Home
Harman Stove Company P43 User's Manual
Contents
1. 4 Outside air connection allows your vent termination 1 00 08543 25 to be as close as 18 from windows or doors Outside air is optional except in mobile homes and where building codes require The benefit of Inlet Cover part outside air is mainly noticed in small very tight 1 10 08542 houses To install outside air use 2 3 8 non combus tible flex pipe There is a break away hole on the rear panel of the P43 stove which must be removed before connecting the flex pipe The pipe should be run outside and terminate to the side or below the vent pipe outlet so the flue outlet is more than 12 from the inlet cover The maximum length run of this pipe is 15 feet If a longer run is needed the size must be increased to 3 Inlet cover part number 1 10 08542 should be used to keep birds rodents etc out of the pipe You may choose to use the optional Direct Vent Wall Passthrough Kit part 1 00 677077 which incorporates the venting passthrough and outside air inlet into one component Direct Vent Wall Passthrough Kit part 1 00 677077 oo HRV When installing in a house with a Heat Reclaim ing Ventilation System HRV be sure the system is balanced and is not creating a negative pressure in the house P43 Pellet Stove 9 mn Te Fig 9 10 P43 Pellet Stove to Stibles to to comb Ebles 1 Preferred method This method provides excellent venting
2. Floor Protection must be 2 inches to each side 6 inches to the front and 1 inch to the back of the stove Floor Protector minimum 3212 wide 33 deep 1 3216 minimum 33 minimum 6 measured from glass Requirements for Terminating the Venting WARNING Venting terminals must not be recessed into wall or siding NOTE Only approved pellet vent pipe wall pass throughs and fire stops should be used when venting through combustible materials NOTE Always take into consideration the effects of the prevailing wind direction or other wind currents that may cause flyash and or smoke when placing the termination of the vent In addition the following must be observed The clearance above grade must be minimum of 18 1 B The clearance to a window or door that may be opened must be a minimum of 48 to the side 48 be low the window door and 12 above the with outside air installed 18 to the side or below 12 clearance to a permanently closed win dow is recommended to prevent condensation on the window D The vertical clearance to a ventilated soffit located above the terminal within horizontal distance of 2 feet 60 cm from the center line of the terminal must be minimum of 18 E The clearance to an unventilated soffit must be a minimum of 12 F The clearance to an outside corner is 11 from center of pipe G The clearance to an insid
3. Flashing min PL vent firestop and support No insulation or other combustible materials are allowed within 3 of the pellet vent pipe Unless specified by the pipe manufacturer See Page 6 for corner installation clearances 1 IE hie 5 Fig 14 8 Installing through the ceiling Through the ceiling vent follow PLvent manufacturers recommendations when using wall and ceiling pass through Note Do not place joints within wall pass throughs Fig 16 Minimum flue vent configuration It is recommended that outside air be installed with this venting configuration to reduce smoke and creosote smell in the room in the event of power failure a O S gt QO vm S Fig 15 12 min wall to outlet P 36 min clearance to any combustible material P43 Pellet Stove 13 P43 AUTOMATIC IGNITION ESP CONTROL Power Light Feed adjuster Indicates power to the Sets the maximum control feed rate Test POWER Runs all motors at full speed for one minute to Status Light A check operation After Will be lit in either stove two minutes the stove or room temp mode will go to minimum burn when pointer is not DISTRIBUTION BLOWER and the blowers will within off position band alternate from high to except after normal shut COMBUSTION BLOWER low every minute to down Blinks to indicate remind
4. MANUAL Stove Temperature Mode The advantage of this mode is to allow the operator to have a large viewing fire without blowing extra heat into the room During operation with the temperature dial set at 5 or less the distribution fan will not operate A 5 on the temperature dial and a 5 on the feed adjuster is approximately 80 output It is not necessary to oper ate the distribution blower below this point This control setting allows a higher burn rate a larger viewing fire without an excess of hot air blowing into the room An example of when to use the Manual Stove Tem perature Mode is if you want to watch a large fire and the room is already up to temperature The Stove Temperature Mode allows you to have a larger fire and a lower sound level without the distribution blower NOTE During the use of this mode if you keep increasing the temperature dial setting to increase the fire size the distribution blower will automati cally come on when the ESP Temperature reaches 350 F or 81 output P43 MANUAL START UP Helpful Hints 1 Fines are small pieces of broken pellets sawdust Fines do not flow easily and often build up on the hopper funnel bottom angles You can push these fines into the feeder opening and then fill the hopper with pellets As the system works they will be burned Or you can clean them out before filling the hopper As the system works they will be burned 2 The TEST cycle will operate the fe
5. 13 NOILVTIVLSNILG SNOILONYLSNI 591 NOTES YISNILN 13 MITTVLSNI SISSYWOIG NO SATISILSNENOD SALLIINO 3TE8LLSNEINOD Z1H3H 09 S3LTOA 02 9 ANDIYLOATA JONVSSINd NOILONYLSNOD XNVI01 9000 37 NOTIS 13 LNVOINEV4 SNOLLONYLSNI 31 NOTAS STIVLSNI 19 NO 1 YNILVIILNIA LNAINIddVHIAC ILYOS 19 3100 SAG ZS LNYAY INVONAL3S 19 10130 JTSLLSNEWOONI YNSLOALONd YSHONW1d NN YNS SOW Id J413 LO SJINMIY SIYLNIO 30 JLYOd Y1 13 SYNLYSANO d V1 ANINITNIS MIYIdO SNOSIVW SII HINIAIYA 67Z WW 6Zz NY 37304 JGp JSP 37130d 1530 LG 3730d IYIMYV YAW 9 908 3730d 3102 YAN 3109 30 310930 SITELLSNEINOO XNVINILVIN S3C SUNnaLoaLoud SYUNILDILOYd INNINININ S3I498IT S390vdS3 31 591 SNYS 0 Wd AVOU 3SNOH NIVLNNOW ZSE NynuvH Jed anbuge4 Ag SITVENN SNOILJ3L0Ud SNVS NO I TONV NOILVTIVLSNI WWGZZ 6 SCTAIHS ACIS LNOHLIM YO 6 NOILVTIVLSNI YANYOD S3ITVYNIN SNOILIILOUd SNVS 13 TVYILVT SYNIN SADNVLSIG SCTAIHS 3AIS LNOHLIM NOILVTIVLSNI TivMMoVa ANODIGNI SAWWOD FILIYNDIS 30 WNWINIW SJONVLSIG 37 YSTIVLSNI NMOHS SV STIVM OL S30
6. 20 X 375 FHN 250 20 ZINC GRADE 5 20 el cc 1 P43 Pellet Stove 27 P43 Specifications 212 Ibs 135 cfm Feed Rate approximate 75lb to 5 5 Ibs per hr Hopper Capacity 50 Ibs Fuel Wood Pellets Flue Size 3 inch Outside Air Size 2 3 8 inch Fuse Rating 6 amp 28 P43 Pellet Stove OPTIONS Side Heat Shields Side heat shields are available to reduce the clearance to combustible materials Part 41 00 00000 Hopper Extension The hopper extension allows you to put more pellet fuel in the hopper and extends burn time on one load of pellets The hopper extension adds 60 pounds to the existing 60 pound hopper capacity allowing you to load 120 pounds of pellets at one time Part 1 00 08536 Direct Vent Wall Passthrough Kit You may choose to use the optional Direct Vent Wall Passthrough Kit part 1 00 SSN 677077 which incorporates venting passthrough and outside air into one y i component YV Decorative Tile Grey Slate Options The decorative tile and slate measure 11 938 x 5 938 The tile slate frame is necessary to hold the tile or slate in place on the stove There are 10 decorative tile choices and 4 decorative slate choices See dealer for samples The Brushed Stainless deer cutout pictured below is another option available This cutout reveals the color of the stove through the cut out shapes frame tile slate P43 Pellet Stove
