected in the future create the tubing design with adequate consideration for this extension e Select the tubing size for the main tube LA up to the No 1 distribution joint based on the rated cooling capacity of the outdoor unit Select tubing sizes after the distribution point based on the total rated cooling capacity of the connected indoor units e Increasing the tubing size of the wide tubes can reduce the loss of capacity caused by longer tubing lengths Only the main wide tube with the largest tube diameter main tube LA and main tubes after the distribution poi
92. door unit Sub control wiring control wiring U Inter unit control wiring Indoor Unit 1 1 1 2 1 3 1 10 Remote control Remote controller communication wiring Fig 5 5 1 Automatic Address Setting from the Outdoor Unit Case 1 1 set the number of outdoor units on the outdoor main unit control PCB set the No of outdoor units DIP switch S006 to ON ON ON E 3 3 units and set the unit No DIP switch 5007 to E E unit No 1 main outdoor unit 1 2 3 1 2 3 2 Onthe No 2 sub unit control PCB set the unit No switch 5007 to 1 g unit No 2 2 3 N On the No 3 sub unit control PCB set the unit No switch S007 to Bn g unit No 3 1 2 3 3 the outdoor main unit control PCB check that the system address rotary switch 5002 is set to 1 and that the DIP ON ON Switch S003 is set to 0 These the settings at the time of factory shipment 1 2 OFF 4 Tosetthe number of indoor units that are connected to the outdoor unit to 10 on the outdoor main unit control PCB set the ON ON No of indoor units DIP switch S005 to T 2 1 and set the rotary switch S004 to 0 1 2 3 OFF 5 Turn ON th
93. e power to the indoor and outdoor units 6 Onthe outdoor main unit control PCB short circuit the automatic address pin CN100 for 1 second or longer then release it Communication for automatic address setting begins To cancel again short circuit the automatic address pin CN100 for 1 second or longer then release it The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped Be sure to perform automatic address setting again Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF 7 Operation from the remote controllers is now possible To perform automatic address setting from the remote controller perform steps 1 to 5 then use the remote controller and complete automatic address setting Refer to Automatic Address Setting from the Remote Controller 5 6 Test Run 4 Auto Address Setting Basic wiring diagram Example 2 When multiple outdoor main units exist remove the socket that is If link wiring is used used to short circuit the terminal plug 003 from all outdoor No 1 main outdoor unit settings sening main unit PCBs except for one unit System address No of indoor units Alternatively
94. en p Le 208 230V 60Hz 3 PH Controller B gt OO ens BLK gt NZ Aq Indoor unit No 2 D ca control wiring Power supply L1 pm ag 1 uni 208 230V 60Hz 1 12 5 CET 19 o ower supply L2 Remote Ground ets L2 208 230V 60Hz Controller B 5 WHT OkO Ground BLK Group control Indoor Power supply L1 208 230V 60Hz 1 PH L2 Power supply L1 208 230V 60Hz 1 PH 12 Remote em BLK Controller WHT 2 BLK BLK 1 WHT J WHT H 1 CONNECTOR 2P WHT 1 Refer to Section 2 3 2 Recommended Wire RC BLU Length and Wire Diameter for Power Supply System for the explanation of A B and in the above diagram 2 The basic connection diagram of the indoor unit shows the 7P terminal board so the terminal boards in your equipment may differ from the diagram 8 Refrigerant Circuit R C address should be set before turning the power on 4 Regarding the R C address setting refer to Section 5 TEST RUN Address setting can be executed by remote controller automatically NOTE Disconnect switch Field Supply Disconnect Switch may be needed by the National Local code AN Outd
95. essure in WG Motor output of kW 0 7 8P Protective devices TUBING ee a a 27 _____ Suction tube in mm 01 1 8 028 58 Brazing Discharge tube in mm 07 8 922 22 Brazing Liquid tube in mm Balance tube 03 8 09 52 Flare nut 58 0 Quiet mode 55 0 Connection tubing Connection tubing 01 1 8 028 58 23 4 019 05 07 8 022 22 03 4 019 05 07 8 922 22 03 4 019 05 93 4 019 05 05 8 015 88 V A kW kW Starting o 2 3 3 Refrigerant tubing In 3 Drain port External air temperature operation range Operation sound Hi UJ F Primary accessories Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 5 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications 5 PERFORMANCE 2 r s Cooling capacity BTU h kW Heating capacity BTU h kW in in Ceiling dimension 35 2 3 8 Net weight 672 305 Color Munsell code ELECTRICAL RATINGS
96. fficient 0 6 If the size of the discharge tubes and suction tubes LM have been increased apply the correction coefficient from Table 2 9 and calculate the equivalent length of the LM section Equivalent length of tubing after size increase Standard tubing equivalent length x Equivalent length correction coefficient 1 Model Selecting and Capacity Calculator 1 9 Capacity Correction Graph According to Temperature Condition Capacity characteristics The corrected capacity for specific temperature conditions can be found from the graphs below lt Cooling gt lt Heating gt 6 Ton 130 97 Indoor air intake temp WB 72 120 130 Indoor air intake temp F w 110 WB 67 F 120 61 L 110 90 100 70 Q 80 WB 61 p c gt 80 79 120 g 70 110 60 2 50 100 e 40 90 80 uw 2 NI 180 70 420 2 60 a 10 50 100 61 2 40fwB 61 F S 90 30 80 70 20 70 10 60 79 50 14 23 32 41 50 59 68 77 86 95 104 113 4 5 14 23 32 41 50 59 Heating capacity correction coefficients for frost defrost operation Outdoor intake air temp 4 5 14 17 21 23 24 28 30 3 F WB RH85 2 37 Conecioncoetcent 097 287 056 094 091 020 087 087 087 088 089
97. frost outdoor unit cycle defrost g1 1 4 931 75 Brazing 91 1 8 028 58 Brazing 05 8 215 88 Brazing 03 8 09 52 Flare nut 3 3 3 Refrigerant tubing 5 5 pa 026 8 3 3 5 3 3 Cooling 14 113 F DB Heating 4 59 WB 58 0 Quiet mode 55 0 Connection tubing Connection tubing Connection tubing 97 8 022 22 03 4 019 05 07 8 022 22 03 4 019 05 07 8 022 22 03 4 019 05 UJ Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 7 3WAY VRF SYSTEM Uni J j 1 Outdoor Unit WAY VRF SYS Unit Specifications Unit Specifications 7 240 000 70 3 270 000 79 1 82 9 16 2097 UNIT DIMENSIONS 113 2870 OO 573 260 573 260 Color Munsell code Silky shade 1Y 8 5 0 5 Running amperes Cooling Power input Power factor Running amperes Power factor A COMPRESSOR Type Q ty kW FV68S Ether oil Charge amount 1 96 7 4 liters 1 40 5 3 liters 25 32 25 ene 158 kg R410A 25 9 11 8 R410A 25 9 11 8 Electronic expansion valve Reverse cycle defrost outdoor unit cycle defrost Al
98. ft set based on the main tube sizes LA listed in the table above Size of tubing LO between outdoor units Select the size of tubing between outdoor units based on the main tubing size LA as given in the table above Table 2 3 Main Tubing Size After Distribution LB LC Unit in mm Total capacity Below BTU h 54 600 85 300 102 400 124 200 143 300 162 400 200 600 238 900 after distribution Over BTU h 24 200 54 600 85 300 102 400 124 200 143 300 162 400 200 600 05 8 03 4 03 4 07 8 o1 1 8 01 1 8 o1 1 8 01 1 8 o1 1 8 015 88 019 05 019 05 022 22 028 58 028 58 028 58 028 58 028 58 21 2 05 8 05 8 03 4 03 4 97 8 97 8 07 8 91 18 012 70 015 88 015 88 019 05 019 05 022 22 02222 022 22 028 58 liquid tubing 03 8 03 8 93 8 03 8 91 2 91 2 91 2 95 8 95 8 09 52 09 52 09 52 09 52 012 70 012 70 012 70 015 88 015 88 Suction tubing Tubing size Discharge tubing Total capacity Below BTU h 258 000 334 400 ictributi 1 The outdoor unit connection tubing LO is after distribution Over BTU h 238 900 258 000 334 400 determined by the total capacity of the outdoor 21 3 8 01 3 8 9112 units connected to the tube ends The tubing 9 034 92 034 92 041 2
99. g dimension 35 2 3 8 890 60 672 305 672 305 573 260 Silky shade 1Y 8 5 0 5 5 3 3 UNIT DIMENSIONS Net weight Color Munsell code ELECTRICAL RATINGS Voltage rating I 57 3 20 8 91 1 61 5 20 8 93 9 Running amperes Power input Power factor Running amperes 67 3 62 8 Power input 23 0 23 0 Power factor A Inverter driven Rotary type x 1 Inverter driven Rotary type x 1 Fixed Speed Scrolltype x 1 Fixed Speed Scroll type 1 Inverter driven Rotary x kW 2 7 3 75 2 7 3 75 FV68S Ether oil 1 96 7 4 liters 1 96 7 4 liters 1 40 5 3 liters Cooling Heating Starting amperes COMPRESSOR Type Q ty Motor output Refrigeration oil Charge amount Crankcase heater 25 32 25 32 25 Capacity contro Ibs kg R410A 25 9 11 8 R410A 25 9 11 8 R410A 25 9 11 8 Refrigerant amount at shipment Refrigerant control Defrost method Heat exchanger FAN DEVICE Type Q ty Propeller fan x 1 Air circulation CFM 5 300 External static pressure in WG 0 0 Motor output No of poles kW 0 7 8P Protective devices TUBING Suction tube in mm Discharge tube in mm Liquid tube in mm Balance tube n mm 03 8 09 52 Flare nut Drain port External temperature operation range F Operation sound Hi Connection tubing Connection tubing 01 18 028 58 03 4 019 05 0
100. gf cm 1 32 0 8 mm 01 2 012 7 mm 430 480 Ibs inch 490 550 kgf cm 1 32 0 8 mm 05 8 015 88 mm 590 710 Ibs inch 680 820 kgf cm 5 128 1 0 mm 03 4 019 05 mm 870 1040 Ibs inch 1000 1200 over 5 128 1 0 mm Because the pressure is approximately 1 6 times higher than conventional refrigerant pressure the use of ordinary flare nuts type 1 or thin walled tubes may result in tube rupture injury or asphyxiation caused by refrigerant leakage In order to prevent damage to the flare caused by over tightening of the flare nuts use the table above as a guide when tightening When tightening the flare nut on the liquid tube use an adjustable wrench with a nominal handle length of 7 7 8 in Design of 3WAY VRF SYSTEM 5 HOW TO PROCESS TUBING 5 3 Insulating the Refrigerant Tubing Two tubes arranged together Tubing Insulation Liquid tubing Gas tubing Thermal insulation must be applied to all unit tubing 1 including the distribution joint purchased separately Lc Fig 2 25 For gas tubing the insulation material must be heat resistant to 248 F or above For other tubing it must Three tubes arranged together o Cosmetic be heat resistant to 176 F or above finishing tape Gas tubing Insulation material thickness must be 25 64 in or Liquid tubing greater If the con
