Mitsubishi Electronics FX2NC-ENET-ADP User's Manual

image

Contents

1. Changes for the Better a MITSUBISHI PROGRAMMABLE CONTROLLERS MELSEG F FX2NC ENET ADP Ethernet adapter USER S MANUAL Manual Number JY997D12301 m o ooo This manual contains text diagrams and explanations which guide the reader in the correct installation and operation of the FX2NC ENET ADP Ethernet adapter It should be read and understood before attempting to use the unit If in doubt at any stage of the installation of FX2NC ENET ADP consult a professional electrical technician who is qualified and trained to the local and national standards which apply to the installation site If in doubt about the operation or use of the FX2NC ENET ADP please consult the nearest Mitsubishi Electric distributor This manual is subject to change without notice Microsoft and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other countries The company name and the product name described in this manual are the registered trademarks or trademarks of each company Guideline for the safety of the user and protection of the FX2NC ENET ADP This manual provides usage information for the FX2NC ENET ADP Ethernet adapter The manual has been written to be used by trained and competent personnel Notes on the symbols used in this manual At various times throughout out this manual certain symbols will be used to highlight points of information which are intended to ensu
2. 9 Terminal block for grounding Internally short circuited Applicable cable AWG 17 to 14 Tightening torque 0 4 to 0 5 N m 10 DIN rail mounting hook 11 DIN rail mounting groove 7 Parameter Settings for FX2NC ENET ADP To connect the FX2NC ENET ADP to the Ethernet it is necessary to set the Ethernet parameters including the Header IP address Subnet mask Gateway address and TCP port number Set the Ethernet parameters to the D data registers in the PLC Immediately after the power is turned on the FX2NC ENET ADP reads the Ethernet parameters stored in the D data registers in the PLC and configures itself 7 1 Used devices FX1s Set the Ethernet parameters to nine data registers from D128 to D136 j foes Default inti D128 D129 Header fo Set H454E4554 ENET IP address 192 168 0 100 Set the P address for connecting to Ethernet 2 Subnet mask 255 255 255 0 S t the sub net mask for connecting to Ethernet 3 Gateway Set the gateway address for es ee ee connecting to Ethernet 2 TCP port 1024 Set the TCP ports within the number range from 1024 to 65535 FX1N FX2N F X2NC Set the Ethernet parameters to nine data registers from D1000 to D1008 If these data registers are used for any other purpose the Ethernet parameters can be set to nine data registers D starting from D2000 D3000 D4000 D5000 D6000 or D7000 7 2 Parameter setting methods Set the Ethernet parameters using either of
3. 255 255 255 0 HFFFFFFOO D134 D135 D1006 D1007 Gateway 192 168 0 1 HCOA80001 address Device Label D1000 X D134 D135 16 bit integer Display Device name 0 1 D1000 moos a o D136 D1008 TCP port number 1024 When the PLC program is used to set the Ethernet parameters The Ethernet parameters for the FX2NC ENET ADP can be set using the program shown below Note 7 4 Check of configuration using SD LED and RD LED In the FX2NC ENET ADP the Ethernet parameters become valid only when the power The SD LED and the RD LED can be used to check whether the current is turned ON and the setting data is stored in specified data registers configuration is functioning properly or not In either of the following cases turn off the power of the PLC once and then turn it on At startup reset K1024 Character string TENEn viv ZA 3 4 5 6 7 0 0 0 0 0 0 5 4 Used cable D136 STP Shielded twisted pair cable Category 5 e or 3 TCP port number 1024 6 Wiring 6 1 Cautions on wiring Wiring Precaution e Cut off all phases of external power source before installation or performing wiring work in order to avoid electric shock or damage to the product Wiring Precaution AN e The grounding terminal in the main unit should be connected to a grounding resistance of 1009 or less e Do not drop cuttings and wire chips into the ventilation slits of the PLC when drilling screw holes o
4. D j DISPOSAL PRECAUTIONS Detach To lock the tab 1 e When disposing of this product treat it as industrial waste 2 Outline of Product 4 System Configuration The FX2NC ENET ADP is an Ethernet adapter of 10BASE T specifications for the FX2NC ENET ADP 19 1 10 7 0 28 FX1S FX1N FX2N and FX2NC Series 0 76 Height of screw hole INSTALLATION PRECAUTIONS The FX2NC ENET ADP enables the upload download monitor and test of a program 74 2 92 A e Use the module in an environment that meets the general from the personal computer GX Developer or MX Component via Ethernet 78 3 08 ificati tai in thi Using thi le i s specifications contained in this manual Using this module in an 3 Installation environment outside the range of the general specifications could h result in electric shock fire erroneous operation and damage to or Caution deterioration of the product e Use only in the environments specified under the general specifications LAN e Do not disassemble or modify the module Doing so may cause in the manual l l l cables gt m See E a failure malfunction injury or fire Do not use the product in environments with excessive or conductive dust corrosive including salt breeze Cl2 H2S SO2 NO2 etc or flammable gas oily smoke moisture or rain excessive heat regular impact shocks or excessive vibration as it may result in electrical shock fire malfunction damage or deterioration of the product e Make sure