7. 29 O ka Q gt 2 OVAOGL OOG SILIVM 3SN GYVONVLS Yee 4HOY IVAOGL 097 SILVM YOLOW H39NY X30334 3118 LINDI YOLON NOLLSNEWOD YIMOT1G NOLNGIYLISIG MOTISA ALdN3 3LIHM SLIHM SLIHMA 3LIHM a399N 1 SNOILOSNNOD I3TYWNIJI ITYN NMOYG LL 4LIHM Nid MTN OM 0 SLOYLNOD O N aNd Li HIUMS 35055359 MOT SNOILOJNNOS JAIM JC din Nada AQOG JAOLS OL 039NOG SIMOd YOSN3S ILONIN ANNOYS SI IMIM NIIYO n JLIHM DQ NMOH3 SNOILOINNOD 3TYNII ITYN ONIMIM JAOLS 131134 894 194 NYNYYH 91 30 43 Pellet Stove P43 Parts List Options Description Hopper Gasket 5 ft Ash Pan Assembly Burn Pot Weldment Right Rear Shield Left Rear Shield Arrow Scraper Flame Guide Wiring Harness Assembly Thermister Probe Room Sensor Circuit Board Differential Switch 5 Double Fan Blade Combustion Blower Distribution Blower Hopper Lid Latch Hopper Throat Gasket Power Cord Auto Ignite Label Control Panel Door Fire Brick 1 White Black Control Knob 3 Control Knob Shaft 3 Front Door Glass Burn Pot Gasket 1 Tailpipe Gasket Wiring Diagram Control Panel Sticker Owner s Manual Hopper Lid Label Igniter Element Cleanout Cover 1 1 4 20 x 1 2 Wing Screw w Collar 2 Muffler Hopper Extension Assembly Outside Ai
8. DESIGNATED FOR SLEEPING CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED MOBILE HOME INSTALLATION SHOULD BE DONE IN ACCORDANCE WITH THE MANUFACTURED HOME AND SAFETY STANDARD HUD CFR 3280 PART 24 CAUTION KEEP COMBUSTIBLE MATERIALS SUCH AS GRASS LEAVES ETC AT LEAST 3 FEET AWAY FROM THE FLUE OUTLET ON THE OUTSIDE OF THE BUILDING Assembly installation Shipping Bolts Note These same holes are used for securing the stove in mobile home installation Rear Cover Panels Unpacking The P43 is bolted 1 4 x 1 hex head bolts to the skid to prevent movement during shipping To free the stove from the skid you must remove the hold down bolts in the rear of the pedestal base Removing rear cover panels The rear cover panels are secured to the stove with three bolts each Two ot the bolts need only be loosened not removed to remove the panels It is recommended that the rear covers are installed after the unit is in place and the vent pipe is installed to prevent contact with hot or moving parts Firebrick Install the firebrick horizontally on the angle bracket above the burnpot Flame Guide Install the cast iron flame guide on top of the burn pot Make sure that the flame guide is fully seated on the vertical sides of the burn pot and that the back of the guide rests against the body of the stove INSTALL EXHAUST VENT AT CLEARANCE
9. feed rate is too high you may waste fuel 5 This is usually a weekly maintenance procedure Cleaning the burn pot with the scraper with a small amount of new fuel in the bottom is not a problem First scrape the ashes off the front of the burn pot into the ash pan Then scrape the top surface of the burn pot downward into the base of the burn pot When the stove is ignited these scrapings will be pushed out by the feeder and burned 6 The ash pan can hold the ashes from approximately 1 ton of premium fuel This means the ashes will only need to be emptied a few times a year 7 Setting the feed adjuster for maximum burn With the unit burning in AUTO to Stove Mode and put the fan on Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes and check ash on front of burn pot Fig 18 If the ash line is larger than 1 turn the feed adjuster from 4 to 5 Allow another 30 minutes of burn time and check again If at 6 setting a 1 or less ash bed is not obtainable it is not a problem The 1 ash bed is only a maximum burn rate and at most normal settings the ash bed will be larger Starting First Fire Igniter Switch to AUTO up position Make sure the unit is plugged into a 120 VAC 60 HZ electrical source The power light should be the only light lit NOTICE Be sure there is no unburned fuel or other combustibles in the ash pan prior to lighting 1 Turn Mode Selector to OFF 2 Fill hop
10. for normal operation and allows the stove to be in stalled closest to the wall Two inches from the wall is safe however four inches allows better access to remove the rear panel The vertical portion of the vent should be three to five feet high This vertical section will help provide natural draft in the event of a power failure Note Do not place joints within wall pass throughs 2 Preferred method This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least three inches from a combustible wall This vertical section will provide natural draft in the event of a power failure If the stove is installed below grade be sure the vent termination is at least 18 above grade The outlet must also be 1 foot from the house building Note Do not place joints within wall pass throughs CAUTION Keep combustible materials such as grass leaves etc at least 3 feet away from the flue outlet on the outside of the building 12 min wall to outlet 36 P clearance to any combustible material 4 Installing into an existing chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of power failure If the chimney condition is questionable you may want to install a liner as
11. for any reason Secondly if you are using the Harman battery back up system the Manual setting will prevent the stove from turning off and on during a power failure which would drain the back up battery and possibly cause damage to the back up or the stove In the Room Temperature Mode the distribution blower speed can be increased or decreased by adjusting the Room Temp Off Stove Temp dial between L and H As output of the stove increases the speed of the blower will increase automatically to insure that more heat is transferred out into the room The distribution blower will shut off as the room reaches the set temperature this will prevent overheating of the room Room Temperature Mode POWER O STATUS O DISTRIBUTION BLOWER COMBUSTION BLOWER FEED MOTOR AUTO IGNITER IGNITER D MANUAL Room Temperature Mode This setting see above will produce room temperature of 70 degrees with the distribution blower at medium speed Circuit Board Dipswitches On the face of the circuit board there is a series of 8 switches These ON OFF switches are used to set the timings and temperatures for the different models of stove For a P43 the switches numbered 5 and 8 should be with the rest of them off NEVER ADJUST THESE SWITCHES YOURSELF AS SERIOUS ISSUES COULD DEVELOP Also know that if there is a need to replace an ESP probe a switch change may also be needed It is strongly recommended t
12. should be cleaned after each ton of pellets 50 bags and the venting system inspected and cleaned after each ESP heating season Probe Fig 33 Be careful not to damage ESP probe when cleaning with brush P43 Pellet Stove 23 P43 Maintenance Burn Pot A Burn pot igniter Viewed from below through the ash pan opening Fig 36 24 P43 Pellet Stove g Burn Pot Cleaning and Maintenance 1 Scrape the top holed surface and sides of the burn pot Fig 33 Itis not necessary to completely remove all material from the burn pot The excess will be pushed out during the next use DANGER Disconnect the power to the unit before removing cover 2 Loosen the 2 wing thumb screws on the lower front angle of the burn pot Fig 34 3 Lift off the clean out cover Fig 35 to open the bottom clean out chamber Fig 36 4 Clean ash buildup from inside the chamber while cover is off Use the scraper to tap on the top front edge of the burn pot This will help knock pieces of ash loosened by the scraping process down through the holes It also helps knock scale off of the igniter element Figure 36 The igniter is made to be removable for service by insulated male female wire connectors These connections between the hot leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the inside re
