Home
Honeywell MV100 User's Manual
Contents
1. Contact with hot liquid can lead to severe injury or cause death For a pressurized valve only open with Valve Cartridge Replacement Tool B u Contact with hot valve body can cause severe burning Service cartridge only when valve body is cool u Can injure burn or blind Wear safety glasses or goggles Under Pressure Replacing the V100 Cartridge with the system under pressure requires the Valve Cartridge Replacement Tool see Accessories in the Specifications section See Pressurized Valve Cartridge Replacement section for details Not Under Pressure Replacing the cartridge without the Valve Cartridge Replacement Tool requires one of the following e Isolation of valve from system pressure e System shutdown drain to valve level Once the valve is not pressurized 1 Using a 3 4 in 19 mm hex 6 or 12 point socket wrench remove and discard the cartridge 2 Clean the inside of valve and cartridge sealing surfaces Install a new cartridge 62 3048 2 10 NOTE Torque cartridge to 25 ft Ib SINGLE PIPE STEAM APPLICATIONS Many older buildings original heating systems were single pipe steam The advantage of single pipe steam systems is lower initial cost resulting from the use of less piping and elimination of radiator steam traps Nu ul Loss of system control and boiler damage can result For a one pipe steam system radiator install valve only at the vent location
2. M12933B Fig 2 V2000 dimensions NOTE Refer to Table 3 for detailed valve dimensions for each valve size 62 3048 2 4 MV100 ELECTRIC CONTROLLERS 7100 200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 3 Valve Dimensions Valve in in mm in in mm in in mm v20400 W2 33499 RITA pelemmsumeme ere ld V2040A 54 115 1 8 2 132 1 24546 74 nson B Max dimension is with T100A control installed except for the V2042H for which it is without the steam air vent installed 2 1 2 5 3 16 132 1 3 16 31 37 8 9 74 34 R 3 74 3 Connections Inlets Available Internally threaded Sweat 1 2 in and 3 4 in only Outlets Available Union nut with threaded tailpiece Sweat 1 2 in and 3 4 in only Union nut with sweat tailpiece 1 2 in and 3 4 in only Capacity Cv gpm at 1 psi drop across fully open valve 1 2 in 2 0 3 4 in 2 2 1 in 2 3 Btuh Btu hr at 7 psi drop across fully open valve 1 2 in 59 100 3 4 in 63 800 1 in 70 500 Accessories 203225 Replacement Bulb Guard for T100F 272844 Locking Cap and Limit Pins for T100M 272873 MT100C Cartridge Tool Driver Upgrade Kit A104F Limit Pins for T100A F VS1200SL01 Replacement Valve Cartridge G111B Bulb Guard to protect T100C sensor when wall mounted VA8200A001 Valve Cartridge Replacement Tool for system under pressure V2000 Q1
3. IMPORTANT Ensure vacuum breakers are installed on the steam system risers If vacuum breakers that open to the atmosphere at zero psig are not installed the system can develop a negative pressure and pull steam back into the radiators on resumption of steam Refer to Fig 12 for installing the one pipe steam radiator adapter assembly Single Pipe Steam Systems T100 V2043H with vent operation to provide temperature control for a formerly uncontrolled single pipe steam system follows 1 The boiler is off zero steam pressure radiators are filled with air the vent is open 2 The T100 calls for heat opening the valve 3 At the command of an external controller such as a representative zone thermostat or a timer controlled by outside temperature the boiler cycles on and begins delivering steam to the system 4 Steam enters the radiator forcing air through the open V2042H and out through the vent 5 Once the air is exhausted the steam heats the thermostatic element of the vent causing it to close 6 The steam cools forming condensation Condensation flows out of the radiator making room for more steam to enter 7 The T100 is eventually satisfied temperature equals the setpoint and it closes the V2042H 8 The air in the system introduced by the vacuum breakers begins to fill the radiator The air in the radiator prevents steam from coming in and the radiator cools 9 The boiler cycles off by command of com
4. A and remove cartridge from chamber B See Fig 23 5 Clean or replace cartridge Fig 26 Disconnecting valve cartridge and draining chamber M16275 M16274 M16276 Fig 24 Loosening valve cartridge Fig 27 Removing valve cartridge To reinstall cartridge into the valve use the same process and figures Perform steps in reverse order All figure arrows are backwards except Fig 20 arrow A Proceed as follows 1 Replace cartridge into chamber B and screw end cap onto VA8200A A See Fig 23 2 Close drain cock C open ball valve B and push handle in A See Fig 22 3 Turn tool handle cw to screw in cartridge D open drain cock to drain chamber of remaining water and steam C and loosen VA8200A Cartridge Changer from valve body B A See Fig 21 4 Tighten valve cartridge using a 19mm socket wrench A B and replace controller See Fig 20 13 62 3048 2 62 3048 2 14 19 62 3048 2 Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitee 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 479 customer honeywell com U S Registered Trademark rinted in U S A on recycle 2006 Honeywell International Inc 69 paper containing at least 10 62 3048 2 Rev 02 06 post consumer paper fibers Honeywell