101. heet No treatment Polyester powder coating 2120 Tapping screws SUS410 Hexavalent chromium free coating Hexavalent chromium free coating urethane coating Stud supplementary bracket Hot dip zinc coated steel sheet No treatment Polyester powder double coating 2120 treatment Dessicant coating 2 30 Accumulator Receiver tank Steel Epoxy coating alkyd coating Zinc rich double coating urethane coating Z 704m Welded portion Copper tube No treatment Urethane coating Outer surface Refrigeration cycle tube Copper tube No treatment Urethane coating Fixing bracket Hot dip zinc coated steel sheet No treatment Polyester powder double coating both sides Z 804m Notes 1 Consult us before introducing a salt air damage resistant model as it requires a special treatment 2 The specifications are subject to change without notice for development 3 Contact us for the delivery schedule Design of 3WAY VRF SYSTEM Contents 2 DESIGN OF 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator J J 2 2 pu eat PEN EE 2 2 1 2 Procedure for Selecting Models and Calculating Capacity 2 3 UC 2 4 1 4 Tubing Size
102. ic address setting has been successfully completed both LEDs 1 and 2 turn OFF LED 1 is D72 LED 2 is 075 If automatic address setting is not completed successfully refer to the table below and correct the problem Then perform automatic address setting again Display details of LEDs 1 and 2 on the outdoor unit control PCB 3 ON Blinking OFF LED 1 LED 2 Display meaning X Xt After the power is turned ON and automatic address setting is not in progress no communication with the indoor units in that system is possible AX After the power is turned ON and automatic address setting is not in progress 1 or more indoor units are confirmed in that system however the number of indoor units does not match the number that was set _ Automatic address setting is in progress Alternating e Automatic address setting completed At time of automatic address setting the number of indoor units did not match the number that was set Simultaneous AN when indoor units are operating indication appears on the display 5 Refer to Table of Self Di tic Functi dD ipti Displays Alternating efer to Table of Self Diagnostic Functions and Description of Alarm Displays Note A indicates that the solenoid is fused or that there is a CT detection current failure current is detected when the compressor is OFF Remote controller display
103. icted by laws imposed to protect the ozone layer However since it contains more than air it poses the risk of suffocation if its density should rise excessively Suffocation from leakage of refrigerant is almost non existent With the recent increase in the number of high density buildings however the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space individual control energy conservation by curtailing heat and carrying power etc Most importantly the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners If a single unit of the multi air conditioner system is to be installed in a small room select a suitable model and installation procedure so that if the refrigerant accidentally leaks out its density does not reach the limit and in the event of an emergency measures can be made before injury can occur FAN CASE You may be injured and the unit may be damaged ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safeguards related to the use of refrigerants all of which define a Refrigerant Concentration Level RCL of 25 pounds per 1 000 cubic feet for R410A refrigerant For additional guidance and precautions related to refrigerant safety please refer to the following documents International Mechanical Code 2009 IMC 2009 or mo
104. in Tubing Size LA Unit in mm BTU h 72 000 96 000 139 000 168 000 192 000 203 000 240 000 264 000 288 000 kW 21 1 28 1 40 7 49 2 56 3 59 5 70 3 77 4 84 4 Total system tonnage 6 8 12 14 16 18 20 22 24 Combined outdoor U 72MF1U9 E U 96MF1U9 E U 72MF1U9 E U 96MF1U9 E U 96MF1U9 E U 72MF1U9 E U 96MF1U9 E U 96MF1U9 E U 96MF1U9 E U 72MF1U9 E U 72MF1U9 E U 96MF1U9 E U 72MF1U9 E U 72MF1U9 E U 96MF1U9 E U 96MF1U9 E models U 72MF1U9 E U 72MF1U9 E U 72MF1U9 E U 96MF1U9 E Suction tubing 5 y PER Discharge tubing s eines 92858 Liquid tubing ae 2 1 1588 18 05 1 If future extension is planned select the tubing diameter based on the total tonnage after extension However extension is not possible if the resulting tubing size is two ranks higher 2 The balance tube outdoor unit tube diameter is 03 8 09 52 8 Type 1 tubing should be used for the refrigerant tubes 4 If the length of the longest tube L1 exceeds 295 ft equivalent length increase the main tube LM size by 1 rank forthe suction discharge and liquid tubes Use field supply reducers Select from Table 2 2 and Table 2 7 5 If the longest main tube length LM exceeds 164 ft increase the main tube size at the portion before 164 ft by 1 rank r the suction tubes and discharge tubes For the portion that exceeds 164
105. ing valve on the nitrogen tank Do not use agents intended to prevent the formation of oxide film They will adversely affect the refrigeration oil and may cause equipment failure The balance tube is not used if only 1 outdoor unit is installed Use the unit in the same conditions as when it was shipped from the factory 5 TO PROCESS TUBING 5 HOW TO PROCESS TUBING The liquid tubing side is connected by a flare nut and the gas tubing side is connected by brazing 5 1 Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units In this method the copper tubes are flared at each end and connected with flare nuts Flaring Procedure with a Flare Tool 1 Cut the copper tube to the required length with a tube cutter It is recommended to cut approx 1 2 ft longer than the tubing length you estimate 2 Remove burrs at the end of the copper tube with a tube reamer or file This process is important and should be done carefully to make a good flare Fig 2 19 When reaming hold the tube end downward and be sure that no copper scraps fall into the tube Fig 2 20 3 Remove the flare nut from the unit and be sure to mount it on the copper tube 4 Make a flare at the end of copper tube with a flare tool Fig 2 21 A good flare should have the following char
106. ints of the tubing both indoor and outdoor and all service valves Bubbles indicate a leak Wipe off the soap with a clean cloth after a leak test 4 After the system is found to be free of leaks relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder When the system pressure is reduced to normal disconnect the hose from the cylinder Evacuation 1 Attach the charge hose end described in the preceding steps to the vacuum pump to evacuate the tubing and indoor unit Confirm that the Lo knob of the manifold valve is open Then run the vacuum pump The operation time for evacuation varies with the tubing length and capacity of the pump The following table shows the amount of time for evacuation Pressure Required time for evacuation when 30 gal h vacuum pump is used If tubing length is If tubing length is less than 49 ft longer than 49 ft 45 min or more 90 min or more Evacuation is not necessary for the balance tube if only 1 outdoor unit is installed The required time in the above table is calculated based on the assumption that the ideal or target vacuum condition is less than 14 7 psig 755 mmHg 5 Torr 2 45 Design of 3WAY VRF SYSTEM Manifold valve Vacuum pump Suction tube Outdoor unit Discharge tube Balance tube 6 AIR PURGING 2 When the desired vacuum is reached close the Lo knob of the manifold
107. iquid tube Balance tube Suction tube Outdoor unit Discharge tube Liquid tube Balance tube Design of 3WAY VRF SYSTEM 7 Optional Parts 7 1 Distribution Joint Kits CZ P900PH1U for R410A How to Attach Distribution Joint 1 Accompanying Parts Check the contents of your distribution joint kit 2 Distribution Joint Kits with insulation CZ P900PH1U USE For outdoor unit Capacity after distribution joint is 90 0kW or less Suction Tube Discharge Tube Liquid Tube mG F Distribution Reducing Joint Joints Insulation Insulation Insulation Insulators for both the Suction tube and the Discharge tube are the same Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter So the both Distribution joints can fit into different tubes Since the diameter of the tube ends for both Suction and Discharge tube are different take care not to connect the distribution joint different See the marks on the above figures Size of connection point on each part Shown are inside diameters of tubing
108. is installed Checking of limit density When installing an air conditioner in a room it is necessary to ensure that even if the refrigerant gas accidentally leaks out its density does not exceed the limit level for that room 2 22 2 System Design 2 3 Installing Distribution Joint Pay special attention to any location such as a basement etc where leaking refrigerant can accumulate since refrigerant gas is heavier than air 1 Refer to HOW TO ATTACH DISTRIBUTION JOINT enclosed with the optional distribution joint kit CZ P900PH1U P224BH1U P680BH1U P1350BH1U When creating a branch using a commercially available T joint header joint system orient the main tubing so that it is either horizontal level or vertical In order to prevent accumulation of refrigerant oil in stopped units if the main tubing is horizontal then each branch tubing length B should be at an angle that is greater than horizontal If the main tubing is vertical provide a raised starting portion for each branch When only one indoor unit is connected to the side of A install part A at a positive angle 15 30 for the field tubing as shown in the figure Header joint system Be sure to solidly weld shut T joint end marked by X in the figure In addition pay attention to the insertion depth of each connected tube so that the flow of refrig erant within the T joint is not impeded When using the hea