13. will at its option repair or replace the product as described below The warranty above constitutes the entire warranty with respect to Harman Home Heating products HARMAN MAKES NO OTHER WARRANTY EXPRESSED OR IMPLIED INCLUDING ANY WARRANTY OF MERCHANT ABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE No employee agent dealer or other person is authorized to give any warranty on behalf of Harman This warranty does not apply if the product has been altered in any way after leaving the factory Harman and its agents assume no liability for resultant damages of any kind arising from the use of its products In addition the manufacturer and its warranty administrator shall be held free and harmless from liability from damage to property related to the operation proper or improper of the equipment THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HERE OF THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user s manual THESE WARRANTIES WILL NOT APPLY if abuse accident improper installation negligence or use beyond rated capacity causes damage HOW TO MAKE A CLAIM Any claim under this warranty should be made to the dealer from whom this appliance was purchased Then contact is made with manufacturer giving the model and serial numbers the date of purchase your dealer s name and address plus a simple explanation of the nature of the defect Extra costs
14. you that you are errors listed below PEED O MOTOR AUTO still in Test Mode IGNITER J IGN ER OD MANUA Igniter switch Set to appropriate Indicates power to Start Up mode distribution blower got bt Distribution Blower lt n speed adjustment 7 sin bee Variable speed Indicates power to combustion blower Indicates power to the feed motor 5 OVE We anywhere between L 60 55 and H although as the stove temp goes up Indicates power to the WARNING HIGH VOLTAGE so does the low end of igniter Disconnect power before opening cover the scale T dial Mode Selector emp dia Dealer Diagnostic Port Allows you to choose between Allows you to adjust the room temperature in Room For dealer maintenance Temp Mode using the outer scale marked in degrees only Requires special DDM Fahrenheit It also allows you to adjust the stove monitor supplied to Harman temperature while in Stove Temp Mode using the inner Dealers exclusively scale marked from 1 to 7 Room Temp Mode Stove Temp Mode or OFF Also allows you to vary the distribution blower speed by turning the knob to the high or low side of each mode Status light error messages 1 Blink Indicates control board self diagnostic fail 6 Blinks Indicates that the control has calculated ure This requires a manual reset poor or incomplete combustion occurring for more 3 Blinks Indicates ESP Exhaust Sensing Probe than 50 min
15. 695 511 8 F1SCOW 19G0N 3215 NNNINIIN 40014 SQTAIHS 3AIS NOILVTIVLSNI TIVMMOVEA TIVMAAIS 006 6 18 NOD340 60913 WLSV 2871 10 OL 931591 LESCO N M 490 SAY aa ra P43 Pellet Stove 2 introduction The P43 Pellet Stove has huge features in a small package giving you 0 to 43 000 BTU when you need it automatically You basically need to set your desired room temperature and fill the hopper With the P43 you will notice even heat throughout your zone and a level of convenience you never thought possible The P43 epitomizes the capability of Harman Pellet Stoves taking advantage of Harman s 20 years of pellet stove design technology and manufacturing This 43 000 BTU stove has the smartest controls coupled with minimal maintenance The P43 s output is managed by a microprocessor that senses the room temperature and the fire temperature with tiny thermistor probes and then determines the best feed rate for your heating demand This improved and smarter control also has a diagnostic port which allows a service representative to attach an external display showing live working data for ease in troubleshooting The platinum combination is Harman s Patented Feeder amp Burn Pot and ESP Control which have been developed to their highest state These features work together to allow amazing heat output with little regar
16. ER 40 CFR 60 534 METHOD 28A EXEMPTION EPA PAR 40 VED FOR USE IN MOBILE HOMES APPROUVE POUR L USAGE DANS LES MAISONS MOBI T RATING 75 TO 5 5 LBS PER HOUR TAILLE MINIMALE PUISSANCE ESTIMEE 75 5 5 LBS PAR HEURE 50 CONNECT THIS UNIT CHIMNEY SERVING ANOTHER APPLIANCE DELAPROTECTIONDE SOL NE PAS CONNECTER CET APPAREIL UNE CHEMIN E SERVANT UN AUTRE APPAREIL MADE IN USA Please read this entire manual before you and use your new room heater Failure to fol RUCTION PUISSANCE LECTRIQUE 6 AMPS 120 VOLTES 60 HE FR 60 534 DE M THODE 28a 229 EMENT AVEC LA PORTE STOVE TOP 18 domm YOUVERTURE ET Li PORTE DES CENTRES FERM ES L APPAREIL DOIT ETRE P RUN PLANGHER PROTECTEURINCOMBUS TIBLE CELUL CIS ET EVENT HOUSE FIRES OPERATE WITH VIEWING amp ASH DOOR CLOSED DISTANCES AUX MURS DISTANCES AUX MURS mm EN AVANT DE 152 mm DES COTES ET D 25 mm DE L ARRIERE LACED ONANON COMBUSTIBLE FLOOR PROTECTOR EXTENDING LAT RAL ET ARRIERE AVEC LAT RAL ET ARRIERE SANS CHAPPEMENT VENTILATEUR DE TYPE L FRONT FROM GLASS RUCTIONS DU FABRICANT ET SELON LES CORNER II 9 WITI CODES LOCAUX DE LA RTZ BIOMASSES SELON LES INSTRUCTIONS D INSTALLATION ET ELACONSTRUCTIONOU D OP R UD AND OPERATING INSTRUCTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS LE DES N IERS AU SUJET DES RESTRICTIONS ET DES INSPEC
17. H VOLTAGE Disconnect power before opening cover This setting will produce large viewing fire without distribution blower operating 18 P43 Pellet Stove The P43 Pellet Stove is capable of manual operation This also allows the operator to manually control operation during an emergency i e igniter failure when using a 502H battery backup as opposed to the 512H or when using certain generators The unit can be switched between AUTO and MANUAL at any time during op NOTE When starting the unit in the AUTO mode and switching to MANUAL the fire must be large enough to start the distribution blower The starting of the blower is a signal that the start cycle is completed and the fire will not go out Igniter Switch to MANUAL Room Temperature Mode The fire will have to be lit with starting gel and a match or started automatically see Automatic Opera tion on Page 15 Turn to Manual position when the fire is established The difference between AUTO Room Temperature Mode and Manual Room Temperature Mode is that the fire will not go out as the room temperature goes above the control board setting The unit can only go to low burn and will remain there until it runs out of fuel or until more heat is needed and the feed rate increases Feed rate adjustments and dial settings are the same as AUTO settings The blower will shut off com pletely if the temperature on the ESP is too low Igniter Switch to
18. Installation amp Operating Manual P43 Pellet Stove Owners Manual We suggest that our NTERTE hearth products be installed and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Specialists SAFETY NOTICE PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH FOR USE IN THE U S AND CANADA SUITABLE FOR INSTALLATION IN MOBILE HOMES IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED HOUSE FIRE MAY RESULT FOR YOUR SAFETY FOL LOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILDING DEPARTMENT FIRE DEPARTMENT FIRE PREVENTION BUREAU ETC TO DETERMINE THE NEED FOR PERMIT CETTE GUIDE D UTILISATION EST DISPONIBLE EN FRANCAIS CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE COMPANY SAVE THESE INSTRUCTIONS Manual Itemit 3 90 04301 00 0 06 N d VSN 3AVN IUNIH S91 S S SZ SAWILSA JONVSSINA SITIGOW SNOSIVN 37 SNVG JOVSN TI IANOYddV 287 JOOHLIN v S 09 440 OF NOLLANIX3 JOVNISIOA SYLOA SNVG NOILVTIVLSNI G SNOILOAdSNI 13 SNOILOILSSY 30 LANs NY SYIIdWNOd 30 NYINNE IT NO NOLLONHLSNOOVT3A NYAYNEITHILOVLNOO 3A NOLLVHIOG
19. LLET FUEL DO NOT BURN GARBAGE IN STOVE P43 Pellet Stove 19 P43 Low Draft Voltage Adjustment Combustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation POWER STATUS O DISTRIBUTION BLOWER COMBUSTION BLOWER WARNING HIGH VOLTAGE onn wer before ni Fig 22 Low Draft Voltage Adjustment These units are pre tested at the factory with exactly 120 Volts A C 60 Hz They are checked and adjusted for firebox tightness gasket leakage motor operation and igniter operation The P43 is then factory set ata mid point adjustment and in most cases will not need any adjustments NOTE The factory low draft setting may not be correct for the unit s permanent installation conditions The control board on the P43 is equipped with low draft adjustment port Located on the control face just to the right of the igniter light This voltage adjustment is provided to allow the unit to be adjusted for the household voltage where the unit is going to be in permanent operation NOTE The line voltage varies from area to area and often home to home The low draft voltage should be adjusted to achieve the most efficient burn on low burn or maintenance This voltage adjustment allows the installer to change the low voltage set point approximately 10 volts This adjustment should be done by the installer during se