5. Used to connect the main unit 8 RJ45 connector Connects the Ethernet cable 9 Terminal block for grounding Internally short circuited Applicable cable AWG 17 to 14 Tightening torque 0 4 to 0 5 N m 10 DIN rail mounting hook 11 DIN rail mounting groove 5 3 Connector pin arrangement The RJ45 connector in the FX2NC ENET ADP has the following pin arrangement Pin Signat name Direction Description BE i ee Ee ie Ce ee ee es e a 5 4 Used cable STP Shielded twisted pair cable Category 5 e or 3 6 Wiring 6 1 Cautions on wiring Wiring Precaution e Cut off all phases of external power source before installation or performing wiring work in order to avoid electric shock or damage to the product Wiring Precaution AN e The grounding terminal in the main unit should be connected to a grounding resistance of 10029 or less e Do not drop cuttings and wire chips into the ventilation slits of the PLC when drilling screw holes or performing wiring work Otherwise fire failure or malfunction may occur Another equipment Another Another equipment equipment Dedicated grounding Shared grounding good Common grounding best not possible PLC 6 2 Wiring example Grounding 10092 or less 7 Parameter Settings for FX2NC ENET ADP To
6. 0 2 Character string 4 6 prooo as assa coasoose rrrrrroo C coasoooi poos NL AO A aoaea Header ENET Device Label D1000 X Display Subnet mask 255 255 255 0 Gateway address 192 168 0 1 IP address 192 168 0 110 e Settings of D136 or D1008 16 bit DEC mode Device Label D1000 Device name jpuoos 1024 TCP port number 1024 7 4 Check of configuration using SD LED and RD LED The SD LED and the RD LED can be used to check whether the current configuration is functioning properly or not At startup reset After power is turned on the SD LED and RD LED are lit for 2 seconds and the FX2NC ENET ADP reads the configuration data from the PLC If the configuration data is read correctly the SD LED and RD LED turn off If an error occurs the SD LED and RD LED indicate the error status as shown below SoteD RDTED Descrnton be i of data registers in the PLC cannot be The header ENET cannot be detected 2 OFF ON A parameter such as IP address Gateway address Subnet mask and TCP port number is invalid Note In case of 1 or 2 the parameters such as IP address Gateway address Subnet mask are incorrect and the default parameters are valid 8 Settings in GX Developer Set the IP address the TCP port number and the connection route etc on the Transfer setup dialog box when accessing FX1S FX1N FX2N or FX2NC Series PLC
7. F X2N F X2NC M8002 Setting of Header ASCII codes to specify ENET ByMov H454E4554 D1000 Setting of IP address 192 168 0 110 CO A8 00 6E ByMOV HCOA8006E D1002 Setting of Subnet mask 255 255 255 0 FF FF FF 00 ByMov HFFFFFFOO D1004 Setting of Gateway ByMov HCOA80001 D1006 address 192 168 0 1 CO A8 0001 TCP Port number 1024 6 When connecting two or more PLCs to a network do not use the same IP address twice Example Personal computer GX Developer 192 168 0 10 192 168 0 110 PLC2 192 168 0 111 After power is turned on the SD LED and RD LED are lit for 2 seconds and the FX2NC ENET ADP reads the configuration data from the PLC If the configuration data is read correctly the SD LED and RD LED turn off If an error occurs the SD LED and RD LED indicate the error status as shown below eoo poo Deseipfon Me a of data registers in the PLC cannot be The header ENET cannot be detected 2 OFF ON A parameter such as IP address Gateway address Subnet mask and TCP port number is invalid Note In case of 1 or 2 the parameters such as IP address Gateway address Subnet mask are incorrect and the default parameters are valid 8 Settings in GX Developer 9 Setting in MX Component Set the IP address the TCP port number and the connection route etc on the Note First set Ethernet board at PC Transfer setup dialog box when accessing FX1S FX
8. connect the FX2NC ENET ADP to the Ethernet it is necessary to set the Ethernet parameters including the Header IP address Subnet mask Gateway address and TCP port number Set the Ethernet parameters to the D data registers in the PLC Immediately after the power is turned on the FX2NC ENET ADP reads the Ethernet parameters stored in the D data registers in the PLC and configures itself 7 1 Used devices FX1s Set the Ethernet parameters to nine data registers from D128 to D136 D128 D129 Header fo Set H454E4554 ENET D130 D131 IP address 192 168 0 100 Set the IP address for connecting to Ethernet 2 D132 D133 Subnet mask 255 255 255 0 59t the sub net mask for connecting to Ethernet 3 D134 D135 Gateway 192 168 0 1 Set the gateway address for connecting to Ethernet 2 address 4 TCP port Set the TCP ports within the Dio ne range from 1024 to 65535 FX1N F X2N F X2NC Set the Ethernet parameters to nine data registers from D1000 to D1008 If these data registers are used for any other purpose the Ethernet parameters can be set to nine data registers D starting from D2000 D3000 D4000 D5000 D6000 or D7000 DO000 D0001 Header fo Set H454E4554 ENET DO002 D0003 IP address 192 168 0 100 Set the IP address for connecting to Ethernet 2 todd prois Subnetimasic 255955255 0 ot Me Sub net mask for connecting to Ethernet 3 Gateway Set the gateway addre
9. ethernet A i go n PC IF Ethernet CPU type Time out 60000 ms Module type Host IP Address Port No FX2N C FX ENET ADP 192 168 0110 1024 10 Troubleshooting Turn ON power of PLC No Check the cable connection between FX2NC ENET ADP and PLC Is POWER LED ON Yes No Check if FX2Nc ENET ADP and HUB are connected correctly Check if power of HUB is ON Yes Two seconds after FX2NC ENET ADP is turned ON Execute PING command for IP address set to PLC 1 Check again IP address set to PLC No 2 Confirm that network address in PLC Any response matches network address in PC 3 Confirm connection of Ethernet between PC and PLC Yes Yes Yes Confirm that TCP port number set in GX Check Ethernet Developer or MX Component matches TCP parameters No For details refer to 7 Parameter Parameters are read port number set in PLC Are FX2Nc ENET ADP and PLC connected correctly tly Settings for GOTEC FX2nc ENET _ from PLC ADP Yes Turn ON power again Is any numeric value other than 0 stored in D8120 s communication port set for computer link or no protocol communication Value other than 0 stored in D8120 No Yes Clear communication parameter check box Set 0 to D8120 and download Check if PLC and PC Turn ON power again program Reference The PING command confirms confirmation whether