109. ited pins to remain short circuited Y Set the wired remote controller for test run Refer to the remote controller test run settings Check and make corrections according to Table of Self Diagnostic Functions Does system operate YES Return remote control to normal mode Fig 5 3 3 Main Outdoor Unit PCB Setting 3 Main Outdoor Unit PCB Setting Examples of the No of indoor units settings S005 S004 1 unit factory setting Al OFF agg 8 OFF Indoor unit setting 5005 Indoor unit setting S004 No of indoorunits 3P DIP switch blue Rotary 10 20 30 ON Set 1 ON ON 7 11 units toON 8 Set to 1 12 3 OFF ON ON 7 21 units 20 8 Set to 1 1 2 9 OFF ON _ ON 7 31 units A 2 Setto 1 12 38 OFF ON 0 40 units 1830N Fg Set to 0 1 3 OFF Examples of refrigerant circuit R C address settings required when link wiring is used S003 S002 System address S003 System address 002 System address No 2P DIP switch blue Rotary switch Black 1020 System 1 factory setting Both OFF k 5 Set to 1 BEI 2 System 11 10N u
110. ly Table 2 10 Correction coefficient for equivalent length when the size of the gas tube LM is increased Standard tube diameter 91 2 95 8 93 4 97 8 01 1 8 gas tube in mm 012 7 015 88 019 05 022 22 028 58 Tube diameter after change 95 8 93 4 97 8 01 1 8 01 3 8 gas tube in mm 015 88 019 05 022 22 028 58 934 92 Equivalent length correction coefficient 0 4 0 5 0 6 When increasing the size of the suction and discharge tubing LM multiply by the correction coefficient from Table 2 11 and calculate the equivalent length for section LM Tubing equivalent length after size increase Standard tubing equivalent length x Equivalent length correction coefficient Table 2 11 Dimensions for connections of each part Unit in Position A B C D E F G H J Dimension 01 1 2 1 1 4 1 1 8 1 97 8 03 4 05 8 21 2 03 8 _ 2 System Design 2 1 System Example 1 Below are the tables created using the PAC System Diagram Software Details of the calculations are shown in 2 As the maximum tubing length equivalent length is over 295ft in the following selection sample the item 3 is applied due to the main tube size up Outdoor unit 1 Elevation difference 33 ft Outdoor unit 2 Selection conditions Design of 3WAY VRF SYSTEM
111. m Carefully refer to the wiring diagram and these instructions when wiring Improper connections and inadequate grounding can cause accidental injury or death Ground the unit following local electrical codes Connect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard To prevent possible hazards from insulation failure the unit must be grounded When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing Select an installation location which is rigid and strong enough to support or hold the unit and select a location for easy maintenance In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and water damage to walls and floors Keep the fire alarm and the air N outlet at least 5 feet away from the unit In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High Winds Securely anchor the outdoor unit down with bolts and a metal frame Provide a suitable air baffle a Snowy Area for Heat Pump type Systems Install the outdoor unit on
112. m the LCD display To prevent continuous test runs this remote controller includes a timer function that cancels the test run after 60 minutes If the test run is performed using the wired remote controller operation is possible even if the cassette type ceiling panel has not been installed P09 display does not occur 6 Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit Pump down is used when the unit is to be moved or before servicing the refrigerant circuit Refer to the Service Manual This outdoor unit cannot collect more than the rated refrigerant amount as shown by the CAUTION nameplate on the back If the amount of refrigerant is more than that recommended do not conduct pump down In this case use another refrigerant collecting system Test Run 7 Meaning of Alarm Messages 7 Meaning of Alarm Messages Table of Self Diagnostics Functions and Description of Alarm Displays Alarm messages are indicated by the blinking of LED 1 and 2 D72 D75 on the outdoor unit PCB They are also displayed on the wired remote controller Viewing the LED 1 and 2 D72 and D75 alarm displays LED 1 LED 2 Alarm contents Xt AX Alarm display Al LED 1 blinks M times then LED 2 blinks N times The cycle then repeats ternating 2 alarm 3 Halarm 4
113. mensions 5 3 4 2 5 3 4 33 3 16 33 3 16 33 3 16 31 1 8 31 1 8 31 1 8 staleton hole pitch installation hole pitch Installation hole pid Top view unit in 35 a ud 2 Ceiling panel dimensions 7 78 7 7 8 2 1 5 i i O O O I LEE EL IgE sh Front view Right side view 4 Installation Instructions 4 7 Dimensions of Snow Ducting Design of 3WAY VRF SYSTEM Reference diagram for snow proof ducting field supply gt Air direction Air direction Front direction Right direction e allele JE 12 355 254 aD T aT 5 m e 25 Ceiling panel 58 8 s Ceiling panel Iz 31 1 2 31 1 2 5 Air intake duct 54 unit in 3 16 o 9 1 2 Air outlet duct 9 4 2 9 1 2 35 9 1 2 9 1 2 35 9 1 2 Ceiling panel dimensions Ceiling panel dimensions Ceiling panel dimensions 54 32 7 8 32 7 8 1 S e L 2 5 a
114. mount at Shipment for outdoor unit U 72MF1U9 U 96MF1U9 DC U 72MF1U9E U 96MF1U9E oz 416 416 Additional Refrigerant Charge Additional refrigerant charge amount is calculated from the liquid tubing total length as follows Amount of Refrigerant Charge Per ft According to Liquid Tubing Size Liquid tubing size Amount of refrigerant Required amount of additional refrigerant charge Amount of in mm charge oz ft additional refrigerant charge per ft of each size of liquid tube x 91 4 96 35 0 279 its tube length Necessary amount of additional 23 8 99 52 0 602 refrigerant charge per outdoor unit 91 2 912 7 1 38 05 8 015 88 1 99 Always charge accurately using a scale for weighing 93 4 019 05 2 78 07 8 022 22 3 93 U 72MF1U9 U 96MF1U9 U 72MF1U9E U 96MF1U9E 42 oz unit 42 oz unit System Limitations Table 2 1 1 Necessary Amount of Refrigerant Charge Per Outdoor Unit Max No allowable connected outdoor units capacity allowable connected outdoor units 288 000 BTU h 24 Ton 84 kW Max connectable indoor units 40 Max allowable indoor outdoor capacity ratio 50 130 6 1 Up to 3 units can be connected if the system has been extended Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 4 Tubing Size Table 2 2 Ma
115. n shorted condition For a system without link no connection wiring between outdoor units do not remove the short plug 2 Do not install the inter unit control wiring in a way that forms a loop Fig 2 1 X Prohibited l Prohibited Indoor xu z 2 Fig 2 1 3 Do not install inter unit control wiring such as star branch wiring Star branch wiring causes mis address setting Fig 2 2 VE or Branch point Fig 2 2 4 If branching the inter unit control wiring the number of branch points should be 16 or fewer Branches less than 3 3 ft are not included in the total branch number Fig 2 3 Outdoor unit Outdoor unit Outdoor unit 774 77 77 more than 3 3 ft 77 77 77 more than 3 3 ft Indoor unit Indoor unit Branch point 16 or fewer Indoor unit Fig 2 3 3 Electrical Wiring Loose wiring may cause the terminal overheat result in unit malfunction A fire hazard may also exist Therefore ensure that all wiring is tightly connected When connecting each power wire to the terminal follow the instructions on How to connect wiring to the terminal and fasten the wire securely with the fixing screw of the terminal plate How to connect wiring to the terminal For stranded wiring 1 Cut the wire end with cutting pliers then strip the insulation to expose the stranded wiring a
116. nditioning load e Calculate the maximum air conditioning load for each room or zone Selection of an air conditioning system e Select the ideal air conditioning system for air conditioning of each room or zone Design of the control system e Design a suitable control system for the selected air conditioning system m gt Preliminary selection of indoor and outdoor units e Make preliminary selections that are within the allowable range for the system 2 4 2 10 Check of the tubing length and elevation difference e Check that the length of refrigerant tubing and the elevation difference are within the allowable Y 2 4 Calculation of the corrected outdoor unit capacity e Capacity correction coefficient for model 2 11 e Capacity correction coefficient for outdoor temperature conditions 2 11 13 15 e Capacity correction coefficient for tubing length and elevation difference 2 11 14 e Heating capacity correction coefficient for frosting defrosting 2 11 13 Calculation of the corrected capacity for each indoor unit e Capacity correction coefficient for indoor temperature conditions 2 11 14 e Capacity distribution ratio based on the tubing length and elevation difference 2 11 14 Calculation of the actual capacity for each indoor unit Calculate the corrected indoor out
117. ng at max diameter lt 26272 eng 11 12 140 length of each distribution tube lt 98 L1 014 22 240 Total max tubing length including length of A 9B LF LG LH each distribution tube only liquid tubing 984 L5 Distance between outdoor units lt 32 H1 When outdoor unit is installed higher than indoor unit lt 164 Allowable elevation When outdoor unit is installed lower than indoor unit lt 131 difference H2 Max difference between indoor units lt 49 H3 Max difference between outdoor units lt 13 Allowable length of L3 T joint tubing field supply Max tubing length between lt 6 6 joint tubing the first T joint and solidly welded shut end point p L Length H Height 1 The outdoor connection main tubing LO portion is determined by the total capacity of the outdoor units that are connected to the tube ends 2 If the longest tubing length L1 exceeds 295 ft equivalent length increase the sizes of the main tubes LM by 1 rank for the discharge tubes suction tubes and narrow tubes field supplied 3 If the longest main tube length LM exceeds 164 feet increase the main tube size at the portion before 164 ft by 1 rank for the suction tubes and discharge tubes field supplied For the portion that exceeds 164 feet set based on the main tube sizes LA listed in the table on the following page 2 4 Design of 32WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Refrigerant Charge A