20. NVYVITO INNNININ HLIM TIVLSNI ALLANOILA 31199 SVd 3N TIVMAGIS SATEILSNEWOD SALLAINOG SAC YITNYE YNOd ATSGOW JO INDOTVIVI ADVAINVHD 30 WAdVddV YALVSH WOOY ONINYNE 7315 13713 0318511 198 vddv JYLNV NA 1 5 IININIHO ANN T3YVddV 139 YALOANNOO SVd JONVITddV YSHLONV 9 5 AINNIHO OL LINN SIHL LOANNOD LON OG YNOH Hdd 59196 OL 97 ONILVY LNANI S3WOH 3T180N NI ASN 8 GOHLIN HEG 09 459 OF LANIX3 VIYV YNOA NI NOILOAdSNI NOLLWTIVLSNI 9 594 LNOYV 10S NOILDALONd ITVNININ 3T11VL NOLLVTIVLSNI S HIYNLOVINNVIN HLIM JONVAYODDV NI AINO SSN ANY TIVLSNI SSVINOIG 37119713 1913 ZLYAH 09 SLIOA 021 SdNV 9 SNILVY 1 1 S3009 WOOT ANY SNOILONYLSNI SYAYNLOVANNVA LNSA OL GATIVLSNILNSA 1d YO AdALLSNVHXS SaTVUNW SSV19 LNOYS IYNSVIN YVIY OL wb ONY 53015 OL 9 SHL OL 9 13 Wwaalv1 ONIONILX940103104d YOO 15 IT8LLSNEWOD NON Y NO 39 1 38 LSNW LINN Sony 138019 4000 HSV 8 ONIMAIA HLIM ILVHI3dO S3UI4 ISNOH INIAIYd TIVM IWNODVIG OL YSANHOO SAOLS a8 dOl SAOLS OL 5 i il JAOLS OL TIVMMOVE OL OL JAOLS OL TIVM3CIS SQTAIHS 3AIS SCTIHS 3AIS SATEILSNEWOD OL HLIM 1NOHLIM SJONVYV3TO INNININIIN 166 3Lva LSAL ca TEL T98V1 3009 S20 Nd HM L
21. S SPECIFIED BY THE MANUFACTURER Most pellet vent pipe requires a minimum of 3 of clearance to combustible materials allthough some can be installed at 1 clearance P43 Pellet Stove 9 Installation 6 Installing Place the stove noncombustible floor protector that extends minimum of 6 inches to the front mea sured from the glass 6 inches to the sides and 1 inch to the rear of the hopper In some places it is required that floor protection be installed under any horizontal venting The minimum floor protector material is 20 gauge sheet metal Other floor protector materials are ceramic tile stone brick etc Place the stove away from combustible walls at least as far as shown in Figures 3 4 and 5 Note the difference in side wall clearance with and without side shields Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing Connect the power cord to a 120 V A C 60Hz grounded receptacle surge protector is recom mended to protect the circuit board If the voltage entering your home is below 116 volts your stove may not work properly Also be sure that the polarity of the outlet that the stove is plugged into is correct Prior to installing the flue pipe connect a draft meter The draft meter must have a minimum range of 0 5 Record the first reading Connect flue pipe to stove and be sure all doors and windows in the home are closed Reco
22. TIONS 5 LES install low instructions may result in property damage bodily injury or even death 352 Mountain House Road Halifax PA 17032 Table of Contents Safety Information Installation Venting ESP Control Automatic Operation Manual Operation Low Draft Voltage Adjustment Room Sensor Maintenance Trouble Shooting Feeder Parts Specifications Options Wiring Diagram Parts List Warranty P43 Pellet Stove 3 IMPORTANT NOTES 4 DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT THIS UNIT TOA CHIMNEY FLUE SERVING ANOTHER APPLIANCE SPECIAL NOTE DUE TO FLY ASH BUILDUP IT IS STRONGLY RECOMMENDED THAT YOU HAVE YOUR STOVE PROFESSIONALLY CLEANED AND SERVICED ANNUALLY THIS INCLUDES ALL PARTS OF THE STOVE AND THE ENTIRE VENTING SYSTEM CAUTION ALWAYS BE SURE THERE IS NO UNBURNED FUEL IN THE ASH PAN PRIOR TO LIGHTING A FIRE THIS WILL CAUSE SMOKE AND SOOT AND OTHER UNWANTED RESULTS INSTALLATION AND REPAIR OF THIS HARMAN STOVE SHOULD BE DONE BYA QUALIFIED SERVICE PERSON WE RECOM MEND THAT THE STOVE BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON PERIODIC CLEANING IS REQUIRED THROUGHOUT THE HEATING SEASON AND AT THE END OF EACH WINTER FOR THE STOVE TO WORK EFFICIENTLY SEE CLEANING INSTRUC TIONS ON PAGE 22 P43 Pellet Stove WARNING MOBILE MANUFACTURED HOME STANDARDS DO NOT ALLOW INSTALLATION IN ROOMS
23. Temperature Mode Most consumers use the stove in the Room Temperature Mode because it is the easiest and most efficient method of keeping the room at a given temperature In the Room Temperature Mode the Room Sensing Probe constantly monitors room temperature As the weather changes outside and your home needs varying amounts of heat to be at a desired temperature the stove will automatically increase fire size and heat output so that a constant even temperature is maintained If the weather warms up and no heat is required the stove will gradually shut down When the house cools down the stove will automatically bring the room temperature to the precise temperature you desire In the Room Temperature Mode you can select either Auto or Manual modes for the igniter using the igniter toggle switch When the toggle switch is in the Auto position the igniter located inside the burn pot is ready to automatically light the fire wnen required When the toggle switch set to the Manual position the stove can be lit manually with either a gel or a wax type fire starter see lighting instructions on page 19 With the igniter toggle switch set in the Manual position the stove will automatically adjust heat output but the stove will not automatically shut down if no heat is required Instead it will go to its lowest setting and remain there The Manual position on the igniter toggle switch lets you light the stove manually should the igniter fail
24. aning or emptying the hopper P43 Pellet Stove 25 P43 Trouble Shooting FEEDER DOES NOT FEED 1 No pellets in hopper 2 Firebox draft may be too low for low draft pressure switch in feeder circuit to operate Check for closed doors loose or missing gasket on doors or hopper lid or a faulty pressure switch 3 Feed motor will not run until the ESP control senses 165 deg F Maybe you did not put enough pellets in the burn pot before manually light ing the fire 4 Something is restricting flow in the hopper or caus ing the slide plate to stick 5 Feed motor has failed PARTIALLY BURNED PELLETS 1 Feed rate too high 2 Draft too low Check burn pot clean out slide and door gasket 3 Burn pot or heat exchanger tubes may need to be cleaned 4 Combination of all the above 5 6 status blink blink control board status indi cation is caused by poor or incomplete combustion The Automatic Ignition circuit board has the ability to track the combustion through feed settings and ESP temperatures When the control board has calculated poor or incomplete combustion it will shut down the unit as a Safety feature Poor or incomplete combus tion is a contributer of creosote which may cause a chimney fire A blink status may be caused by several things 1 Blocked or partially blocked flue 2 Blocked or partially blocked inlet air a Backdraft damper on the inlet pipe may be stuck closed b If outside air is instal
25. ar of the feeder body Not coiled inside the burn pot It is very important that these connections are to the inside rear of the feeder body Also the extra wire of the igniter wire service loop must be pulled out through the rear of the feeder and tied up so that it will not be damaged by any moving parts WARNING Use caution when cleaning burn pot clean out chamber Do not damage the high temperature igniter wires Igniter hot lead wires high temperature Note The hot lead cold lead connection must always be pulled to the rear of the feeder body before operation P43 Maintenance Cleaning the Feeder Body Pellet fines will accumulate in the feeder body over period of time therefore yearly inspection and cleaning of this area must be performed 5 16 Hex Head Screws 2 on each side To clean out fines EEE 1 Remove the rear cover panels Screws 2 on 2 Remove wing nut and feeder cover on the side of the feeder 3 Use vacuum cleaner to remove all fines 4 Reinstall feed cover wing nut and rear cover panels Pellet Fines will build up in this area The low draft sensor monitors air pressure in the hopper Failure to close the hopper lid will result in the feed motor not running Depending on the amount of fines in the fuel being burned this fitting known as the muffler may need to be cleaned Note the location of the muffler and use special care when cle