10. first time e When the setting of a parameter is changed during operation FX1s M8002 Setting of Header PIMov H454E4554 D128 ASCII codes to specify ENET Setting of IP address PMov HCOA8006E D130 192 E 68 P 110 CO A8 00 6E Setting of Subnet mask M mMov HFFFFFFOO D132 255 255 255 0 FF FF FF 00 Setting of Gateway ByMov HCOA80001 D134 address 192 168 0 1 CO A8 0001 K1024 D136 TCP Port number 1024 FX1N F X2N F X2NC M8002 Setting of Header ASCII codes to specify ENET ByMov H454E4554 D1000 Setting of IP address 192 168 0 110 CO A8 00 6E ByMoOV HCOA8006E D1002 Setting of Subnet mask 255 255 255 0 FF FF FF 00 ByMov HFFFFFFOO D1004 Setting of Gateway address 192 168 0 1 CO A8 0001 TCP Port number 1024 B yMov HCOA80001 D1006 6 When connecting two or more PLCs to a network do not use the same IP address twice Example Personal computer GX Developer PLC2 192 168 0 10 192 168 0 110 192 168 0 111 When file registers are used to set the Ethernet parameters Select Parameter PLC parameter Memory capacity in GX Developer and set the file register capacity to 1 block or more Then right click Device memory add the device memory data and set the parameters as shown below e Settings of D128 to D135 or D1000 to D1007 32 bit HEX mode 32 bit integer HEX _x J D0 D7999 Device name
11. in the manual Do not use the product in environments with excessive or conductive dust corrosive including salt breeze Cl2 H2S SO2 NO2 etc or flammable gas oily smoke moisture or rain excessive heat regular impact shocks or excessive vibration as it may result in electrical shock fire malfunction damage or deterioration of the product e Make sure to shut off the external power before installing or wiring it Electric shock or serious damage to the product may occur if the external power is not disconnected e Never drop wire chips or shavings into the ventilation slits when drilling screw holes or performing wiring as they may cause fire breakdown or malfunction e Securely install the FX2NC ENET ADP to the designated port A poor connection may result in malfunction 3 1 How to Install to FX Series PLC Installation to FX1S FX1N FX2N Turn OFF the PLC before beginning any work 1 Remove the panel cover from the top face of the main unit 2 Take off the resin cover from the left side of the main unit 3 Install the following board to the port Installation to FX1S FX1N FX2N on the main unit Corresponding FX1N CNV BD FX1S FX1N 4 Affix the above board using the supplied M3 screws Installation to FX2NC Tightening torque 0 3 to 0 6 N m 5 Connect the built in cable of the FX2NC ENET ADP to the port on the left side of the board Installation to FX2NC Turn O
12. the FX Series PLC except the following items E 500V AC for 1 Conforms to JEM Withstand voltage 1021 between all terminals together 5 MQ or more by and grounding 500V DC megger terminal Power suppi SUppIy voltage 5V DC 135 mA supplied from PLC specifications current CSMA CD IEEE802 3 General specifications Insulation resistance Performance 10BASE T specifications Topology Star type Communication method Full duplex To Ethernet RJ45 connector Connector To ground opis g However internally short circuited 0 kg 022 5 2 Outside dimensions and name of each part 16 1 0 64 to screw holes Unit mm inches 2 4 2 0 17 ole E TPE COCE TORR ll a a a zZ 1 A z l 7 e g Cc 3 8 O 2 vp T a 3 11 ss oO Z 2 ze worn 19 1 10 7 0 28 0 76 Height of screw hole 74 2 92 J 78 3 08 1 Mounting hole 2 04 2 Used when FX2NC ENET ADP is mounted directly Not used when the module is mounted on DIN rail 2 POWER LED green Lit while 5V DC power is supplied from the PLC 3 LINK LED green Lit while the HUB is connected by an RJ45 connector and the power is on 4 ACT LED red Lit while transferring data with connected Ethernet 5 SD LED red Lit while sending data to the connected PLC 6 RD LED red Lit while receiving data from the connected PLC 7 Connecting cable
13. the communication between Ethernet devices using the IP address of TCP IP is possible Memory capacity Jevice PLC name 1 0 assignment PLC system 1 PLC system 2 Execute the PING command from the personal computer connected to Ethernet and check whether the FX2Nc ENET ADP sends a response Refer to the PING command described below Clear the check box FX parameter If the box is not checked the parameters will be cleared Operate When the program is transfered to the communication board parameters and Executing the PING command E ee ages D8120 values in the PLC must be cleard upon program transfer Open the MS DOS prompt command prompt in the Windows2000 XP a In the example parameter settings in Section 7 3 the IP address is set to 192 168 0 110 r S PING 192 168 0 110 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Aa MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN A Note Concerning the CE Marking The CE marking does not guarantee that an entire mechanical module produced in accordance with the contents of the notificatio
14. to shut off the external power before installing or wiring it Electric shock or serious damage to the product may occur if the external power is not disconnected e Never drop wire chips or shavings into the ventilation slits when drilling screw holes or performing wiring as they may cause fire breakdown or malfunction e Securely install the FX2NC ENET ADP to the designated port A poor connection may result in malfunction 1 Mounting hole 2 04 2 Used when FX2NC ENET ADP is mounted directly Not used when the module is mounted on DIN rail 2 POWER LED green Lit while 5V DC power is supplied from the PLC 3 LINK LED green Lit while the HUB is connected by an RJ45 connector and the power is on 4 ACT LED red Lit while transferring data with connected Ethernet 5 SD LED red Lit while sending data to the connected PLC 6 RD LED red Lit while receiving data from the connected PLC 7 Connecting cable Used to connect the main unit 8 RJ45 connector Connects the Ethernet cable LAN cables FX1S FX1N PLC FX1N CNV BD Twisted pair cable FX2N PLC FX2N CNV BD FX2NC ENET ADP Category 5 e STP or 3 STP straight cable FX2NC PLC TRANSPORTATION AND MAINTENANCE PRECAUTIONS e During transportation avoid any impact as the module is a precision instrument Doing so could cause trouble in the module e It is necessary to check the operation of module after transportation in case of any impact damage