118. ng to the temperature conditions tubing length elevation dif ference and other factors select the correct model after taking into account the various correction values When selecting The model calculate the corrected capacities of the outdoor unit and each indoor unit Use the corrected outdoor unit capacity and the total corrected capacity of all the indoor units to calculate the actual final capacity of each indoor unit 1 Outdoor unit capacity correction coefficient Find the outdoor unit capacity correction coefficient for the following items 1 Capacity correction for the outdoor unit model The capacity correction coefficient is 1 00 2 Capacity correction for the outdoor unit temperature conditions Cooling From the graph of capacity characteristics on page 2 13 Graph of Outdoor Unit Capacity Characteristics use the outdoor temperature to find the capacity correction coefficient Heating From the graph of capacity characteristics on page 2 15 use the outdoor temperature to find the capacity correction coefficient Indoor air intake temperature should be set to 68 FDB 3 Capacity correction for the outdoor unit tubing length and elevation difference From the graph of capacity change characteristics on page 2 14 use the tubing length and elevation difference to find the capacity correction coefficient The outdoor unit correction coefficient is the value which corresponds to the most demanding indoor unit 4 Capacity cor
119. nitNo 2 1 2 3 OFF Move the socket to Unit P the OPEN side 2 003 Sub 0 Inter unit control wiring QN Inter outdoor unit control wiring X Indoor unit 2 1 2 2 2 0 other system link wiring Remote Remote control communication wiring controller Make settings as appropriate for the cases listed below Refer to the instructions on the following pages Indoor and outdoor unit power can be turned ON for each system separately Case 2 Indoor and outdoor unit power cannot be turned ON for each system separately Y Case Automatic address setting in Heating mode Y Case 3B Automatic address setting in Cooling mode Fig 5 6 Test Run 4 Auto Address Setting Case 2 Automatic Address Setting no compressor operation Indoor and outdoor unit power can be turned ON for each system separately Indoor unit addresses can be set without operating the compressors Automatic Address Setting from Outdoor Unit ON 1 Onthe No 1 main unit control PCB set the unit No switch S007 to N g unit No 1 1 23 ON On the No 2 sub unit control PCB set the unit No switch S007 to g a g unit No 2 1 2 3 On the No 3 sub unit control PCB set the unit No switch 5007 to w E unit No 3 1 2 3
120. nits in that sys tem Ruh 1 then Actual heating capacity of each indoor unit 7 Corrected heating capacity of each indoor unit 5 x 0 1 x Ruh 0 9 Ruh In other words the correction coefficient 6 based on the corrected indoor outdoor capacity ratios for each indoor unit is the underlined part in the formula above Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Refer to the graph below for the correction coefficients for Ruc and Ruh Indoor unit capacity correction coefficient for Ruc cooling Indoor unit capacity correction coefficient for Ruh heating Indoor unit capacity correction coefficient 0 4 0 5 0 6 0 7 0 8 0 9 1 2 1 7 1 8 1 9 2 0 Corrected S ratio ne or BN When Ruc or Ruh is less than or equal to 1 0 the indoor unit capacity correction coefficient for both Ruc and Ruh is 1 0 5 Graph of capacity correction coefficients Graph of outdoor unit capacity characteristics 1 2 Outdoor unit cooling capacity characteristics Outdoor unit heating capacity characteristics o 120 o 120 2 2 S S 110 5 110 5 100 2 g 8 90 Q Q 5 100 g 80 8 70 8 9 60 5 6 50 8 80 w 40 23 32 41 50 59 68 77 86 95 104 113 m 4 5 14 23 32 41 50 59 Outdoor air intake temp F DB Outdoor air intake temp F WB Outdoor unit heating capacity correction coeffi
121. ns 35 Ceiling panel dimensions 33 3 16 Air direction Front direction Air direction Right direction pas 35 35 35 Ceiling panel dimensions panel dimensions E lt j g panel dimensions Ceiling panel dimensions 35 1 4 5 1 ing p Maximum bracket dimensions ai N e e PORK IKKREKKRE KKK lt 2222222224 2 eet e E 1 2 lt Te e PORK m eene EK 0520 1 1 0000600050 2 4 4 1 4 E m Front view Right side view Front view Right side view Note Can be installed so that the air direction is to the front right left or rear direction 3 unit installation 113 3 installation maximum dimensions 74 1 4 2 unit installation maximum di
122. nsafe practice which can result in personal CAUTION injury product property damage 1 Accessories Part Name i Remarks Washer For hanging bolts Hanging hook Used to hang the Solenoid Valve Kit screw L 15 32 For hanging hook Tapping screw L 5 16 For Solenoid Valve Relay Kit Wire holder For Solenoid Valve Relay Kit wiring 3 Way connect wire 6 5ft ACC 3WAY AAB Solenoid Valve Relay Kit 2 Positioning for Installation e The solenoid valve kit produces some refrigerant noise it is to be installed in a quiet place such as a hospital library or hotel it is recommended that the solenoid valve kit be installed in the ceiling of a corridor etc apart from the room Room Room Indoor unit Indoor unit 777 WM A Recommended installation Solenoid valve kit Avoid Solenoid valve kit Corridor Corridor 2 51 Design of 3WAY VRF SYSTEM 7 Optional Parts e Be sure to secure the solenoid valve kit to the structure and the hanging bolts etc using the top or side holes of the hanging hooks Do not place the solenoid valve kit directly on the ceiling surface When installing the solenoid valve kit remember to install it with the top surface facing upward See the figure shown in the subsection How to use the fittings in 3 Valve Dimensions and Hanging Front side Method e Provide
123. nt that are the same size as LA can be changed In this case it is necessary to recalculate the actual indoor unit 2 20 Calculation of additional refrigerant charge amount e Calculate the additional refrigerant charge from the diameters and lengths of the refrigerant tub ing Even if the wide tubing diameter was increased determine the additional refrigerant charge based only on the narrow tubing SiZ ssa aaaea E nre 2 21 Check the minimum indoor capacity limit density with respect to the amount of refrigerant If the limit density is exceeded be sure to install ventilation equipment or take other corrective steps 2 22 Design of electrical wiring capacity Select a wiring capacity according to the method of power 2 24 2 3 Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 3 Tubing Length Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below 1 Main tubing length LM LA lt 262 ft 2 Main distribution tubes LC LH are selected according to the capacity after the distribution joint 3 The outdoor connection main tubing LO portion is determined by the total capacity of the outdoor units that are connected to the tube ends Sizes of indoor unit connec
124. nt tubing Outdoor unit 4 tube layout Outdoor unit 3 tube layout 2 2 tube layout Indoor unit Suction tube Suction tube Gas tube Discharge tube Discharge tube Liquid tube Liquid tube Liquid tube Balance tube Install the solenoid valve kit 98 ft or less from the indoor unit In quiet locations such as hospitals libraries and hotel rooms the refrigerant noise may be somewhat noticeable It is recom mended that the solenoid valve kit be installed inside the corridor ceiling at a location outside the room _ Desrabe _ OD Undesirable i Room TRoom i Room TRoom I I I Indoor unit I Indoor unit I I Indoor unit Indoor unit I I I I I I I I I I 1 I I 1 I I I I I I I I I I I a m Hallwa Hallwa 5 E y Solenoid 20258 ee eee S 28 Solenoid valve kit Common solenoid valve kit Multiple indoor units under group control can utilize a solenoid valve kit in common Categories of connected indoor unit capacities are determined by the solenoid valve kit Type of solenoid valve kit Total capacity of indoor units BTU h 160 19 000 lt Total capacity lt 54 600 56 7 500 lt Total capacity lt 19 000 Ifthe capacity range is exceeded use 2 solenoid valves connected in parallel 2 When adding ball valve
125. oid Solenoid m T valve p valve b valve 1 1 Fusible Outside air 0 2 Fusible plug Electronic 4 control valve 28 L Electronic control valve U 96MF1U9 U 96MF1U9E lt gt Thermistor position Solenoid High pressure switch tps Low pressure sensor valve N AC1 i 5 22 M To be brazed pinch INV 0 after oil is inserted 1 portion te gt o o lt Oil separator Balance tube Oil drain sel amp n 03 8 flare connection 2 Solenoid valve b Strainer am 2 Suction tube 97 8 Brazing Use supplied only 5 For LP Zt r High Pressure sensor p lt gt For HP gj Discharge tube 93 4 Brazing Use supplied onl P P di g pp y LA A Narrow tube 4 way 4 way 93 8 Brazing 5 1 valve 6 valve olenoid Solenoid Solenoid B Fusible J valve D valve valve plug Outside air 0 10 Fusible i plug Electronic control valve 5 Electronic control valve 4 15 1 Outdoor Unit 1 6 Noise Criterion Curves
126. on both indoor and outdoor units using the same pipings f the additional installment of outdoor and indoor units expected the size of refrigerant piping should be decided according to the total capacity after the addition Combination of outdoor units The DC inverter unit can be used independently or in combination e R407C models and R22 models must not be used in combination with each other Outline of 3WAY VRF SYSTEM 2 Features of 3WAY SYSTEM B Dimensions 6 8 Ton Air X intake _ 6 Ton U 72MF1U9 U 72MF1U9E 8 U 96MF1U9 U 96MF1U9E 2 g 5 58255 D N Installation hole pitch 35 Ceiling panel dimensions Unit in Top view B Dimensions of unit combinations 12 14 16 Ton 74 Ceiling panel dimensions 35 4 35 Ceiling panel dimensions Ceiling panel dimensions Ceiling panel dimensions Installation hole pitch Maximum dimensions 31 1 8 31 1 8 Installation hole pitch 70 1 8 Installation hole pitch Installation hole pitch Unit in Top view 18 20 22 24 Ton 113 Ceiling panel dimensions 35 2 35 Ceiling panel dimensions Ceiling panel dimensions al ah lt