5. inspect vent Replace if necessary Overheating Sensor in the wrong location Change sensor location or change control type Control not properly installed Check for bosses and grooves reset actuator on valve and tighten knurled ring to valve body Capillary tube broken kinked or Replace control bent sharply Dirt or scale under the seat Remove the control from the valve body allowing valve to open prevents tight shutoff fully and flush away scale and debris Reinstall control Turn fully clockwise If the valve does not close fully remove the control and cartridge see Cartridge Replacement section Always use a strainer insert in steam applications Flow through the valve is in the Check the arrow on the valve body It should correspond to the flow wrong direction damaging the direction Change the valve direction or flow direction Remove valve seat valve cartridge and inspect seat disk for damage Defective steam traps Repair or replace traps Excessive differential pressure Install differential pressure regulator D146A to maintain less than forces the valve open hot water 15 psi 103 kPa differential between the supply and return pipes systems Single pipe Insufficient air in Check boiler cycling and system vacuum breakers Repair or system replace breakers as necessary Chattering or knocking Flow through the valve in the Check the arrow on the valve body It should correspond to the flow wrong directio
6. 00 Thermostatic Controllers Models See Table 1 Dimensions See Fig 1 Power Self powered no electrical connections Components Sensor setpoint dial and valve actuator ORDERING INFORMATION Materials Body Industrial grade plastic with low thermal conductivity Fastening Ring Plated brass Internal Parts Brass thermostat capsule other metals Thermal Element T100A M Wax T200 T100B C F Liquid Ethyl Acetate non toxic flammable Temperature Ratings Range 43 F to 79 F 6 C to 26 C Maximum 1254F 527 V2000 Valves Models See Table 2 Dimensions See Fig 2 and 3 Materials Body Bronze V2040A 1 2 in Brass Union Brass Seal Double EPDM seal Cartridge Brass and stainless steel with EPDM seat disk NOTE Apply 25 ft Ib 30 torque when installing the valve cartridge Maximum Temperature Rating 266 F 130 C Maximum Pressure Ratings System Water 145 psi 10 bar Steam 15 psi 103 kPa Differential With MV100 Controller 36 psi 248 kPa With T100 or T200 Controller 14 5 psi 1 bar For Low Noise 2 9 psi 20 kPa Sizes V2024H 1 8 in V200LD 1 2 in 3 4 in V2040D E A 1 2 in 3 4 in and 1 in When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor refer to the TRADELINE Catalog or price sheets for complete ordering number If you have additional questions need further informati
7. 10D Inlet Strainer Inserts for NPT V100 models available for 1 2 in and 3 4 in valves SA123A Steam Air Vent for V2042HSL10 One pipe Steam Valve M17016 Fig 3 V2042H Body V2043H Body with Airstream Vent Dimensions NOTE Refer to Table 3 for detailed valve dimensions for each valve size INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions u Excessive force can distort and damage valve Do not overtighten the union nut u Driving an unmounted MV100 can damage the actuator beyond repair Mount the MV100 before applying power to the actuator Soldering the valve with the cartridge or controller attached can damage the device Prior to attaching valve to piping remove controller and cartridge from potential exposure to heat IMPORTANT When installing the valve body ensure that the arrow cast into the body points in the direction of the flow 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Pre setting and Balancing Fl
8. A See Fig 17 MV100 ELECTRIC CONTROLLERS 7100 200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES CORRECT M16272A INCORRECT Fig 21 Horizontal body V2000 application Install controllers with external sensors in any position The sensor can easily be mounted in a position to measure and control the room air temperature NOTE When temperature of medium exceeds 190 F 88 C mount the MV 100 horizontally WIRING MV100 ONLY Wire the MV100 according to Fig 18 u Can short equipment circuitry Disconnect all power supplies before installation Connecting improper voltage can damage the device beyond repair Connect only 24 Vac or 24 Vdc to the MV100 TO CIRCULATOR PUMP MULTIZONE PANEL OR BURNER RELAY YELLOW T810 T822 L1 HOT L2 N POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED RESISTANCE HEATER NORMALLY OPEN END SWITCH CLOSES WHEN MV100 IS POWERED ZN SUGGESTED HEAT ANTICIPATOR SETTING IS 0 35A M12947A Fig 22 MV100 internal schematic and wiring connections OPERATION The T100 and MV100 Controllers contain temperature sensitive capsules that expand or contract in reaction to temperature changes When the capsule expands pressure from the expand ing material closes the valve preventing flow through the radiation unit When the capsule contracts the valve opens and