15. within 64 characters refer to Chapter 7 For details on the IP address setting for the FX2Nc ENET ADP refer to Chapter 7 8 2 Operations In GX Developer operations such as upload download monitoring and test of a program are performed in the same way as with serial communication 9 Setting in MX Component Note e MX Component must be Version 3 08J or later e FX Configurator EN must be installed on the personal computer For details on the installation method of FX Configurator EN refer to the FX Configurator EN Operation Manual Note In case of Virtual COM Port VCP Driver If using Virtual COM Port VCP Driver add the Logical station number for Ethernet 9 1 Setting method Select Programs MELSOFT Application MX Component Communication Setup Utility Li Communication Setup Utility Menu Help Target setting List view Connection test Logical station number k Wizard 4 Communication Setting Wizard Introduction This Communication Setting Wizard will set the communication information for ACT You can press Back at any time to change your selections Please click Next to begin Please select the logical station number Logical station number 1 X Select the Logical station number Next amp A First set Ethernet board at PC side I F Next set FX ENET ADP at Connect module Communication Setting Wizard PC side Please select the PC sid
16. 1N FX2N or FX2NC Series side I F Next set FX ENET MX Component must be Version 3 08J or later i PLC via Ethernet from GX Developer p ADP at Connect module e FX Configurator EN must be installed on the personal computer For details on the installation method of FX Configurator EN refer to the FX Configurator EN Operation Manual Note In case of Virtual COM Port VCP Driver If using Virtual COM Port VCP Driver add the Logical station number for Ethernet Ji PC side IF Communication Setting Wizard PC side Note e GX Developer must be Version 8 25B or later e FX Configurator EN must be installed on the personal computer For details on the installation method of FX Configurator EN refer to the FX Configurator EN Operation Manual 8 1 Setting method Select Online Transfer setup Communication Setting Wizard Network Please select the Network Station type Host station bd CPU type FR2N C Please select the PC side I F Ethernet board v Communication setting Connect module FX ENET ADP 9 1 Setting method Select Programs MELSOFT Application MX Component Communication Setup Utility Transfer Setup Li Communication Setup Utility Menu Help i 0 zi Serial NET 10 H NET II CC Link Ethernet ssc board board board board net COM COM 1 Transmission speed 9 6Kbps Target setting List view Connection test Logical station number i n
17. DP by the Set the IP address connection destination as assigned to the FX2Nc ENET ADP by the sequence L Communication Setup Utility Menu Help a Logical station number sequence program For details on the TCP port Number setting for the FX2Nc ENET ADP refer to Chapter 7 program When using the Host Name set the name assigned by the hosts file For details on the IP address setting for the FX2Nc ENET ADP refer to Target setting List view Connection test IP input format DEC v IP address 192168 0110 C Host Name Logical station number 1 via FX2NC ENET 4DP E nemt SE _ V gp e eee Chapter 7 Select the Logical station number Port No f 024 Input format decimals PC IF Ethernet CPU type FX2NCC Time out 60000 ms Module type FX ENET ADP Next Host IP Address 192 168 0 110 Port No 1024 Set the TCP Port Number Port No connection destination as assigned to the FX2Nc ENET ADP by the sequence program For details on the TCP port Number setting for the FX2Nc ENET ADP refer to Chapter 7 Set the IP address connection destination as assigned to the FX2Nc ENET ADP by the sequence program When using the Host Name set the name assigned by the hosts file within 64 characters For details on the IP address setting for the FX2Nc ENET ADP refer to Chapter 7 Next 8 2 Operations In GX Developer operations such as upload download monitoring and test of a
18. FF the PLC before beginning any work 1 Remove the cover from the special adapter port provided on the left side of the main unit 2 Connect the built in cable of the FX2NC ENET ADP to the special adapter port 3 2 Installation to a Panel Face Direct installation to the panel face Directly attach to the panel face using 2 sets of a screw M4 a spring washer and a flat washer in the mounting holes Tightening torque 0 7 to 1 0 N m For the pitch and positions of mounting screw holes refer to the external dimensions FX Series Mounting on DIN rail Affix the FX2NC ENET ADP to the DIN rail DIN46277 35 mm 1 37 wide ADP PLC Dismounting from DIN rail Slightly pull down the DIN rail mounting clip using a tool such as a slotted screwdriver Pull down the clip further and the rail will be locked with the clip left open se 4 System Configuration FX2NC ENET ADP X1S FX1N FX2N LAN cables LAN cables STP straight cable FX1S FX1N PLC FX1N CNV BD Twisted pair cable FX2N PLC FX2N CNV BD FX2NC ENET ADP Category 5 e STP or 3 FX2NC PLC e Applicable version of GX Developer MX Component Software Applicable Version With FX Configurator EN GX Developer Ver 8 12N or later Ver 8 25B or later MX Component Ver 3 05F or later Ver 3 08J or later 5 Product Specification 5 1 Specifications The general specifications of FX2NC ENET ADP are same as those of