26. be installed even if only installed on the rear of the unit as a return air sensor Rear Shields 5 16 Hex Head Screws 3 on 5 16 Hex Head each side Screws 3 on each side Fig 25 The rear insulated shields are split in the middle for easy removal Each shield has 3 5 16 hex head screws Two 2 that only need to be loosened and one 1 that needs to be completely removed to allow the shield to slide away from the unit NOTE It is not recommended that the unit be operated with the shields removed due to the hot and moving parts which they protect P43 Pellet Stove 21 Maintenance Cleaning the Door Glass e Always use a soft cloth and glass cleaner such as Windex or a mixture of vinegar amp water to clean the glass Do not use razor blades or any other hard object to scrape the glass Removing Ashes When approximately 1 ton of pellets has been burned it will be necessary to empty the ash pan Ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a noncombustible floor or on the ground well away from all com bustible materials pending final disposal If ashes are disposed of by burial in soil or other wise locally dispersed they should be retained in the closed container until all cinders have thoroughly cooled 1 Pull on latch handle and remove ash pan Use ash pan handle to carry and dispose of ashes Combusti
27. d for fuel quality We suggest that our hearth products be installed and serviced by professionals who are certified in the U S by the National Fireplace Institute NFI as NFI Specialists www nficertified org This label is located on the back of the unit Please copy the Serial Number for future reference POUR R LER DES BOULETTES COMBUSTIBLES MOD LE PP 38 P43 Manufactured By Fabrique Par 352 MOUNTAIN HOUSE ROAD HALIFAX PA 17032 UL 1482 ASTM E1509 814 23 900 ESPACES LIBRES MINIMUM EN PN 025 JUNE 1997 CLEARANCES WITH 2 51mm 51mm DU MOR RRIERE Al POEL TO COMBUSTIBLES DU PLAFOND AU DESSUS DU PO LE LTO STOVE 1 DU COIN DU PO LE AU MUR DIAGONA LL TO STOVE 16 PR VENIR LES Fi EL MAISONS OPERER SEUL RNER TO DIAGONAL WALL THE FRONT TO SIDES AND 1 TO RI EASUR YPE ISTEDTYPEL ORPL VENT INSTALLED TO VENT MANUFACTURER S NSTRUCTIONS AND LOCAL BUILDING CODES ELECTRICAL RATING 6 AMPS 120 VOLTS 60 HERTZ COMBUSTIBLE DE BOULETTES COMBUSTIBLES OU FUEL PELLETIZED OR SS 9 229mm NSTALLER E LISER NSTALL AND USE ONLY IN ACCORDANCE WITH MANUFACTURER S INSTALLATION 1 AT OND ABRICANT CONTACTERLE BUREAI ABOUT RESTRICTIONS amp INSTALLATION INSPECTION IN YOUR AREA 2 m D INSTALLATI N DANS VOTRE en EXEMPT P
28. d soot USING A VACUUM WHICH IS NOT EQUIPPED WITH A FINE DUST FILTER WILL BLOW FLY ASH AND SOOT OUT INTO THE ROOM NOTE THE STOVE MUST BE COMPLETELY OUT BEFORE YOU VACUUM THE STOVE LIVE PEL LETS IF SUCKED INTO THE VACUUM WILL LIGHT Fig 28 Fig 29 THE VACUUM ON FIRE AND MAY ULTIMATELY Latch closed with blower Latch open with blower A HOUSE FIRE cover in place Burn pot cover partly removed Burn clean out is closed pot clean out is open 9 Use a brush to clean the flue being careful not to damage the ESP probe see Fig 30 The flue goes straight through into the vent pipe Fig 27 therefore the vent pipe can also be cleaned to some extent through the flue outlet 10 Reinstall blower cover and relatch 11 Slide ash pan into stove and latch the door Blower cover removed Brush not Fig 30 Exposed blower wheel and flue opening NOTE ESP probe is visible supplied can be found in hardware stores Fig 32 Soot and Fly Ash The products of combustion will con tain small particles of fly ash which must be removed from the inner walls of the stove and from the venting system periodically Removing fly ash and soot improves efficiency insures that the flue venting passageway is clear and unobstructed The stove
29. e corner is 12 H Avent must not be installed within 3 feet 90 cm above a gas meter regulator assembly when measured from the horizontal center line of the regulator Vent terminal Air supply inlet The clearance to service regulator vent outlet must be a minimum of 6 feet J The clearance to a non mechanical air supply inlet to the building or the combustion air inlet to any other appliance must be a minimum of 48 K The clearance to a mechanical air supply inlet must be a minimum of 10 feet with outside air installed 6 feet L The clearance above a paved sidewalk or a paved driveway located on public property must be a mini mum of 7 feet M The clearance under a veranda porch deck or balcony must be a minimum of 12 inches NOTE The clearance to vegetation and other exte rior combustibles such as mulch is 36 as measured from the center of the outlet or cap This 36 radius continues to grade or a minimum of 7 feet below the outlet Certain Canadian and or Local codes or regula tions may require different clearances 2A vent shall not terminate directly above a side walk or paved driveway which is located between two single family dwellings and serves both dwellings 3Only permitted if veranda porch deck or balcony is fully open on a minimum of 2 sides beneath the floor NOTE Where passage through a wall or partition of combustible construction is desired the installation s
30. eder motor for exactly one minute Turning to TEST again and again may purge too much fuel into the burn pot causing excessive smoke on start up 3 The firebox low pressure switch will not allow the auger motor or the igniter element to operate if the view door or the ash pan door are open 4 Adjust Feed Rate Ifthis is your first fire or you are trying different pellets set the feed adjuster to 4 Fig 19 This is conservative number and will probably need to be increased After you know feed rate setting that works well use that setting Remember if your feed rate is too high you may waste fuel 5 This is usually weekly maintenance procedure Cleaning the burn pot with the scraper with a small amount of new fuel in the bottom is not problem First scrape the ashes off the front of the burn pot into the ash pan Then scrape the top surface of the burn pot downward into the base of the burn pot When the stove is ignited these scrapings will be pushed out by the feeder and burned 6 The ash pan can hold the ashes from approximately 1 ton of premium fuel This means the ashes will only need be emptied a few times a year 7 Setting the feed adjuster for maximum burn With the unit burning in AUTO turn to Stove Mode and put the fan on Set the Temperature Dial to 7 Allow the unit to burn for about 30 minutes and check ash on front of burn pot Fig 21 If the ash line is larger than 1 turn the feed adjuster fr
31. hall conform to CAN CSA B365 if in Canada 7 GO Inside Corner etail mal i 7 Area where terminal is not permitted 43 Pellet Stove 7 8 IMPORTANT NOTICE Approved Pellet Vent Pipe Such As Type L Or PL Must Be Used Positive Static Pressure Negative Static Pressure Fig 7 P43 Pellet Stove Venting combustion blower is used to the combustion gases from the firebox This causes a negative pressure in the firebox and positive pres sure in the venting system as shown in Fig 7 The longer the vent pipe and more elbows used in the system the greater the flow resistance Because of these facts we recommend using as few elbows as possible and 15 feet or less of vent pipe The maximum horizontal run should not exceed 48 If more than 15 feet of pipe is needed the interior diameter should be increased from 3 to 4 because a larger pipe causes less flow resistance Be sure to use approved pellet vent pipe wall and ceiling pass through fittings to go through combustible walls and ceilings The use of a starting collar is not always necessary The first piece of pipe should be fastened securely with at least 2 fasteners to the flue collar of the stove If a starting collar is used to attach the venting system to the stove the starting collar must be sealed to the stove with high temp silicone caulking Vent Pipe Pellet venting pipe Kno