9. CONTROLLERS 7100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 1 T100 T200 Models Model Control Range Mounting Capillary Descipion _ T100A 43 F to 79 F Direct None Components are in one unit 6 C to 26 C T100B 48 to 79 F Remote One 6 1 2 ft 2 Sensor and setpoint dial combined and remote from valve 9 C to 26 C or 16 ft 5 m actuator T100C HEEL E Two 4 1 2 ft Components mount remotely from each other 1 4 m 43 F to 79 F Direct with One 6 1 2 ft 2 m Sensor is remote from combination setpoint dial and valve 6 C to 26 C remote actuator sensor T100M Direct Components are in one tamper resistant unit Mount the unit horizontally on the valve body for accurate temperature regulation Table 2 V2000 Models Body Pattern Inlet Outlet Application V2040D Straight NPT Union Nut with Use where manual valves were not originally installed V2040E Ange hreaded NPT Threaded Typically used with remote temperature sensing controllers or Sweat V2040A Horizontal Angle Typically used with direct mount controllers T100A M T200A V200LD Straight Sweat Sweat Use with copper tubing installations o One Pipe in NK for Use in single pipe steam applications V2043H SA123A Vent V2040D Straight Body V2040E Angle Body M12930B V2040A Horizontal Angle Body B MAX M12932B 22 NS
10. HERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES TROUBLESHOOTING Refer to Table 6 for troubleshooting details Table 7 T100 V2000 Troubleshooting Symptom Possible Cause Not all sections of the radiator are heating Many radiators are oversized and System is operating properly not all sections heat to maintain the desired temperature Underheating Sensor in the wrong location Change the sensor location or change the control type See Installation Instructions T100A M Controller mounted in a Mount the T100A M horizontally or switch controller to a T100F vertical position above the hot pipe Excess capillary tubing coiled Coil excess capillary tubing below or away from the heat source above or too close to the heat source Flow through the valve is in the Check the arrow on the valve body It should be in the direction of wrong direction the flow Change the valve direction or flow direction Inadequate system temperature Check boiler operating and limiting controls circulating pump and pressure isolating valves Defective steam traps Repair or replace the traps Airlock in the hot water system Fully open the valve to allow air to pass Install vents Scale or debris blocks flow Flush the system Do not use oil based additives Clean strainer insert in steam applications Heating cabinet dampers are Open or remove the dampers closed Single pipe Blocked vent Remove and
11. Honeywell 100 Electric Controllers T100 T200 Thermostatic Controllers and V2000 Radiator Valves THERMOSTATIC CONTROLS P VALVE BODIES V2043H V2040A V2040D V2040E V200LD PRODUCT DATA APPLICATION The MV100 T100 T200 Controllers when paired with V2000 Radiator Valves provide automatic temperature control by modulating the flow of steam or hot water through free standing radiators convectors and other heating units They provide comfort and energy savings at affordable prices FEATURES e Continually monitors and adjusts room temperature for consistent comfort and relief from underheating and overheating e T100 T200 Controllers include sensor setpoint dial and valve actuator components can be integral or connected by capillary tubing e T100 T200 Controllers require no electrical connections T100A F M models have range limiting features to limit adjustment or lock at a fixed setting can require limit pin accessory e EPDM valve seat disk assures tight shutoff on steam and hot water systems Nickel plated bronze cast valve body Cartridge containing all working parts inserts into valve body for ease of service Cartridges are replaceable while valves remain in service and under pressurE WITH accessory service tool MT100C Valves remain normally open with no control mounted e Valves can be used with T100 T200 Thermostatic or MV100 Electric Controllers Contents A
12. POICATON 1 Features 1 2 Ordering Information 2 InslallallON e 5 Wiring 100 only 9 Soie NNMERO NOR 9 Settings and Adjustments 9 Single Pipe Steam Applications 10 Troubleshooting 2 464004 00 12 Pressurized Valve Cartridge Replacement 13 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES SPECIFICATIONS 100 Electric Controller Dimensions See Fig 1 Materials Body Industrial grade plastics with low thermal conductivity Fastening Ring Plated brass Internal Parts Brass thermostat capsule other metals Thermal element Wax filled brass capsule Electrical Ratings Control Type Spst switch Controller Voltage 24 Vac 60 Hz or 24 Vdc Power Consumption 0 125A 3W End Switch Low voltage 24 Vac 5A two position spst normally open switch closes when controller powered Configuration with Controller Mounted Normally closed valve remains closed without power NOTE Normally open model available in Canada Opening Time at 78 F Maximum 5 minutes from cold to fully open Ambient Temperature Rating Maximum 122 F 50 C T100 T2