19. aa 1 Time out 60000 ms Back von J First set Ethernet module at PLC side I F Next set FX ENET ADP at Module type PLC side I F PLC MNET 10 H MNET II CC Link Ethernet C24 G4 Bus module module module module module module Set FX1s FX1N FX2N or FX2nc at CPU type Click Ethernet board P Transfer Setup The Communication wizard has finished collecting information PC side I F ho Serial NET 10 H board a NET II CC Link Ethernet board board board board net Communication Setting Wizard PLC side Please Finish to build the logical station number Please select the PLC side I F i tty PLC side IF Ethernet module PLC side I F Wizard S Communication setting FX ENET ADP Host IP Address 192 168 0110 PLC MNET 10 H MNET II CC Link module module module module Double click Ethernet module E PLC side I F detailed setting of Ethernet module G4 Bus module Module type Comment via FX2NC ENET ADP Communication Setting Wizard Introduction This Communication Setting Wizard will set the communication information for ACT You can press Back at any time to change your Select FX2Nc ENET ADP selections Port No 1024 Enter a comment Please click Next to begin Please select the logical station number Finish 4 Set the TCP Port Number Port No connection destination as assigned to the FX2Nc ENET A
20. address must be in the range from 1 to 223 If any number outside this range is used the RD LED will be lit when the FX2NC ENET ADP is turned on and Ethernet communication will not be performed Set numbers from 1 to 223 3 In the following cases and as explained in 2 concerning the Subnet mask data the RD LED will be lit when the FX2NC ENET ADP is turned on an error will occur and Ethernet communication will not be performed The following conditions are expressed in binary form 1 If 1 is set for all bits 2 If O is set for all bits 3 If 1 is set immediately after 0 is set Example 111 11000100 4 The settings of the IP address Subnet mask and Gateway address depend on the network environment For the contents of these parameters see the network administrator 5 The FX2NC ENET ADP searches for the header in the order D1000 D7000 The values described in lowest data resister numbers are set as the Ethernet parameters again e When a parameter is set for the first time e When the setting of a parameter is changed during operation FX1s M8002 Setting of Header B Mov H454E4554 D128 ASCII codes to specify ENET Setting of IP address BJMOV HCOA8006E D130 192 3 68 0 110 CO A8 00 6E Setting of Subnet mask M mMov HFFFFFFOO D132 255 255 255 0 FF FF FF 00 Setting of Gateway mov HCOA80001 D134 e 192 168 0 1 CO A8 0001 K1024 D136 TCP Port number 1024 FX1N
21. e registered trademarks or trademarks of each company Compliance with all relevant aspects of the standard Radiated Emissions and Mains Terminal Voltage Emissions Compliance with all relevant aspects of the standard RF Immunity Fast transients ESD and Damped oscillatory wave Compliance with all relevant aspects of the standard RF immunity Fast transients ESD Conducted Surges Power magnetic fields Voltage dips and Voltage interruptions Compliance with all relevant aspects of the standard Radiated Emissions Mains Terminal Voltage Emissions RF immunity Fast Transients ESD Surge Voltage drops and interruptions Conducted and Power magnetic fields Installation to FX2NC General specifications EN61000 6 2 2001 Insulation resistance Electromagnetic compatibility Generic standards Immunity for industrial environments Installation to FX2NC Turn OFF the PLC before beginning any work EN61131 2 2003 Programmable controllers 1 Remove the cover from the special adapter port provided on the left side of the Equipment requirements and tests main unit 2 Connect the built in cable of the FX2NC ENET ADP to the special adapter port Performance 10BASE T specifications Topology Star type Communication method For more details please contact the local Mitsubishi Electric sales site Notes for compliance to the EMC regulation It is necessary to install the FX2NC ENET ADP modul
22. e I F PC side IF Ethernet board v Communication setting Connect module FX ENET ADP gt Time out 60000 ms Back von J First set Ethernet module at PLC side I F Next set FX ENET ADP at Module type Communication Setting Wizard PLC side Please select the PLC side I F PLC side IF Ethernet module v Communication setting Module type FX ENET ADP J Host IP Address 192 168 0110 Port No 1024 Cancel Set the TCP Port Number Port No Set the IP address connection connection destination as assigned destination as assigned to the to the FX2Nc ENET ADP by the FX2Nc ENET ADP by the sequence sequence program program When using the Host For details on the TCP port Number Name set the name assigned by setting for the FX2Nc ENET ADP the hosts file refer to Chapter 7 For details on the IP address setting for the FX2Nc ENET ADP refer to Chapter 7 Next P Communication Setting Wizard Network Please select the Network Station type Host station bd CPU type FX2N C Set FX1S FX1N FX2N or Next J FX2nc at CPU type The Communication wizard has finished collecting information Please Finish to build the logical station number Comment via FX2NC ENET ADP Enter a comment Finish 4 L Communication Setup Utility Menu Help Target setting List view Connection test Logical station number 1 via FX2NC ENET A amp DP VEE