127. ons Unit Specifications 3 PERFORMANCE ee Cooling capacity BTU h kW Heating capacity BTU h kW in in mm BM 3 5 UNIT DIMENSIONS Ceiling dimension 35 2 3 8 890 60 Net weight 573 260 573 260 Color Munsell code ELECTRICAL RATINGS CE EET ARTE Voltage rating 230 5 3 3 k c 30 2 28 4 106 935 30 9 116 94 0 Inverter driven Rotary type x 1 kW 1 40 5 3 liters W 25 ra 5 __ 4 Ibs kg R410A 25 9 11 8 Defrost method Heat exchanger Aluminum plate fin Copper tube FAN DEVICE SSeS eS eS Se Propeller fan x 1 CF 5 300 in 0 0 0 7 8P Motor output No of poles High pressure switch overcurrent CT method Protective devices itch TUBING in ee 7 7 7 7 7 7 i F Cooling 14 113 F DB Heating 4 59 WB Connection tubing Connection tubing 07 8 022 22 03 4 019 05 27 8 922 22 63 4 919 05 Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Running amperes Power input Power factor Running amperes Power input Power factor Cooling Heating A Starting amperes COMPRESSOR Type Q ty Motor output A Refrigeration oil Charge amount Crankcase heater Capacity control Refrigerant amount at shipment Refrigerant control M W 5
128. oor Unit 4P terminal board Z 1 ALWAYS WITH NATIONAL AND LOCAL CODE REQUIREMENTS 4P terminal board s H H H 1 He E gt ILI mie 9996 L 1 2 4 Ly Ly L1 L2 L3 Inter unit Inter outdoor control unit control wiring wiring Indoor Unit U1 E1 Types Y1 D1 T1 F1 M1 P1 R1 Types 7P terminal board 1 L1 2 L2 U1 U2 R1 R2 Power Unit Remote supply control control Line Line K1 Type Model S 07MK1U6 S 09MK1U6 S 12MK1U6 5P terminal board Power Unit supply control Line 6P terminal board 50965 a e E U2 R1 R2 L2 Ui Power Unit supply control Line Remote control Line K1 Type Model S 18MK1U6 S 19MS1U6 S 24MK1U6 5P terminal board 1 2 L1 L2 Power supply ee U1 U2 Unit control Line Design of 3WAY VRF SYSTEM 3 Electrical Wiring 1 When linking outdoor units in a network disconnect the terminal extended from the short plug CN003 2P Black location right bottom on the outdoor main control PCB from all outdoor units except any one of the outdoor units When shipping I
129. ortant part of your job to install or service the system so it operates safely and efficiently For safe installation and trouble free operation you must Carefully read this instruction booklet before beginning e Follow each installation or repair step exactly as shown Observe all local state and national electrical codes Pay close attention to all warning and caution notices given in this manual This symbol refers to a hazard or N WARNING unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can result CAUTION N NA in personal injury or product or property damage If Necessary Get Help These instructions are all you need for most installation sites and maintenance conditions If you require help for a special problem contact our sales service outlet or your certified dealer for additional instructions In Case of Improper Installation The manufacturer shall in no way be responsible for improper installation or maintenance service including failure to follow the instructions in this document SPECIAL PRECAUTIONS When Wiring ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH ONLY A QUALIFIED EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked Highly dangerous electrical voltages are used in this syste
130. ot be done from the remote controller Automatic Address Setting from the Remote Controller Selecting each refrigerant system individually for automatic address setting Automatic address setting for each system Item code A1 1 Next press either the temperature setting 4 __ L Y button Use either the or button to set the system No to perform automatic Then press the button Press the remote controller timer time 4 button and button at the same time Press and hold for 4 seconds or longer Check that the item code is A1 address setting Automatic address setting for one refrigerant system begins When automatic address setting for one system is completed the system returns to normal stopped status Approximately 4 5 minutes is required During automatic address setting is displayed on the remote controller This message disappears when automatic address setting is completed Repeat the same steps to perform automatic address setting for each successive system 5 10 Test Run 4 Auto Address Setting Display during automatic address setting On outdoor main unit PCB LED 2 1 B Bg Do not short circuit the automatic address setting pin CN100 again while automatic address setting is in WH progress Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF Blink alternately When automat
131. other RC line is executing auto address operation Error in auto address setting Number of connected indoor units E 15 is less than the number set When turning on the power Error in auto address setting Number of connected indoor units E16 supply number of connected is more than the number set units does not correspond to No indoor unit is connected during auto address setting E20 number set Except address is 0 Main outdoor unit is detecting error signal from sub outdoor unit E24 Error of outdoor unit address setting E25 The number of connected main and sub outdoor units do not E26 correspond to the number set at main outdoor unit PCB Error of sub outdoor unit in receiving serial communication signal E29 from main outdoor unit Indoor unit communication error Error of main indoor unit in receiving serial communication signal E18 of group control wiring from sub indoor units Improper setting This alarm message shows when an indoor unit for multiple use 102 is connected to the outdoor unit Duplication of main indoor unit address setting in group control lt L03 gt Duplication of outdoor R C address setting L04 There are 2 more indoor unit Priority set remote controller 105 controllers that have operation mode priority in refrigerant circuit Non priority set remote controller 106 Group control wiring is connected to individual control indoor unit 107 Indoor unit address is not
132. pprox 3 8 and tightly twist the wire ends Fig 2 4 2 Using a Phillips head screwdriver remove the terminal screw s on the terminal plate 8 Using a ring connector fastener or pliers securely clamp each stripped wire end with a ring pressure terminal 4 Place the ring pressure terminal and replace and tighten the removed terminal screw using a screwdriver Fig 2 5 2 27 Strip 3 8 Design of 3WAY VRF SYSTEM _Stranded wire_ pressure terminal Fig 2 4 Special washer Screw T uis pressure db terminal Screw and 5 Special washer Terminal plate Ring Lone terminal 3 Electrical Wiring 3 4 Important Note When Wiring for Common Type Connect the wires referring to the diagram Note that the control wirings Low voltages shall be segregated from the power supply wires High voltage as follows 1 Connect the Inter unit control wiring to U1 U2 terminals and the remote control wire to R1 R2 excepting K1 type 2 Connect the power supply wires to L1 L2 of the terminal block Be sure to connect the grounding conductor of the incoming power supply to the earth ground screw 3 Securely affix the power supply wires and remote control wires by the clamping strap or clamping clip not to cross each other and not to leave the wirings loose When loosening the clamping clip twist the strap and it will come undone Design of 3WAY VRF SYSTEM Clamping clip
133. r Side unit unit Indoor unit I Side In case of vertical position IM 1 In case of horizontal position directed upward or downward Direction of Indoor unit Distribution Joint e When brazing replace air inside the tube with nitrogen gas to prevent copper oxide from forming e To insulate the distribution joint use the supplied tubing insulation If using insulation other than that supplied make sure that its heat resistance is 248 F or higher e For additional details refer to the installation instructions provided with the outdoor unit Design of 3WAY VRF SYSTEM 7 Optional Parts CZ P224BH1U CZ P680BH1U CZ P1350BH1U for R410A How to Attach Distribution Joint 1 Accompanying Parts Check the contents of your distribution joint kit 2 Distribution Joint Kits with insulation
134. r the straight equivalent length of joints Table 2 8 Straight Equivalent Length of Joints Unit ft G bi 1 2 5 8 3 4 7 8 1 1 1 8 1 3 8 as tubing size in mm 12 7 15 88 19 05 22 22 25 4 28 58 38 1 90 elbow Ry 1 1 1 1 4 1 6 1 7 1 9 2 5 45 elbow oo 1 12 1 14 18 U shape tube bent 82 23 64 3 15 16 in 17 3 3 4 4 1 4 7 5 1 5 6 7 4 Trap bend UNII 75 9 2 10 5 125 141 154 19 2 Y branch distribution joint eu Equivalent length conversion not needed Ball valve for service Equivalent length conversion not needed Design of 32WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator Check of limit density Always check the gas den WARNING sity limit for the room which the unit is installed 1 7 Check of limit density When installing an air conditioner in a room it is neces sary to ensure that if the refrigerant gas accidentally leaks out its density does not exceed the limit level for that room Pay special attention to any location such as a basement etc where leaking refrigerant can accumulate since refrig erant gas is heavier than air Design of 3WAY VRF SYSTEM 1 Model Selecting and Capacity Calculator 1 8 Calculation of Actual Capacity of Indoor Unit Calculating the actual capacity of each indoor unit Because the capacity of a multi air conditioner changes accordi
135. re recently revised ASHRAE 15 ASHRAE 34 Precautions for Installation Using New Refrigerant 1 Care regarding tubing 1 1 Process tubing e Material Use C1220 phosphorous deoxidized copper specified in JIS H3300 Copper and Copper Alloy Seamless Pipes and Tubes For tubes of 7 8 22 22 mm or larger use C1220 T 1 2H material or H material and do not bend the tubes e Tubing size Be sure to use the sizes indicated in the table below e Use a tube cutter when cutting the tubing and be sure to remove any flash This also applies to distribution joints optional e When bending tubing use a bending radius that is 4 times the outer diameter of the tubing or larger Use sufficient care in handling the tubing Seal the tubing ends with caps or tape to prevent dirt moisture or other foreign substances from entering These substances can result in system malfunction Unit in mm Material Outer diameter 1 4 6 35 3 8 9 52 1 2 12 7 5 8 15 88 3 4 19 05 tube Wall thickness 1 32 0 8 1 32 0 8 1 32 0 8 5 128 1 0 over5 128 10 Unit in mm Material 1 2 H H TN Outer diameter 7 8 22 22 1 25 4 1 1 8 28 58 1 1 4 31 75 1 1 2 38 1 1 5 8 41 28 opper tube EP Wall thickness 5 128 1 0 5 128 1 0 5 128 1 0 3 64 1 1 over 3 64 1 15 over 3 64 1 20 1 2 Prevent impurities including water dust and oxide from ente