13. S 7100 200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Typical Applications Table 5 Figure References to Typical Applications Figure No Controller Valve T100A T100M T200 MV100 9 Ti00A TIOOM T200 100 V2040A A NI r 12934 3236 Fig 11 steam system M12935 4635 7 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES V2042H M11752A 62 3048 2 2 12939 Fig 20 Location and Mounting Because these controls are thermostats that have sensors that measure air temperature in the immediate vicinity it is critical to select an appropriate installation location These devices are adversely affected by radiant heat solar heat or airflow obstructions such as curtains or enclosures Two essential considerations for choosing the correct controller valve body combination for a particular installation are Adequate dimensional clearances Proper sensor positioning IMPORTANT Install built in sensor type controllers in a horizontal position to prevent air warmed by the hot valve body from influencing the sensor NOTE The most common misapplication of these valves and controllers is the use of a horizontal body valve V2040E with a direct mount controller T100A M or T200
14. flow resumes through the radiation unit 1100 The T100 temperature sensitive capsule expands when the temperature rises above the setpoint MV100 When signalled by the thermostat an electric element in the MV100 heats the capsule causing it to expand NOTE For normally open MV100 models the capsule cools when signalled by the thermostat SETTINGS AND ADJUSTMENTS When installation is complete rotate the setpoint dial to the desired setting NOTE The setpoint varies with the location of the sensor floor level sensor controls at a setpoint different from the wall level sensor Normally correction of an overheating or underheating condition requires only small changes See Table 5 for dial markings and corresponding temperature settings After changing the setting allow the valve at least 30 minutes to stabilize 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES Table 6 T100 and T200 Settings and Corresponding Temperatures in F C Setting not marked on dial Setpoint Locking or Limiting T100A F M only A single temperature or range limiting lock is available for the T100A F M See Accessories in the Specifications section Refer to the T100A F M Installation Instructions for procedural details Cartridge Replacement With the appropriate tools the V2000 cartridge can be replaced while under pressure Ah WARNING Severe Scalding Hazard
15. n direction Change the valve direction or flow direction Vacuum in the system Steam check traps and vents Hot water check expansion tank operation and location Excessive differential pressure Install differential pressure regulator D146A to maintain less than 15 psi 103 kPa differential between the supply and return pipes Bent piping Ensure adequate space for piping 62 3048 2 12 MV100 ELECTRIC CONTROLLERS 7100 200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES PRESSURIZED VALVE CARTRIDGE VA8200A001 Valve Cartridge Changing Tool enables the user to remove and clean or replace the valve cartridge while the valve remains pressurized Boiler shutdown is not required Ah WARNING Severe Scalding Hazard Contact with hot liquid can lead to severe injury or cause death Exercise extreme caution when working with hot liquid mu u Can injure burn or blind Wear eye protection to prevent injury To remove the cartridge perform the following 1 Remove controller and loosen valve cartridge slightly using a 19mm socket wrench A B See Fig 20 2 Tighten VA8200A Cartridge Changer to valve body close drain cock C and turn tool handle ccw to unscrew cartridge D See Fig 21 3 Pull handle out to clear VA8200A ball valve A close ball valve B and open drain cock to remove excess water and steam from chamber C See Fig 22 4 Unscrew end cap
16. on or would like to comment on our products or services please write or phone 1 Your local Honeywell Automation and Control Products Sales Office check white pages of your phone directory 2 Honeywell Customer Care 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limited Honeywell Limit e 35 Dynamic Drive Scarborough Ontario M1V 4Z9 International Sales and Service Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Netherlands Spain Taiwan United Kingdom U S A 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES TOP uuewpyn uuewyneag QM 29UOH 2 1 8 54 5 1 25 gt 3 5 16 84 12925 12929 100 CAPILLARY TUBE LENGTH 6 1 2 FT 2m OR 16 FT 7 nu 2 1 8 im 1 13 16 2 5 32 46 5 5 lt 2 31 32 75 12926 200 gt 13 16 20 76 MAX M12945 T100C CAPILLARY TUBE LENGTH 2 1 8 54 4 1 2 1 4 m 1 13 16 2 5 32 46 55 75 pon 2 31 32 CAPILLARY TUBE LENGTH 4 1 2 FT 1 4 m M12927 T100F CAPILLARY TUBE LENGTH 6 1 2 FT 2 m A MV100 2 51 Fig 1 MV100 T100 and T200 dimensions in in mm 62 3048 2 MV100 ELECTRIC