23. e in a shielded metal control panel 1 Associated Manuals 3 2 Installation to a Panel Face Direct installation to the panel face Directly attach to the panel face using 2 sets of a screw M4 a spring washer and a flat washer in the mounting holes Tightening torque 0 7 to 1 0 N m For the pitch and positions of mounting screw ENET holes refer to the external dimensions ADP FX Series Full duplex Guideline for the safety of the user and protection of the FX2NC ENET ADP This manual provides usage information for the FX2NC ENET ADP Ethernet adapter The manual has been written to be used by trained and competent personnel Notes on the symbols used in this manual At various times throughout out this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment Whenever any of the following symbols are encountered its associated note must be read and understood Each To Ethernet RJ45 connector Connector To ground opis g However internally short circuited 0 kg 022 5 2 Outside dimensions and name of each part 16 1 0 64 to screw holes Wanoainame WanvalWe Descriptor FX1S HARDWARE MANUAL JY992D83901 FX1N HARDWARE MANUAL JY992D89301 Describes the hardware of the FX2N HARDWARE MANUAL JY992D66301 FX Series PLC such as specifications wiring and FX2NC HARDWARE MANUAL DSS DS M
24. ersonal computer connected to Ethernet and check whether the FX2Nc ENET ADP sends a response Refer to the PING command described below Check if PLC and PC Clear the check box FX parameter Memory capacity Jevice PLC name 170 assignment PLC system 1 PLC system 2 If the box is not checked the parameters will be cleared Operate When the program is transfered to the communication board parameters and Executing the PING command a pein D8120 values in the PLC must be cleard upon program transfer Open the MS DOS prompt command prompt in the Windows2000 XP In the example parameter settings in Section 7 3 the IP address is set to 192 168 0 110 PING 192 168 0 110 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual a MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN HIMEJI WORKS 840 CHIYODA CHO HIMEJI JAPAN
25. n comply with the following standards Installation to FX1S FX1N FX2N _ Compliance to EMC standards of the entire mechanical module should be checked by Turn OFF the PLC before beginning any the user manufacturer work Standards with which this product complies 1 Remove the panel cover from the top Type Programmable Controller Open Type Equipment face of the main unit Models Products manufactured from April 1st 2004 to April 30th 2006 are compliant with 2 Take off the resin cover from the left side of the main unit EN61000 6 4 and EN61131 2 1994 A11 1996 A12 2000 and EN61000 6 2 after May 1st 2006 are compliant with EN61131 2 2003 3 Install the following board to the port on the main unit Electromagnetic Compatibility Standards EMC Correspondin EN61000 6 4 2001 Electromagnetic compatibility FX1N CNV BD FX1S FX1N Generic standards Emission standard for Industrial environment 4 Affix the above board using the supplied M3 screws EN61131 2 1994 A11 1996 A12 2000 Tightening torque 0 3 to 0 6 Nm Programmable controllers Equipment requirements and tests 5 Connect the built in cable of the FX2NC ENET ADP to the port on the left side of the board 3 1 How to Install to FX Series PLC e Applicable version of GX Developer MX Component Software Applicable Version With FX Configurator EN GX Developer Ver 8 12N or later Ver 8 25B or later Installation to FX1S FX1N FX2N Changes f
26. or the Better a MITSUBISHI PROGRAMMABLE CONTROLLERS MELSEG F MX Component Ver 3 05F or later Ver 3 08J or later 5 Product Specification 5 1 Specifications The general specifications of FX2NC ENET ADP are same as those of the FX Series PLC except the following items 500V AC for 1 Conforms to JEM Withstand voltage 1021 between all terminals together 5 MQ or more by and grounding 500V DC megger terminal Power suppi SUppIy voltage 5V DC 135 mA supplied from PLC specifications current CSMA CD IEEE802 3 FX2NC ENET ADP Ethernet adapter USER S MANUAL Manual Number JY997D12301 pasm ooo This manual contains text diagrams and explanations which guide the reader in the correct installation and operation of the FX2NC ENET ADP Ethernet adapter It should be read and understood before attempting to use the unit If in doubt at any stage of the installation of FX2NC ENET ADP consult a professional electrical technician who is qualified and trained to the local and national standards which apply to the installation site If in doubt about the operation or use of the FX2NC ENET ADP please consult the nearest Mitsubishi Electric distributor This manual is subject to change without notice Microsoft and Windows are either registered trademarks or trademarks of Microsoft Corporation in the United States and or other countries The company name and the product name described in this manual are th
27. ounting on DIN rail Affix the FX2NC ENET ADP to the DIN rail DIN46277 35 mm 1 37 wide installation Unit mm inches JY992D76401 of the symbols used will now be listed with a brief description of its meaning JY992D87201 T D UL 2 94 2 0 17 Hardware Warnings e201 2 lt f i 2 f Describes the instructions gt Sel pale Me Hentieg danger WILE pause piyslea and FX PROGRAMMING MANUAL II JY992D88101 available in the FX1S FX1N re N GLa a i A E E oe property damage FX2N FX2NC Series PLC A Z EX Confiqurator EN Describes operation details of ADP PLC 1 7 A S 2 Indicates that the identified danger could POSSIBLY cause ABE OKTGh MANUAL JY997D20501 FX Configurator EN Dismounting from DIN rail E i fi ti ft S physical and property damage Configuration Software Slightly pull down the DIN taii mounting dip 3 G FX1N CNV BD Special Adapter using a tool such as a slotted screwdriver Pull 9 2 tion Board JYASADBS TDA d the clip furth d the rail will be locked E 3 Indicates a point of further interest or further explanation Panne cron Boan Describes matters related to the SWD MG SIP AAMO ANA MA TAN N Te D a FX2N CNV BD Special Adapter installation of the boards with the clip left open g 11 JY992D63601 lt z Connection Board P 2 ee For GX Developer and MX Component refer to the operation manual respectively