136. rection for outdoor unit frosting defrosting during heating From the table on page 2 13 find the capacity correction coefficient 2 Indoor unit capacity correction coefficients Find the indoor unit capacity correction coefficient for the following items 2 Capacity correction for the indoor unit temperature conditions From the graph of capacity characteristics on page 2 14 Graph of Indoor Unit Capacity Characteristics use the indoor temperature to find the capacity correction coefficient 3 Capacity distribution ratio based on the indoor unit tubing length and elevation difference First in the same way as for the outdoor unit use the tubing length and elevation difference for each indoor unit to find the correction coefficient from the graph of capacity change characteristics on page 2 14 Then divide the result by the outdoor unit correction coefficient to find the capacity distribution ratio for each indoor unit Capacity distribution ratio for each indoor unit 3 Correction coefficient for that indoor unit Correction coefficient for the outdoor unit 3 Calculating the corrected capacities for the outdoor unit and each indoor unit The corrected capacities for the outdoor unit and each indoor unit are calculated form the formula below Cooling Outdoor unit corrected cooling capacity b Outdoor unit rated cooling capacity x Correction coefficient for model 1 Page 2 11 x Correction coefficient for
137. ring Diagram U 96MF1U9 U 96MF1U8E 6 4 2 Indoor Unit Refer to the 2WAY VRF SYSTEM TECHNICAL DATA TD831157 Electrical Data 1 Outdoor Uni 1 Electric Wiring Diagram U 72MF1U9 U 72MF1U9E 9500900050000 11 81836128 81819161 2 00060000 LAON H ZH IH HA oe aud ovd zasa No Es SdH 541 5 88 l 88 88 8 8 8 88 8 88 88 ni 10X3 135 ppp Pee 2 P 3 3 17 RT HE iH 1717 17 RE Ts DI 9009090 210 000000600 000000 090000 90060 990060000 090000 ELEL 1 151 CCEE CL CEELI CELT EDT 181 81819161 818 49181916 1 5 2 2 1 9 2 SH 541 j 3 1 EHSIO 1 2510 10 YAYO AWA Add ZAO 120 ZMS 1806 JAYS 20 Ad YAON TAON 02 0 ong 5 5 cw one ong ong ma AYE 130 mg 039 ong avoa 11012813 1
138. ring the tubing Impurities can cause R410A refrigerant deterioration and compressor defects Due to the features of the refrigerant and refrigerating machine oil the prevention of water and other impurities becomes more important than ever 2 Be sure to recharge the refrigerant only in liquid form 2 1 Since R410A is a non azeotrope recharging the refrigerant in gas form can lower performance and cause defects in the unit 2 2 Since refrigerant composition changes and performa nce decreases when gas leaks collect the remaining refrigerant and recharge the required total amount of new refrigerant after fixing the leak 3 Different tools required 3 1 Tool specifications have been changed due to the characteristics of R410A Some tools for R22 and R407C type refrigerant systems cannot be used New R407C tools Manifold gauge Item tool compatible Remarks with R410A Manifold gauge Yes No Types of refrigerant refrigerating machine oil and pressure gauge are different Charge hose Yes No To resist higher pressure material must be changed Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped with a check valve If it has no check valve purchase and attach a vacuum pump adapter Leak detector Yes No Leak detectors for CFC and HCFC that react to chlorine do not function because Vacuum pump R410A contains no chlorine Leak detector Outlet for HFC134a can
139. rter for compressor is unusual DC compressor does not P29 operate Thermistor Indoor thermistor is either open Indoor coil temp sensor E1 lt lt F01 gt gt fault or damaged Indoor coil temp sensor E2 lt lt F02 gt gt Indoor coil temp sensor E3 lt lt F03 gt gt Indoor suction air room temp sensor TA lt lt F10 gt gt Indoor discharge air temp sensor BL lt lt F11 gt gt Outdoor thermistor is either Comp No 1 discharge gas temp sensor DISCH1 F04 open or damaged Comp No 2 discharge gas temp sensor DISCH2 F05 Outdoor No 1 coil gas temp sensor EXG1 F06 Outdoor No 1 coil liquid temp sensor EXL1 F07 Outdoor air temp sensor AIR TEMP F08 Compressor intake port temperature sensor SCT F12 High pressure sensor F16 Low pressure sensor failure F17 Outdoor No 2 coil gas temp sensor EXG2 F23 Outdoor No 2 coil liquid temp sensor EXL2 F24 EEPROM on indoor unit P C B failure F29 Protective Protective device for compressor EEPROM on the main or sub outdoor unit PCB has failed F31 device for No 1 is activated Current is not detected when comp No 1 is ON compressor is Discharge gas temperature of the comp No 1 is not detected activated Temp sensor is not seated at the sensor holder H05 Protective device for compressor Compressor No 2 current trouble overcurrent H11 No 2 is activated Compressor No 2 current trouble locked H12 Compressor No 2 CT sensor disconnected or short cir
140. s from all service ports on the outdoor unit Fig 2 30 Note that all service valves on the outdoor unit are kept closed at this stage The balance tube leak test is not necessary if only 1 outdoor unit is installed Leak test 1 Attach a manifold valve with pressure gauges and dry nitrogen gas cylinder to all service ports with charge hoses The balance tube leak test is not necessary if only 1 outdoor unit is installed Use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed 2 Pressurize the system to no more than 512 psig 86 kgf cm G with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 512 psig 36 kgf cm G Then test for leaks with liquid soap To avoid nitrogen entering the refrigerant system in a liquid state the top of the cylinder must be higher than the bottom when you pressurize the system Usually the cylinder is used in a vertical standing position 2 44 Design of 3WAY VRF SYSTEM Manifold gauge Vacuum pump Fig 2 29a Fig 2 29b Valve cap Fig 2 30 Charge hose Oylinder valve es 1 Nitrogen gas cylinder In vertical standing position Suction tube Outdoor unit Discharge tube Liquid tube Balance tube Fig 2 31 6 AIR PURGING 3 Do a leak test of all jo
141. s digit and 20s digit f 10 systems or more are set the setting is made by a combination of this DIP switch and S002 f 10 19 systems are set set switch 1 10s digit to ON f 20 29 systems are set set switch 2 20s digit to ON and set switch 1 10s digit to OFF f 30 systems are set set both switch 1 10s digit and switch 2 20s digit to ON For details concerning S002 and S003 refer to Table 7 1 S004 Rotary switch 10 positions red Switch for setting the number of connected indoor units In order to allow the outdoor unit to manage indoor units in the same refrigerant system set the number of connected indoor units For details refer to Table 7 2 S005 DIP switch 3P blue Switches for setting the 10s 20s and 30s digit for the number of connected indoor units f 10 systems or more are set the setting is made by a combination of this DIP switch and S004 f 10 19 systems are set set only switch 1 10s digit to ON f 20 29 systems are set set switch 2 20s digit to ON and set switch 1 10s digit to OFF f 30 39 systems are set set only switch 3 30s digit to ON For details concerning S004 and 005 refer to Table 7 2 S006 DIP switch blue Switch for setting the number of outdoor units Turn the switches ON according to the number of outdoor units 1 4 For details refer to Table 7 3 S007 DIP switch blue Unit No setting switch The setting is 1 at
142. set L08 Capacity code of indoor unit is not set lt lt L09 gt gt Capacity code of outdoor unit is not set L10 Mis match connection of outdoor units that have different kinds of L17 refrigerant Continued 7 Meaning of Alarm Messages Test Run Possible cause of malfunction s Activation of Protective device in indoor unit Thermal protector in indoor unit fan motor is activated lt lt P01 gt gt protective is activated Improper wiring connections of ceiling panel lt lt P09 gt gt device Float switch is activated lt lt P10 gt gt O2 sensor detects low oxygen level activated P14 Protective device in outdoor Incorrect discharge temperature Comp No 1 P03 unit is activated High pressure switch or over load relay is activated Power supply voltage is unusual The voltage is less than 160 V P04 between L1 and L2 phase Negative defective phase P05 Compressor running failure resulting from missing phase in the P16 compressor wiring etc Start failure not caused by IPM or no gas Incorrect discharge temperature Comp No 2 P17 Outdoor unit fan motor is unusual P22 Overcurrent at time of compressor runs more than 80Hz DCCT secondary current or ACCT primary current is detected at a time P26 other than when IPM has tripped IPM trip IPM current or temperature H31 Inve
143. ss slanted slightly upward 15 to 30 Cutting point 4 N Indoor unit Side utdoor unit Make this as long as Side possible Insertion length of the 15 to 30 connecting tube upward slant d In case of horizontal position When brazing replace air inside the tube with nitrogen gas to prevent copper oxide from forming To insulate the distribution joint use the supplied tubing insulation If using insulation other than that supplied make sure that its heat resistance is 248 F or higher For additional details refer to the installation instructions provided with the outdoor unit L In case of vertical position directed upward or downward Design of 3WAY VRF SYSTEM 7 Optional Parts 7 2 Solenoid Valve Kit for 3WAY VRF System CZ P56HR1U CZ P160HR1U For safety installation and trouble free operation you must e Carefully read this instruction booklet before beginning e Follow each installation or repair step exactly as shown e Observe all local state and national electrical codes Pay close attention to all warning and caution notices given in this manual This symbol refers to a hazard or unsafe practice which can result in severe WARNING personal injury or death This symbol refers to a hazard or u