17. ow Through Valve Body Close valve with straight blade screwdriver by turning black pre setting ring clockwise M22687 Fig 4 Closing valve When closed the position of the screwdriver slot equals pre setting zero Mark the position of the slot with a felt tip pen M22688 Fig 5 Mark zero position of screwdriver slot Take required value from Table 4 Turn presetting ring counterclockwise with a straight blade screwdriver to this position Chose value has to be congruent with marking M22689 Fig 6 Set pre setting ring to correct value 62 3048 2 One complete revolution of the black ring equals a pre setting of 10 Fig 7 M22690 Fig 7 One complete revolution equals a pre setting of 10 Table 4 CV Values Pre setting 7 13 8 in 10 29 0 58 10 87 11 16 11 45 1 68 1 80 2 00 3 4 in 2 26 1 in NOTE Pressure drop psi flow gpm cvy Product Selection 1 Select the installation diagram from Fig 4 through 16 that most accurately represents your equipment and pip ing configuration 2 Use Table 4 to select the combination of controller and valve that is most suitable based on a Equipment and pipe configuration see Tables 1 and b Flow capacity requirement see Specifications section IMPORTANT The T100 and T200 are modulating not manual shut down valve actuators Do not use them for hand shutoff valves MV100 ELECTRIC CONTROLLER
18. ponents external to the T100 V2042H and the steam pressure returns to zero MV100 ELECTRIC CONTROLLERS T100 T200 THERMOSTATIC CONTROLLERS AND V2000 RADIATOR VALVES NOTE While the T100 is satisfied the V2042H is closed and the radiator remains airlocked Thus no steam can enter the radiator The airlocked condition remains until the T100 calls for heat at which point the system operates as described in steps 1 through 6 An improperly cycled boiler causes either excessive heating or lack of heat depending on the system time constant Bringing the Steam Pressure to Zero psig To assure the proper operation of any single pipe steam system ensure that the steam pressure is brought to zero at some time during the off cycle One suggested procedure follows 1 Determine if steam is required using one of two methods a Athermostat in a representative zone controls the valve or cycles the boiler b Atiming device cycles the boiler for varying lengths of time in response to outdoor temperature IMPORTANT When cycling the boiler from a space thermostat in a zone do not apply a radiator valve to that radiator 2 Turn off the steam and allow system pressure to drop to zero Do this using one of two methods a Turn the boiler off and allow the total steam pressure in the system to drop to zero IMPORTANT Before applying controls to turn a boiler on and off check the manufacturer recommendations b In installation
19. s where turning the boiler off at the end of each cycle is undesirable install a control valve such as a Honeywell V5011 Valve on the boiler dis charge line 11 Install the valve on the boiler side of the condensation takeoff to ensure that the condensation can return to the boiler NOTE 3 Verify that the steam pressure has returned to zero Verification Verification is necessary to prove that the pressure has returned to zero Simply turning off the boiler or shutting off the steam supply does not ensure zero steam pressure The simplest way to check for zero pressure follows 1 Install a strap on Aquastat Controller such as the Honeywell L6006C Aquastat Controller on the condensation return line see Fig 19 2 Setthe Aquastat Controller at about 150 F 66 C With the return line at or below this temperature the water is all condensation and the pressure is functionally zero 3 Wire the Aquastat Controller into the interrupting circuit to ensure that steam flow cannot resume until the condensation line is below the setpoint The 150 F 66 C setpoint serves as a nominal starting point and can require adjustment for individual steam systems MASTER ZONE THERMOSTAT i POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M7536A Fig 23 Holding circuit for use with L6006 when verifying zero psig steam pressure 62 3048 2 MV100 ELECTRIC CONTROLLERS 7100 T200 T
Download Pdf Manuals
Related Search
Related Contents
Manual de Instrucciones 取扱説明書 règlement d`utilisation des véhicules de services de la Communauté bathurstsustain...development.com ATD-10538 3/8” Electric Drill Avaya v.3.0.6 Release Notes Rand McNally & Company 2000 User's Manual Guía Rápida FD75 Fle x Dra per con Ada p tador CA25 StickFont™ v2.50 User Manual Copyright © All rights reserved.
Failed to retrieve file