28. program are performed in the same way as with serial communication 10 Troubleshooting Turn ON power of PLC No Check the cable connection between FX2NC ENET ADP and PLC Is POWER LED ON Yes No Check if FX2Nc ENET ADP and HUB are connected correctly Check if power of HUB is ON Yes Two seconds after FX2Nc ENET ADP is turned ON Execute PING command for IP address set to PLC 1 Check again IP address set to PLC 2 Confirm that network address in PLC matches network address in PC 3 Confirm connection of Ethernet between PC and PLC No Any response Yes Check Ethernet Confirm that TCP port number set in GX parameters For details refer to 7 Parameter Settings for FX2Nc ENET ADP Developer or MX Component matches TCP port number set in PLC Parameters are read correctly from PLC No Are FX2Nc ENET ADP and PLC connected correctly Yes Turn ON power again Is any numeric value other than 0 stored in D81 s communication port set for computer link or no protocol communication Value other than 0 stored in D8120 No Yes Clear communication parameter check box and download program Set 0 to D8120 Turn ON power again Reference The PING command confirms confirmation whether the communication between Ethernet devices using the IP address of TCP IP is possible Execute the PING command from the p
29. r magnetic fields For more details please contact the local Mitsubishi Electric sales site Notes for compliance to the EMC regulation It is necessary to install the FX2NC ENET ADP module in a shielded metal control panel 1 Associated Manuals Manualname Manua No J Desorption Describes the hardware of the pn naRomaRE MANUAL vosznesanr FX Series PLC such as specifications wiring and FX2NC HARDWARE MANUAL JY992D76401 installation DUL 1Yo92D87201 EN61131 2 2003 Programmable controllers Equipment requirements and tests Describes the instructions FX PROGRAMMING MANUAL II JY992D88101 available in the FX1S FX1N FX2N FX2NC Series PLC FX Configurator EN OPERATION MANUAL Describes operation details of JY997D20501 FX Configurator EN Configuration Software FX1N CNV BD Special Adapter JY992D84701 Connection Board Describes matters related to the J _ i installation of the boards FX2N CNV BD Special Adapter JY992D63601 Connection Board For GX Developer and MX Component refer to the operation manual respectively 2 Outline of Product The FX2NC ENET ADP is an Ethernet adapter of 10BASE T specifications for the FX1S FX1N FX2N and FX2NC Series The FX2NC ENET ADP enables the upload download monitor and test of a program from the personal computer GX Developer or MX Component via Ethernet 3 Installation Caution e Use only in the environments specified under the general specifications
30. r performing wiring work Otherwise fire failure or malfunction may occur Another equipment Another Another equipment equipment Dedicated grounding Shared grounding good Common grounding best not possible PLC 6 2 Wiring example Grounding 100 or less 99299 E9Reeee DO000 DL001 Header fo Set H454E4554 ENET DO002 D0003 IP address 192 168 0 100 Set the IP address for connecting to Ethernet 2 He0dd Huds Subnetmask 2552552550 Oot ME SUP Net mask for connecting to Ethernet 3 Gateway Set the gateway address for Bente BEOU address 4 dee tee 0 connecting to Ethernet 2 TCP port Set the TCP ports within the DEROS mee range from 1024 to 65535 O Indicates any number in the range from 1 to 7 e If ENET is not found or the parameters such as IP address Gateway address Subnet mask are incorrect the default parameters are valid e If FX2NC ENET ADAP cannot read out the specified data register stored in the PLC the default parameters are used In such a case the SD or RD LED is lit Refer to 7 4 Note 1 This is the header identifier required when FX2NC ENET ADP identifies the Ethernet parameters Make sure to set H454E4554 ENET to D128 D129 or DL1000 DL1001 2 The first 8 bits used for the IP address and Gateway
31. re the users personal safety and protect the integrity of equipment Whenever any of the following symbols are encountered its associated note must be read and understood Each of the symbols used will now be listed with a brief description of its meaning I 9 s Q o s 1 S s 2 Ss Q 7 1 Indicates that the identified danger WILL cause physical and property damage 2 Indicates that the identified danger could POSSIBLY cause physical and property damage 3 Indicates a point of further interest or further explanation DISPOSAL PRECAUTIONS e When disposing of this product treat it as industrial waste INSTALLATION PRECAUTIONS e Use the module in an environment that meets the general specifications contained in this manual Using this module in an environment outside the range of the general specifications could result in electric shock fire erroneous operation and damage to or deterioration of the product e Do not disassemble or modify the module Doing so may cause failure malfunction injury or fire gt D OFF TRANSPORTATION AND MAINTENANCE PRECAUTIONS e During transportation avoid any impact as the module is a precision instrument Doing so could cause trouble in the module e It is necessary to check the operation of module after transportation in case of any impact damage Note Concerning the CE Marking The CE marking does not guarantee that an entire mechanical module produced in accordance wi
32. ss for address 4 connecting to Ethernet 2 TCP port 1024 Set the TCP ports within the number range from 1024 to 65535 O Indicates any number in the range from 1 to 7 DL1006 DL1007 192 168 0 1 D1008 e If ENET is not found or the parameters such as IP address Gateway address Subnet mask are incorrect the default parameters are valid e If FX2NC ENET ADAP cannot read out the specified data register stored in the PLC the default parameters are used In such a case the SD or RD LED is lit Refer to 7 4 Note 1 This is the header identifier required when FX2NC ENET ADP identifies the Ethernet parameters Make sure to set H454E4554 ENET to D128 D129 or DLI000 DH001 2 The first 8 bits used for the IP address and Gateway address must be in the range from 1 to 223 If any number outside this range is used the RD LED will be lit when the FX2NC ENET ADP is turned on and Ethernet communication will not be performed Set numbers from 1 to 223 3 In the following cases and as explained in 2 concerning the Subnet mask data the RD LED will be lit when the FX2NC ENET ADP is turned on an error will occur and Ethernet communication will not be performed The following conditions are expressed in binary form 1 If 1 is set for all bits 2 If O is set for all bits 3 If 1 is set immediately after 0 is set Example 111 11000100 4 The settings of the IP address Subnet mask and Gateway address depend on