144. stte Type and Slim Low Static Ducted Type Refer to the 2WAY VRF SYSTEM TECHNICAL DATA TD831157 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications 1 1 Specifications Unit Specifications 1 3WAY SYSTEM Capacity Control Outdoor Unit lt 6 gt MODEL No U 72MF1U9 U 72MF1U9E SOURCE 208 230V 3N 60Hz PERFORMANCE Cooling capacity 72 000 21 1 Heating capacity 81 000 23 7 i 82 9 16 2097 UNIT DIMENSIONS 35 890 Ceiling dimension 35 Net weight 573 260 Color Munsell code Silky shade 1Y 8 5 0 5 ELECTRICAL RATINGS Voltage rating Power factor Heating kW kW A 9o o o o Starting amperes COMPRESSOR Type Q ty Motor output gt m Inverter driven Rotary type x 1 FV68S Ether oil 1 40 5 3 liters Type Charge amount Refrigeration oil Crankcase heater Capacity control Refrigerant amount at shipment Refrigerant control Defrost method Heat exchanger FAN DEVICE Type Q ty Air circulation External static pressure Motor output No of poles Protective devices TUBING 10 100 R410A 25 9 11 8 Electronic expansion valve Reverse cycle defrost outdoor unit cycle defrost Aluminum plate fin Copper tube 25 Propeller fan x 1 5 300 0 7 8 High pressure switch overcurrent method 5 3 3 Suction tube Discharge tube Liquid tube Balance tube
145. supplied connect wire 4 The left over wires connected to the solenoid valve relay kit should be tied up in a bundle of wires by the supplied wire holder not to leave the wires loose as shown in the diagram at right 3 Way connect wire supplied E DU 5 wires field supplied Class 98ft N 6 oor 1 5 Installation to the Solenoid Valve Relay Kit Install the solenoid valve relay kit into the indoor unit and fix it using a Philips head screwdriver See the diagram in the section of 6 Electrical Wiring Diagrams e Do not install outside the building and the area where the water is splashed Failure to do so could result in product or property damage e Do not handle or touch the unit with wet hands Failure to do so could result in electric shock 2 54 Design of 3WAY VRF SYSTEM 7 Optional Parts 6 Electrical Wiring Diagrams X Make sure that the power supply wiring communication wiring and 3 way wiring will not be crossed each other U1 Type Y1 Type e I T ee e PF l X Solenoid valve Solenoid valve 4 relay kit relay kit 1
146. t and rear 4 brackets total Fig 2 16 Remove the 2 screws 8 screws total MA 5 DER Remove the 2 transport brackets from the front and rear 4 brackets total Fig 2 16 4 11 Routing the Tubing e The tubing can be routed out either from the front or from the bottom Fig 2 17 e The connecting valve is contained inside the unit Therefore remove the front panel Fig 2 17 1 If the tubing is routed out from the front use cutting pliers or a similar tool to cut out the tubing outlet slit part indicated by from the tubing cover Figs 2 17 and 2 18 Remove 11 panel screws from front Use cutting pliers or similar tool to cut cover out Fig 2 17 2 If the tubing is routed out from the bottom remove the slit part e Use a drill bit approximately 13 64 dia to create holes at the 4 slit hole indentations openings e Punch out the slit part KS e Be careful not to damage the base plate Indentation 4 locations Slit hole Fig 2 18 2 37 4 Installation Instructions 4 12 Prepare the Tubing Design of 3WAY VRF SYSTEM e Material Use C1220 phosphorous deoxidized copper as described JIS H3300 Copper and Copper Alloy Seamless Pipes and Tubes For tubes that are 91 925 4 mm or larger use 1 2H material or H material For all others use O material e Tubing size Use the tubing size indicated in the
147. t press the button 4 The address is displayed for 1 of the indoor units which is connected to the remote controller Check that the fan of that indoor unit starts and that air is discharged 5 Press the button again and check the address of each indoor unit in se quence 6 Press the button again to return to normal remote controller mode e Number changes to indicate which Remote Controller Test Run Settings indoor unit is currently selected Press the remote controller button for 4 seconds or longer Then press the Indoor unit address button TEST appears on the LCD display while the test run is in progress gt oO The temperature cannot be adjusted when in Test Run mode UNT This mode places a heavy load on the machines Therefore use it only when per ALE XX XX Vt RC No 5 forming the test run 2 The test run can be performed using the HEAT COOL or FAN operation modes CODE No Note The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is stopped 3 correct operation is not possible a code is displayed on the remote controller Number changes to indicate which LCD display indoor unit is currently selected Refer to Table of Self Diagnostic Functions and correct the problem Indoor unit address 4 After the test run is completed press the button again Check that TEST disappears fro
148. t control wiring should be wired apart from the inter unit power wiring Use shielded wires for inter unit control wiring between units and ground the shield on both sides If the power supply cord of this appliance is damaged it must be replaced by a repair shop appointed by the manufacture because special purpose tools are re quired 3 2 Recommended Wire Length and Wire Diameter for Power Supply System Outdoor unit Time delay fuse or circuit capacity U 72MF1U9 U 72MF1U9E ae U 96MF1U9 45A U 96MF1U9E Indoor unit Time delay fuse yp circuit capacity K1 10 16 D1 Ut Y1 F1 M1 T1 R1 10 16 1 10 16 Control wiring A Inter unit between outdoor and indoor units control wiring B Remote control wiring C Control wiring for group control AWG 18 0 75 mm2 AWG 18 0 75 mm AWG 18 0 75 mm2 3 280 ft 1 640 ft 650 ft Total With ring type wire terminal D Inter outdoor unit control wiring AWG 18 0 75 mm Max 980 ft 3 Electrical Wiring 3 3 Wiring System Diagram Design of 3WAY VRF SYSTEM Indoor unit No 1 Power supply Outdoor unit 208 230V 60Hz 1 PH L2 INV unit ee L1 Power suppl E O pply NER Ground ers 9 r
149. table below e When cutting the tubing use a tube cutter and be sure to remove any burrs The same applies to distribution tubing optional e When bending the tubes bend each tube using a radius that is at least 4 times the outer diameter of the tube When bending use sufficient care to avoid crushing or damaging the tube e For flaring use a flare tool and be sure that flaring is performed correctly Use sufficient caution during preparation of the tubing Seal the tube ends by means of caps or taping to prevent dust moisture or other foreign substances from entering the tubes Refrigerant tubing Existing tubing can be used Tubing size mm Outer dia Thickness Outer dia Thickness 91 4 06 35 11 32 10 8 03 4 919 05 over t5 128 11 0 03 8 09 52 t1 32 10 8 07 8 022 22 15 128 t1 0 91 2 012 7 t1 32 t0 8 91 1 8 028 58 15 128 t1 0 05 8 915 88 t5 128 t1 0 01 3 8 034 92 over t3 64 t1 1 4 13 Connect the Tubing e Use the supplied connector tubing See figure below 72 type 6 Ton EEE 96 type 8 Ton connec
150. tion insulator and platform extend to the inside of the legs In addition the washers used to anchor the unit from the top must be larger than the installation anchor holes Figs 2 13 and 2 14 Unit in Positions where anchor bolts are fastened Installation anchor hole 4 19 32 x 25 32 oval holes The vibration insulator base or platform must be large enough to bear the full surface of the mo Tu unit in base plate legs 2 5 Fig 2 13 ls ale 10 E E 5 olc olo N E g es 5 o E 8 SGo Detailed view of legs DUO PENES 2595 Installation hole pitch T 5 35 2858 Ceiling panel dimensions g 113 Ceiling panel dimensions e o9 35 35 35 Ceiling panel dimensions Ceiling panel dimensions Ceiling panel dimensions ig up MUN 7 Unit 4 19 32 x 25 32 hole 1 33 64 Fig 2 14 35 Ceiling panel dimensions 36 1 4 Installation hole pitch Maximum dimensions 31 1 8 nstallation hole pitch 31 1 8 nstallation hole pitch 31 1 8 nstallation hole pitch 109 Installation hole pitch Top view Fig 2 15 Design of 3WAY VRF SYSTEM 4 Installation Instructions 4 10 Remove the Brackets Used for Transport e After installing the unit remove the 2 transport brackets from the fron
151. tion method Comer bes CD Suction tube Brazed connection No 2 Discharge tube Brazed connection No Liquid tube Brazed connection No 4 Balance tube Flared connection No connection method eerie D Suction tube Brazed connection Yes 03 4 27 8 2 Discharge tube Brazed connection Yes 05 8 93 4 Liquid tube Brazed connection No 4 Balance tube Flared connection No Refrigerant tube port e Use caulking putty or a similar material to fill any gaps at the refrigerant tube port in order to prevent rainwater dust or foreign substances from entering the unit Perform this work even if the tubing is routed out in a downward direction Tubing routed out forward 2 38 Base plate Tubing routed out downward 4 Installation Instructions e Tighten each cap as specified below Tightening torque for each cap Service port cap width 19 32 Valve cap width 55 64 Flare nut valve dia 03 8 60 100 Ibs in 70 120 kgf cm 170 220 Ibs in 200 250 kgf cm 300 360 Ibs in 340 420 kgf cm Do not apply an adjustable wrench to the hexagonal part when Do not use two adjustable wrenches when removing or installing the balance tube flare nut In particular do not apply Design of 3WAY VRF SYSTEM Valve cap
152. tion tubing 01 040 are determined by the connection tubing sizes on the indoor units L1 H3 L2 R410A distribution joint To CZ P900PH1U for outdoor unit CZ P224BH1U for indoor unit CZ P680BH1U indoor unit CZ P1350BH1U for indoor unit mi X H1 040 Balance tubing 03 8 Explanation of symbols 04 extension LF Distribution joint E purchased separately For I extension Ball valve field supply H2 Max 1 3 ft Solenoid valve kit T joint field supply Solidly welded shut gt n pinch weld L4 Note Do not use commercially available T joints for the liquid tubing ulla and parts Be sure to use special R410A distribution joints CZ purchased separately for outdoor unit connections and tubing branches Table 2 1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights Item Mark Contents Length ft Actual length lt 492 L1 Max tubing length _ Equivalent length lt 574 Difference between max length and min AL L2 L4 length from the No 1 distribution joint se Mise tubing LM Max length of main tubi