32. in method 7 In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the tile liner you will need to install a Stainless steel liner within the chimney In most cases the inside diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 6 amp 7 Be sure to design the venting so that it can be easily cleaned 5 Installing into an existing fireplace chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in method 6 In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the tile liner you will need to install a stainless steel liner within the chimney In most cases the inside diameter of this liner should be 4 Either flexible or rigid liner may be used for this purpose Refer to Method 6 amp 7 The chimney should be sealed at the damper using a steel pla
33. led the inlet cover may be blocked 3 The air chamber under the burnpot may be filled with fines and small bits of ash 4 The holes in the burnpot may be getting filled with ash or carbon buildup 5 Combustion blower fan blades may need cleaned 6 There is no fuel in the hopper SMOKE SMELL Seal the vent pipe joints and connection to stove with silicone FIRE HAS GONE OUT 1 No pellets in hopper 2 Draft setting is too low 3 Something is restricting fuel flow 4 Feed motor or combustion blower has failed 5 Power failure or blown fuse 26 P43 Pellet Stove SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high B Draft too low caused by a gasket leak LOW HEAT OUTPUT 1 Feed rate too low 2 Draft too low because of gasket leak 3 Poor quality or damp pellets 4 Combination of 1 and 2 Helpful Hints Cleaning Burn Pot Whenever your stove is not burning take the opportunity to scrape the burn pot to remove carbon buildup A vacuum cleaner is handy to remove the residue Be sure the stove is cold if you use a vacuum Carbon buildup can be scraped loose with the fire burning using the special tool provided with your stove Scrape the floor and sides of the burn pot The carbon will be pushed out by the incoming fuel Always wear gloves to do this Removing Ashes Turn the Temp Dial to number 1 approximately 30 minutes before removing ashes This will result in a cooler stove a
34. mediately and may take more than an hour to fully shut down If the stove is left to run out of fuel you may get a 6 blink status light If this happens simply reset the control board by turning the mode selector to OFF and back ON Stove Temperature Mode The setting above will produce continuous medium heat output with the distribution blower at low speed The setting above will produce continuous maximum heat output with the distribution blower at full speed P43 AUTOMATIC START UP SeeHint 7 Helpful Hints 1 Fines are small pieces of broken pellets sawdust Fines do not flow easily and often build up on the hopper funnel bottom angles You can push these fines into the feeder opening and then fill the hopper with pellets As the system works they will be burned Or you can clean them out before filling the hopper 2 The TEST cycle will operate the feeder motor for exactly one minute Turning to TEST again and again may purge too much fuel into the burn pot causing excessive smoke on start up 3 The firebox low pressure switch will not allow the auger motor or the igniter element to operate if the view door or the ash pan door are open 4 Adjust Feed Rate If this is your first fire or you are trying different pellets set the feed adjuster to 4 Fig 17 This is a conservative number and will probably need to be increased After you know a feed rate setting that works well use that setting Remember if your
35. nd ash pan Maximum Feed Adjuster settings are not need ed in most cases Operating in the normal range 4 is recommended when maximum heat output is not required The ESP probe prevents the stove from being over fired Keep the stove free of dust and dirt Fuel Pellet fuels are put into 3 categories in terms of ash content Premium at 1 or less Standard at 3 orless and all others at 3 or more The P43 is capable of burning all 3 categories of pellets due to a patented feeder and burn pot system It should be noted however that higher ash con tent will require more frequent ash removal scraping of the burn pot and may provide less BTU s per pound Normally standard and high ash pellets cost less than premium pellets and can be cost effective when burned in the P43 The moisture content must not exceed 8 Higher moisture will BTU s and may not burn properly P43 Feeder ITEM Part Nane 1 10 724132 ULTRALIGHT FEEDER WELDMENT UL FEEDER PUSHER ARM WELDMENT o2 ot 1 10 677187 P38 P43 ACCENTRA ACCENTRA INSERT ee racer serere Perier reemer cene moror a een e co oaoas PELLET searing ermer 15 HWH TCS 10 24 X 75 BLACK UL FEEDER GEARMOTOR BRACKET 1 2 GROMMET TEK SCREW 10 X 75 1 TEK SCREW 10 X 75 UL FEEDER AIR INTAKE EPDM GASKET 04 093 750 MASKING CAP 04 3 30 2252003813 82 FLNG 25
36. ng is lower very slowly turn the set screw clockwise until the draft increases NOTE The test mode alternates from high to low draft every 60 seconds If more time is needed for draft adjustment wait until the next low draft cycle NOTE In some cases the draft may not go as low as 35 to 45 even with the set screw completely counter clockwise Ideally you should just set it as low as possible Room Sensor and Rear Shield Installation Room Sensor Installation Av A 7 Fig 24 The room sensor 5 small temperature sensor on the end of 60 wire This sensor is installed much like a standard wall thermostat Because is SO small it can be hidden along the trim of a door way or even up the leg of a coffee table There is a remote room sensor port on the rear of the unit for easy external connection Use standard 18 2 ther mostat wire to extend the distance to the desired location 50 maximum The room sensor should be installed in the location where you want to control the temperature In most installations locating the room sensor behind the stove near the distribution fan works well because the sensor monitors the room air being drawn into the distribution fan NOTE Distances of more than 25 feet from the unit or in another room are not recommended The room sensor is essential for the P43 s excellent ef ficiency NOTE It is recommended that the room sen sor
37. o have a trained service representative make any repairs to the appliance Location of Dipswitch amp gas P43 Pellet Stove 15 P43 AUTOMATIC IGNITION OPERATION Stove Temperature Mode In the Stove Temperature Mode and with the igniter toggle switch in the Auto position the stove will light automatically and can be adjusted to the desired setting using the same temperature control dial as is used in the Room Temperature Mode The heat output and fuel consumption will remain constant regardless of room temperature The settings from 1 to 7 on the inner ring of the temperature dial provide for relative heat output settings with 1 being low and 7 being the maximum In Stove Temperature Mode the stove will not automatically shut off unless the stove runs out of fuel or is turned off Never pull the plug to shut down the stove This will stop the combustion blower and smoke will escape through window and door gaskets When the igniter toggle switch is set to manual in this mode the distribution blower will not turn with temperature dial setting from 1 to 5 The advantage of this mode is to allow the operator to have large viewing fire without blowing extra heat into the room During manual operation with the temperature dial set at 45 or less the distribution fan will not operate A 45 on the temperature dial and a 5 on the feed adjuster is approximately 80 output It is not necessary to operate the di