33. th the contents of the notification comply with the following standards Compliance to EMC standards of the entire mechanical module should be checked by the user manufacturer Standards with which this product complies Type Programmable Controller Open Type Equipment Models Products manufactured from April 1st 2004 to April 30th 2006 are compliant with EN61000 6 4 and EN61131 2 1994 A11 1996 A12 2000 and EN61000 6 2 after May 1st 2006 are compliant with EN61131 2 2003 Electromagnetic Compatibility Standards EMC EN61000 6 4 2001 Electromagnetic compatibility Generic standards Emission standard for Industrial environment EN61131 2 1994 A11 1996 A12 2000 Programmable controllers Equipment requirements and tests EN61000 6 2 2001 Electromagnetic compatibility Generic standards Immunity for industrial environments Compliance with all relevant aspects of the standard Radiated Emissions and Mains Terminal Voltage Emissions Compliance with all relevant aspects of the standard RF Immunity Fast transients ESD and Damped oscillatory wave Compliance with all relevant aspects of the standard RF immunity Fast transients ESD Conducted Surges Power magnetic fields Voltage dips and Voltage interruptions Compliance with all relevant aspects of the standard Radiated Emissions Mains Terminal Voltage Emissions RF immunity Fast Transients ESD Surge Voltage drops and interruptions Conducted and Powe
34. the following methods through serial communication e Setting using the PLC program e Setting using file registers For each setting example refer to Section 7 3 When file registers are used to set the Ethernet parameters Select Parameter PLC parameter Memory capacity in GX Developer and set the file register capacity to 1 block or more Then right click Device memory add the device memory data and set the parameters as shown below e Settings of D128 to D135 or D1000 to D1007 32 bit HEX mode 5 3 Connector pin arrangement The RJ45 connector in the FX2NC ENET ADP has the following pin arrangement Pin Signa name Direction Description 7 3 Parameter setting examples for FX2NC ENET ADP Two examples of setting the Ethernet parameters for the FX2NC ENET ADP are shown below Example of parameter settings Data register Setting item Parameter Set data FX1N FX2N FX2NC D128 D129 D1000 D1001 ENET H454E4554 D130 D131 D1002 D1003 IP address 192 168 0 110 HCOA8006E Device Label D1000 X Display 32 bit integer HEX D0 D7999 Device name 0 4 6 iso _ asarassal C eso errr _consooni bm a e E E aaa Header ENET Subnet mask 255 255 255 0 Gateway address 192 168 0 1 D130 D131 BE i ee BE ae es a oe ee e ee el oma IP address 192 168 0 110 e Settings of D136 or D1008 16 bit DEC mode D132 D133 D132 D133 D1004 D1005 Subnet mask
35. the network environment For the contents of these parameters see the network administrator 5 The FX2NC ENET ADP searches for the header in the order D1000 D7000 The values described in lowest data resister numbers are set as the Ethernet parameters 7 2 Parameter setting methods Set the Ethernet parameters using either of the following methods through serial communication e Setting using the PLC program e Setting using file registers For each setting example refer to Section 7 3 7 3 Parameter setting examples for FX2NC ENET ADP Two examples of setting the Ethernet parameters for the FX2NC ENET ADP are shown below Example of parameter settings Data register Setting item Parameter Set data FX1N FX2N FX2NC D128 D129 D1000 D1001 ENET H454E4554 D130 D131 D1002 D1003 IP address 192 168 0 110 HCOA8006E D132 D133 D1004 D1005 Subnet mask 255 255 255 0 HFFFFFFOO D134 D135 D1006 D1007 Gateway 192 168 0 1 HCOA80001 address K1024 D136 D1008 TCP port number 1024 When the PLC program is used to set the Ethernet parameters The Ethernet parameters for the FX2NC ENET ADP can be set using the program shown below Note In the FX2NC ENET ADP the Ethernet parameters become valid only when the power is turned ON and the setting data is stored in specified data registers In either of the following cases turn off the power of the PLC once and then turn it on again e When a parameter is set for the
36. via Ethernet from GX Developer Note e GX Developer must be Version 8 25B or later e FX Configurator EN must be installed on the personal computer For details on the installation method of FX Configurator EN refer to the FX Configurator EN Operation Manual 8 1 Setting method Select Online Transfer setup Transfer Setup PC side F fi F Serial NETA0 H NET II CC Link Ethernet ssc board board board board net COM CoM 1 Transmission speed 9 6Kbps PLC side F PLC MNET 10 H MNET II CC Link Ethernet C24 G4 Bus module module module module module module Click Ethernet board P Transfer Setup PC side I F ho E Serial NET 1O H NET II CC Link Ethernet board board board board board board net PLC side I F PLC MNET 10 H MNET II CC Link module module module module Double click Ethernet module vy PLC side I F detailed setting of Ethernet module G4 Bus module Select FX2Nc ENET ADP IP address 192168 0110 IP input format DEC C Host Name Port No f 024 Input format decimals v Set the TCP Port Number Port Set the IP address connection No connection destination as destination as assigned to the assigned to the FX2Nc ENET ADP FX2Nc ENET ADP by the sequence by the sequence program program When using the Host For details on the TCP port Number Name set the name assigned by setting for the FX2Nc ENET ADP the hosts file