153. tive internal components e Insure compliance with all local codes 2 Heat Insulation e Be sure to insulate the tubing after finishing leakage inspection e Wrap insulators field supplied having a thickness of 25 64 or more with the heat resistance of 248 F or more around the discharge tubes and gas tubes and 176 For more around the suction tubes and liquid tubes e Wrap around the each tube not to make gaps between the thermal insulation e Failure to conduct shielding gaps and thermal insulation will cause water leakage 2 53 Design of 3WAY VRF SYSTEM 7 Optional Parts 3 Wiring Indoor Unit Class Ifield Solenoid valve relay kit connector ELECTRICAL BOX _ supplied Solenoid valve kit a l 4 Fr gt Wiring from indoor unit PCB 3 Way connect wire 6 5ft supplied Solenoid valve Control PCB 1 2 1 2 3 4 5 5 wires field supplied Class II 98ft Terminal base It requires that the Class I wire and Class II wire should be separated 4 Procedure 1 Connect the power supply wire to the solenoid valve kit co using the Class I wire 2 Connect the solenoid valve kit to the solenoid valve relay kit using the Class II wire 3 Connect the solenoid valve relay kit to the indoor unit using the
154. top of the tubing where it enters the wall As you wrap the tubing overlap half of each previous tape turn 8 Clamp the tubing bundle to the wall using 1 clamp approx each ft Fig 2 27 Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also ensure that the condensation drain hose splits away from the bundle and Apply putty here drips clear of the unit and the tubing Insulated tubes Drain hose Fig 2 27 5 5 Finishing the Installation After finishing insulating and taping over the tubing use sealing putty to seal off the hole in the wall to prevent rain Tubing and draft from entering Fig 2 28 Fig 2 28 2 43 6 AIR PURGING 6 AIR PURGING Air and moisture in the refrigerant system may have undesirable effects as indicated below e pressure in the system rises e operating current rises e cooling or heating efficiency drops e moisture in the refrigerant circuit may freeze and block capillary tubing e water may lead to corrosion of parts in the refrigerant system Therefore the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to remove any noncondensables and moisture from the system E Air Purging with a Vacuum Pump for Test Run Preparation Check that each tube between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed Remove the valve cap
155. uminum plate fin Copper tube FAN DEVICE Air circulation CFM 5 650 5 300 5 300 in WG F 0 7 8P TUBING o o C NN O in mm 1 1 4 831 75 Brazing 208 53 4 18 4 95 4 58 4 20 2 95 9 173 Inverter driven Rotary type x 1 Fixed Speed Scroll tye x 1 Inverter driven Rotary type x 1 Inverter driven Rotary type x 1 2 7 3 75 o Ni A i in mm TIN in mm in mm Cooling 14 113 F DB Heating 4 59 WB Connection tubing 01 1 8 028 58 03 4 019 05 Connection tubing Connection tubing 07 8 022 22 03 4 019 05 07 8 022 22 03 4 019 05 0718 022 22 03 4 019 05 03 4 019 05 05 8 015 88 Primary accessories gt 3 Outdoor unit model name ended with the letter E Refer to the Section 1 3 Salt Air Damage Resistant Specifications Rated conditions Performance electrical characteristics values and operating sound are based on JIS B8616 package A C Cooling Indoor intake air temperature 80 F DB 67 F WB Outdoor intake air temperature 95 F DB Heating Indoor intake air temperature 70 F DB Outdoor intake air temperature 47 F DB 43 F WB 4 8 1 Outdoor Unit 3WAY VRF SYSTEM Unit Specifications Unit Specifications 8 PERFORMANCE Cooling capacity BTU h kW 264 000 77 4 Heating capacity BTU h kW 297 000 87 0 in 82 9 16 2097 in mm 113 2870 Ceilin
156. unit Room 1 indoor unit 1 Room 2 indoor unit 2 Room 3 indoor unit 3 Room 4 indoor unit 4 Selected model 2 54 36 36 24 Load cooling heating BTU h p pun pope Rated capacity cooling heating BTU h ponen pps poen a 5 Corrected capacity cooling heating BTU h cu 7 Actual capacity cooling heating BTU h pow Total corrected capacity of indoor units cooling heating 149 008 00 167 398 40 Ruc 149 008 00 168 609 06 0 884 1 Ruh 167 398 40 173 189 02 0 967 lt 1 For both cooling and heating in all rooms actual capacity is now greater than or equal to the maximum load Selection is completed 2 Calculate the final selection results according to the capacity calculation procedure From calculation of the correction coefficient to calculation of actual capacity Cooling heating Outdoor wait Room 1 Room 2 Room 3 Room 4 indoor unit 1 indoor unit 2 indoor unit 3 indoor unit 4 192 000 54 600 36 000 36 000 25 000 Rated capacity BTU h 216 000 61 400 39 000 39 000 27 000 1 0000 1 Model 00 i 5 2 Temp condition 1 0203 0 9474 0 9474 0 9474 0 9474 P 1 0000 1 0060 1 0060 1 0060 1 0060 o 8 m 0 8607 0 9240 0 9030 0 8818 0 8607 3 3 Tu
157. with open space above the unit The mounting base should be concrete or a similar material that allows for adequate drainage Make provisions for anchor bolts platform height and other site specific installation requirements Leave space open above the CAUTION unit Construct louvers or other openings in the wall if necessary to ensure adequate ventilation Do not do any wiring or tubing within 1 ft of the front panel because this space is needed as a servicing space for the compressor Ensure a base height of 4 in or more to ensure that drainage water does not accumulate and freeze around the bottom of the unit If installing a drain pan install the drain pan prior to installing the outdoor unit Make sure there is at least 6 in between the outdoor unit and the ground Also the direction of the tubing and electrical wiring should be from the front of the outdoor unit 35 Ceiling panel dimensions 31 1 8 Installation hole pitch Design of 3WAY VRF SYSTEM Exhaust fan Hotair lt E 1 7 Heat Out source door unit Fig 2 6 Example of installation of 2 units When wall height is below 6 ft More than 4 in More than 4 in More than 2in More than 1 7 ft More than 4 in However be sure to ensure a space of 1 ft or more at either the right side or the rear of the unit Fig 2 7
158. y a pulse signal to start all indoor units in that refrigerant system Stop 2P plug white Stopt pin CN104 Short circuit this pin and apply a pulse signal to stop all indoor units in that refrigerant system AP 2P plug white Vacuuming pin CN102 To perform vacuuming of the outdoor unit short circuit this pin and then turn the power ON All solenoid valves turn ON and vacuuming begins smoothly Do not perform automatic address setting at this time Release the short circuit to return the unit to normal status Mode 2P plug white Indoor unit Heating Cooling mode change pin CN101 When operating the compressors to perform automatic address setting operation in Heating mode can be normally used However short circuiting this pin performs operation in Cooling mode Static signal Short circuiting this pin during ordinary operation changes the mode from Cooling to Heating if the current mode is Cooling or from Heating to Cooling if the current mode is Heating Test 2P plug white 22 This pin is used to test the PCB at the factory When the power is turned ON after this pin has been short circuited all output signals will be output in sequence Sequential output does not occur if this pin is short circuited when the power is already ON Releasing this pin returns the unit to normal control PCB and Functions 1 Outdoor Unit Control PCB Table 7 1 Setting the System Address S002 Rotary switch bl
159. ylinder Do not use agents intended to prevent the formation of oxide film These agents adversely affect the refrigerant and refrigerant oil and may cause damage or malfunctions 5 2 Connecting Tubing Between Indoor and Outdoor Units 1 Tightly connect the indoor side refrigerant tubing extended from the wall with the outdoor side tubing 2 To fasten the flare nuts apply specified torque as at right When removing the flare nuts from the tubing connections or when tightening them after connecting the tubing be sure to use 2 adjustable wrenches or spanners as shown Fig 2 24 If the flare nuts are over tightened the flare may be damaged which could result refrigerant leakage and cause in injury or asphyxiation to room occupants For the flare nuts at tubing connections be sure to use the flare nuts that were supplied with the unit or else flare nuts for R410A type 2 The refrigerant tubing that is used must be of the correct wall thickness as shown in the table at right 2 41 7 8 unit Design of 3WAY SYSTEM lubricant Fig 2 22 Union Fig 2 23 Torque wrench Fig 2 24 Apply refrigerant i Flare nut Spanner Outdoor unit Tube diameter Tightening torque approximate Tube thickness 91 4 96 35 mm 120 160 Ibs inch 140 180 kgf cm 1 32 0 8 mm 93 8 09 52 mm 300 360 Ibs inch 340 420 k
160. ype Remote control wiring and Inter unit control wiring field supplied S v R a P Ti s Clamping i clip ac P Conduit EPI field supplied dm _ Bue SURI e Power wiring Earth screw field supplied T1 Type Clamping clip Earth screw Power wiring field supplied Remote control wiring field supplied Conduit field supplied Conduit P SRM field supplied field supplied Remote control wiring and Inter unit control wiring field supplied Clamping clip Earth screw P1 R1 Type Clamping clip Power wiring Connection for Solenoid Valve Kit for 3WAY Optional remote control wiring field supplied 3 way connection wiring with harness supplied 2 29 Design of 3WAY VRF SYSTEM 3 Electrical Wiring Important Note When Wiring for Common Type Continued

Download Pdf Manuals

image

Related Search

Related Contents

Produkthandbuch SJ200  Samsung SGH-E800 Vartotojo vadovas  MAQUINAD EHUMO - CLOUD 1000 MANUAL DE INSTRUCCIONES  T'nB CSESPUREBK headphone  POCKET GUIDE - Timex.com assets  1.Getting Started 1.1 Basic Operations 1.1.1 Power On/ Off and Sleep  Krups G VS2 41 ice cream maker  Betriebsanleitung cargostor®T  Poste à découper CUT PLASMA 80A  omment utiliser votre lave  

Copyright © All rights reserved.
Failed to retrieve file