38. om 3 to 4 Allow another 30 minutes of burn time and check again If at 6 setting a 1 or less ash bed is not obtainable it is not a problem The 1 ash bed is only a maximum burn rate and at most normal settings the ash bed will be larger Starting First Fire Igniter Switch to MANUAL down position Make sure the unit is plugged into a 120 VAC 60 HZ electrical source The power light should be the only light lit NOTICE Be sure there is no unburned fuel or other combustibles in the ash pan prior to lighting 1 Turn FEED ADJUSTER to desired feed rate No 4 is good for most pellets 2 Turn the MODE SELECTOR to OFF and then to the desired mode This will reset con trol and start the combustion motor 3 Turn the TEMPERATURE DIAL to the desired setting 4 Clean burn pot with scraper if necessary 5 Fill burn pot with pellets only level with front edge Do Not Over Fill 6 Add starting gel on top of the pellets Stir gel into pellets for fast lighting 7 Light starting gel with a match and close the door Operation will begin when the fire reaches the proper temperature 8 Fill hopper with pellets and remove ashes as required 6 WARNING NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IN USE WARNING ONLY USE WOOD PE
39. on Blower Cover 2 Slide the ash pan back into the stove and latch the Blower Cover Latch door by pushing down on the latch handle rig 20 Cleaning The stove should be cleaned after burning ap proximately 1 ton of pellets 50 bags The cleaner the stove the more efficient it will be You will burn less pellets and heat output will be greater Heat Exchanger Fins Note Higher ash content pellets will require more frequent cleanings 1 Shut down stove and disconnect power cord to insure that all motors are stopped 2 Clean heat exchanger with scraper as shown in fig 27 Scraper 3 Brush or scrape the inside of the stove to remove fly ash 4 Scrape burnpot with flat end of scraper provided with the stove Inspect the holes on the burnpot surface See Fig 33 Outlet 5 Open burn pot clean out Clean fly ash from burn pot and replace cover Blower 6 Remove ash pan 7 Remove combustion blower cover by turning the blower cover latch vertical see Fig 26 Sliding the Blower Cover cover out of the slot on the left This will expose Latch the combustion blower wheel and flue outlet Fig 27 22 P43 Pellet Stove Maintenance Burn pot Clean out 8 Clean the combustion blower wheel with a brush and a vacuum cleaner Note Do not use a household vacuum to clean the stove We recommend that you use a shop vacuum that is equipped with a fine dust filter called a HEPA filter or a vacuum specially made for fly ash an
40. per with pellets 3 Clean burn pot with scraper if necessary gt 4 If starting after an empty hopper turn Feed Adjuster to TEST for one 60 second This will purge pellets into the auger tube and also allow you to check the motors for operation NOTE The auger motor will not operate with the view door or ash pan door open 5 Turn Feed Adjuster to 4 6 Flip the Igniter Switch up into the AUTO position 7 Turn the Temperature Dial to the desired temperature 8 Turn Mode Selector to Room Temperature or Stove Temperature 9 Fill hopper with pellets and remove ashes as WARNING NEVER USE GASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THIS HEATER KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IN USE WARNING ONLY USE WOOD PELLET FUEL DO NOT BURN GARBAGE IN STOVE P43 Pellet Stove 17 P43 MANUAL IGNITION OPERATION POWER STATUS DISTRIBUTION BLOWER COMBUSTION BLOWER eration FEED MOTOR IGNITER D Room Temperature Mode This setting see below will produce room temperature of 70 degrees with the distribution blower at medium speed POWER STATUS DISTRIBUTION BLOWER COMBUSTION BLOWER AUTO IGNITER MANUAL FEED MOTOR IGNITER Q 50 WARNING HIG
41. r Assembly 2 3 8 X 25 Flex Pipe Log Set Side Heat Shields Air Grill Door Frame wi ash lip amp tile slate trim Tile Pack 1 piece Decorative Slate 1 piece Direct Vent Wall Passthrough Part Number 0 88 00248 1 10 7738108 1 10 00675 2 00 773828 1P 2 00 773828 2P 2 00 773850 3 00 03000 3 20 08727 3 20 00844 red wire 3 20 00906 3 20 05886 3 20 6866 3 20 502221 3 21 08639 3 21 22647 3 31 199110 3 44 677185 3 20 39685 3 90 06100 3 40 900450125 3 31 605 3 31 015 3 40 950133125 3 44 00409 3 44 06179 3 89 06504 3 90 06655A 3 90 04301 3 90 08416 3 20 06783 2 00 06623 3 31 782108 3 40 06618 Fitting 3 40 1818 1 00 08536 1 10 08542 1 00 08543 3 40 5647 1 00 773863 3 43 08646 See Dealer for finish options 1 00 08500 See Dealer for finish options 3 43 1206 01 thru 10 10 choices Floral 3 43 06731 11 Horses 3 43 06731 12 Deer 3 43 06731 2 Lighthouse 3 43 06731 9 1 00 677077 P43 Pellet Stove 31 HARMAN GOLD WARRANTY 6 YEAR TRANSFERABLE LIMITED eon WARRANTY Residential 1 YEAR LIMITED WARRANTY Commercial WARRANTY Harman warrants its products to be free from defects in material or workmanship in normal use and service for a period of 6 years from the date of sales invoice and for mechanical and electrical failures in normal use and service for a period of 3 years from the date of sales invoice If defective in material or workmanship during the warranty period Harman
42. rd the second draft reading If the second reading more than 05 lower than the first reading check for possible restrictions or the need for outside air see page 9 For more information on the draft test procedure refer to Page 20 Mobile Home Installation When installing this unit in mobile home several requirements must be followed 1 The unit must be bolted to the floor This can be done with 1 4 lag screws through the 2 holes in the base plate 2 The unit must also be connected to outside air See page 9 3 Floor protection and clearances must be followed as shown 4 Unit must be grounded to the metal frame of the mobile home CAUTION This appliance must be vented to the outside Due to high temperatures the stove should be placed out of traffic and away from furniture and draperies Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns to skin and or clothing Young children should be carefully supervised when they are in the same room as the stove Clothing and other flammable materials should not be placed on or near this unit WARNING Mobile Manufactured Home Standards Do Not Allow Installation In Rooms Designated For Sleeping P43 Pellet Stove 9 With or Without Side Shields
43. rols and customer education Labor materials expenses and or equipment needed to comply with law and or regulations set forth by any governmental agencies are not covered This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state In the event of change in ownership the remaining portion of this warranty may be transferred to the new owner by sending the new owner information and a transfer fee of 25 00 US to Harman PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DE VICES THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES NOT HARMAN OR THEIR WARRANTY ADMINISTRATOR FURTHERMORE THESE ACCESSORY DEVICES MUST BE INSTALLED AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER REMEDIES The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or anything done in connection therewith whether in Contract in tort under any warranty or otherwise shall not except as herein expressly provided exceed the price of the equipment or part of which such liability is based CLARIFY The above represents the complete warranty which is given in connection with stoves manufactured by Harman No other commitments verbal or otherwise shall apply except by a written addendum to this warranty
44. stribution blower below this point Therefore the control allows a higher burn rate a larger viewing fire without an excess of hot air blowing into the room An example of when to use the Manual Stove Tempera ture Mode is if you want to watch a large fire and the room is already up to temperature The Stove Tempera ture Mode allows you to have a larger fire and a lower sound level without the distribution blower NOTE During the use of this mode if you keep increasing the temperature dial setting to increase the fire size the distribution blower will automati cally come on when the ESP Temperature reaches 350 F or 81 output Feed Adjuster Knob For most premium grade pellet fuels the Feed Adjuster Knob should be set at 4 If higher ash fuels are used the setting should be increased to 5 or 6 Also higher settings are required if you would like to get the maximum heat output from the stove At the maximum burn rate with the temperature dial on 7 90 and the feed adjuster at 6 there should be 1 or more of ash on the front of the burn pot If there is less than 1 of ash turn the feed adjuster knob down to a lower setting 16 P43 Pellet Stove Shut Down Procedure The best way to shut down the stove is to simply let it run out of pellets The stove will shut down automatically Alternatively you can turn the Mode Selector to off This will cause the fire to gradually die down and go out The fire will not go out im
45. such as mileage and overtime are not covered Nuisance calls are not covered by these warranties THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS REPAIR AND OR REPLACEMENT AT HARMAN S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL DAMAGES CON NECTED THEREWITH WARRANTY EXCLUSIONS Failure due but not limited to fire lightning acts of God power failures and or surges rust corrosion and venting problems are not covered Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic brick panels ceramic fiber afterburners door packing tile ceramic log sets paint bat teries or battery back up and related duct work are not covered Also excluded from this warranty are consumable or normal wear items including but not limited to flame guides grates coal bars afterburner hoods fire brick gaskets Additional exclusions for corn stoves are burnpot housing weldment burnpot grate weldment pellet or corn burnpot front plate pel let or corn burnpot front plate lock corn auger extension ceramic insert and ceramic insert plate Additional or unusual utility bills incurred due to any malfunction or defect in equipment and the labor cost of gaining access to or removal of a unit that requires special tools or equipment are not covered Maintenance needed to keep the stove in good operating condition is not covered This includes but is not limited to cleaning adjustment of customer cont
46. t up because draft meter reading is required to insure proper set up If the unit is not adjusted properly it does not cause a safety concern If the unit is adjusted too high only effiency is lost If the unit is adjusted too low the low draft pressure switch will not allow the feed motor or the igniter to operate 20 P43 Pellet Stove Draft Meter bolt hole location On a P43 the draft test hole is under the left rear corner of the firebox A simple draft test should be performed after completing the flue pipe installation To record the results for future reference 1 Plug unit into a 120VAC 60 HZ outlet 2 Close the hopper lid front view door and the ash pan Neither pellets or a fire are required for this test 3 With the mode selector in the OFF position turn the feed adjuster to TEST 4 Record the high draft in W C Normal is 50 to 60 The control will be on the High Draft for a total of 2 minutes 5 After 2 minutes the combustion motor will go down to low draft and the distribution blower will go on high Allow approximately 15 seconds to pass for the combustion motor to slow before checking the low draft 6 If the low draft is between 35 and 45 record the reading in W C If the reading is higher slowly turn the set screw counter clockwise until the draft lowers If the readi
47. te or with insulation at the first flue tile In both cases the connector pipe should extend through the smoke chamber to the base or into the first flue tile Be sure to design the venting so that it can be easily cleaned P43 Pellet Stove 11 12 P43 Pellet Stove bl 6 Installing into an existing fireplace chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of power failure In some places the US and Canada it is re quired that the vent pipe extend all the way to the top of the chimney The pipe or liner inside the chimney should be 4 diameter In this method cap should also be installed on the chimney to keep out rain Be sure to use ap proved pellet vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 7 Installing into an existing chimney This method provides excellent venting for normal operation This method also provides natural draft in the event of power failure In some places the US and Canada it is re quired that the vent pipe extend all the way to the top of the chimney The pipe or liner inside the chimney should be 4 diameter In this method cap should also be installed on the chimney to keep out rain ay ET 1 2 Storm collar
48. utes failure This requires a manual reset A six blink status may be set if the stove is allowed 4 Blinks Can occur only in Room Temp Mode and to run out of pellets To reset turn mode selector to indicates Room Sensing Probe failed or not installed OFF then back on to the desired mode If the unit Room Sensing Probe is then installed the status W S Not out of pellets see Troubleshooting section light will automatically reset ped ower cord for few 5 Blinks In Igniter Auto Mode Only Indicates EE that the unit has failed to light within the 36 minute 3900nds and reconnect If error still occurs call your start cycle To reset Turn Mode Selector to OFF then turn to either mode again 14 P43 Pellet Stove P43 AUTOMATIC IGNITION OPERATION The P43 is a fully automatic stove that features two operating modes Stove Temperature Mode and Room Temperature Mode In Stove Temperature Mode you select a burn rate and the stove will remain at the same burn rate regardless of the room temperature In the Room Temperature Mode the stove constantly monitors the temperature in the room and adjusts the size of the fire and the heat output of the stove so that the room is kept at a constant temperature Room mode in the AUTO position has the added advantage of turning the stove off if no heat is required and turning the stove on again when the room temperature drops below your desired room temperature Room
49. wn as L or PL vent is constructed of two layers with air space between the layers This air space acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of 1 to 3 inches The sections of pipe lock together to form an air tight seal in most cases However in some cases a perfect seal is not achieved For this reason and the fact that the P43 operates with a positive vent pressure we specify that the joints also be sealed with silicone Aluminum tape can also be used for any joint that is 1ft or more from the outlet of the stove We cannot emphasize enough the importance of sealing every seam and joint in the venting system which is inside the home Even the smallest pin hole can leak and when it does you will smell wood smoke or a creosote smell in the room If this occurs check for leaks Leaks are easiest to see during start up Alternatively you can use a smoke pellet to leak test the venting before lighting your first fire Outside Air Here four benefits of outside air Outside air flex pipe goes here 1 Having air introduced from outside the living area boosts thermal efficiency Because the make up air is not being drawn in through leaky windows or doors 2 Outside air connection eliminates draft problems that can occur in tight homes 3 Outside air connection reduces smoke spillage in the event of power failure Flex pipe
Download Pdf Manuals
Related Search
Related Contents
fundraising - Association Française des Fundraisers mode d emploi - Labover Market ES_FWSS 100315.indd Bedienungsanleitung Dell PowerEdge 1900 Installation Manual Unold Glass advertencia - Remington Power Tools SMASH TV Maison E+ -Atelier de la Grange Invacare® Flamingo / Flamingo Compact Copyright © All rights reserved.
Failed to retrieve file