Home

Alliance Laundry Systems T477C User's Manual

image

Contents

1. P Your tumbler can be Models Hy a oe ihe late converted to the ges following voltages T30 120 Volt 60 Hertz 208 240 Volt 60 Hertz 1 Phase 1 Phase T30 200 220 Volt 60 Hertz 100 Volt 60 Hertz 1 Phase 1 Phase T30 200 Volt 50 Hertz 100 Volt 50 Hertz 1 Phase 1 Phase T30 240 Volt 60 Hertz 200 208 Volt 60 Hertz T45 3 Phase 3 Phase T30 380 Volt 50 Hertz 400 415 Volt 50 Hertz 3 Phase 3 Phase Table 9 NOTE Electric models are not field convertible and must be connected to service specified on serial plate 70304601 Electrical Requirements If tumbler requires conversion for use on another service voltage complete the steps detailed in the Conversion Instructions section prior to connecting service to machine If tumbler does not require conversion or has been converted according to the Conversion Instructions section of this manual continue with step 1 NOTE The wiring diagram is located in the upper junction box or upper contactor box 1 For new service install a circuit breaker or fused disconnect of proper voltage and current rating as close to each tumbler as possible 2 Route service conduit from circuit breaker panel or disconnect panel to tumbler service connection box Conduit routing should not obstruct access for maintenance or servicing Refer to Service Ground Location 3 Pull conductors through conduit and attach to circuit breaker and ground connection Secure service g
2. TMB2135N 1 Gas Shut Off Valve Assembly closed position 6 Required Burner Orifice Pressure 2 Gas Valve 7 Manometer 3 Burner Orifice 8 Hose Connect Over Loosened Slotted 4 Regulator Adjusting Housing and Gasket Pressure Tap Screw in Bottom of Gas Valve Regulated version shown 9 Spud Holder 5 Gas Valve Bracket 10 Outlet Pressure Tap Figure 7 22 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 How to Change Burner Orifice Size 1 4 Disconnect electrical power from tumbler Close gas shut off valve to tumbler Refer to Figure 6 For Johnson GM7000 gas valve Remove burner orifice s from the spud holder Refer to Figure 7 Install the new correct burner orifices Refer to Figure 8 Torque each to 9 10 Nm Commission tumbler for use NOTE Blank burner orifices are available as Part No M400995 How to Adjust Gas Valve Governor Regulator 1 Check gas burner orifice manifold pressure as follows Refer to Figure 7 Loosen screw plug inside pressure tap located on underside of valve Connect a U tube manometer or similar pressure gauge to the tap Start tumbler and note pressure once flame is burning Remove regulator cap and adjust regulator screw until the burner orifice pressure per applicable table is achieved Replace regulator cap and close needle valve pressure tap Commission tumbler for use 70304601 BURNER ORIFICE TMB201
3. au AE C R ES Ae E 1 8 TUTA K Ek A TMB1969N Rear Exhaust Models Diameter A B C 730 Elliptical 36 54 in 4 25 in 62 42 in Fits 8 in 203 mm 928 mm 108 mm 1585 mm T45 Elliptical 40 88 in 4 75 in 66 00 in Fits 10 in 254 mm 1038 mm 121 mm 1676 mm 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 11 Specifications and Dimensions Gas Connection Locations EE TMB1970N 1 1 2 in NPT Models Gas Connection A B C Non CE and 75 20 in 1 74 in 36 84 in Non Australian 1910 mm 44 mm 936 mm T30 CE and 75 28 in 2 5 in 30 60 in Australian 1912 mm 64 mm 777 mm T45 78 75 in 4 12 in 42 88 in 2000 mm 105 mm 1089 mm 12 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Specifications and Dimensions Electrical Connection Locations Y at at GAS AND STEAM ELECTRIC TMB1971N Electric Service Models Gas and Steam Models Electric Models A B C D E T30 59 in 1 75 in 35 63 in 73 21 in 2 28 in 1498 mm 44 mm 905 mm 1859 mm 58 mm 62 5 in 1 75 in T45 1588 mm 44 mm N A N A N A N A Not Applicable 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 13 Specificatio
4. Equivalent length Total Btu hr Using Table 7 the mai connected to single TMB2126N 1 Gas Furnace 120 000 Btu hr 8 25 ft 7 6 m 2 Gas Water Heaters 400 000 Btu hr each 9 Main Regulator 3 Gas Space Heaters 70 000 Btu hr each 10 Gas Meter 4 Sediment Traps Supply Pressure Taps and 11 Pressure Regulator if required Shut off Valves Refer To Figure 13 12 T30 Tumblers 73 000 Btu hr per pocket 5 1 in 25 4 mm Gas Pipe Loop 146 000 total Btu hr for machine 6 19 ft 5 8 m T45 Tumblers 95 000 Btu hr per pocket 7 Minimum Pipe Size is 0 5 in 12 7 mm 190 000 total Btu hr for machine SAMPLE CALCULATIONS Total length of main gas supply pipe to the far end of the tumblers 25 ft 19 ft 7 6 m 5 8 m gas supply pipe 44 ft 13 4 m Total Gas Line The sum of the Btu hr of all T30 tumblers being fed by the main gas supply pipe 9 x 73 000 657 000 Btu hr n supply pipe diameter should be 2 in 51 mm IMPORTANT Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers gas service Other gas using appliances should be connected upstream from loop 32 Figure 14 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Gas Requirements Gas Pipe Size Required for 1000 Btu Natural Gas 0 64 Specific Gravity at 7 1 5 inches 17 4 4 mbar 1 74 0 37 kPa Water Column Pres
5. 40 in 1016 mm 34 in 864 mm 43 in 1092 mm 37 in 940 mm 46 in 1168 mm 39 in 991 mm 47 in 1194 mm 40 in 1016 mm 43 in 1092 mm PA ET TOT mMm DoJ a Table 6 50 in 1270 mm 51 in 1295 mm 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 29 Gas Requirements To reduce the risk of fire or explosion DO NOT CONNECT THE GAS LINE TO THE TUMBLER IF THE GAS SERVICE IS NOT THE SAME AS THAT SPECIFIED ON THE TUMBLER SERIAL PLATE It will first be necessary to convert the gas burner orifice and gas valve Appropriate conversion kits are available IMPORTANT Any product revisions or conversions must be made by the Manufacturer s Authorized Dealers Distributors or local service personnel IMPORTANT The tumbler must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 0 5 psig 3 45 kPa 34 5 mbar IMPORTANT The tumbler and its manually operated appliance gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 0 5 psi 3 45 kPa 34 5 mbar IMPORTANT The installation must comply with local codes or in the absence of local codes e with the latest edition of the National Fuel Gas Code ANSI
6. sq cm working pressure A shut off valve must be installed downstream from each steam trap so the condensate return line can be isolated in event a steam trap requires maintenance Each steam trap must be supported so minimum load is exerted on the coil outlet connection W066 70304601 Steam Requirements SUPPLY RETURN T4731 NOTE Refer to Table 13 for sizing of steam lines Piping must also be sized accordingly for length of runs and number of elbows 1 Steam Coil 6 Trap with Built In Strainer 2 12 in 305 mm Riser 7 Vacuum Breaker Optional 3 Condensate Return Line from Supply Line 8 18 in 457 mm Drop 4 Shut Off Valve 9 Solenoid Valve Supplied with machine 5 Check Valve 10 Union Figure 15 Model Steam Pressure PSI bar Minimum Pipe Diameter Steam Trap Size Pounds Condensate Hour T30 15 100 1 6 9 3 4 in NPT 110 Based on 100 psi Table 13 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 45 Single Drop Timer NOTE The following information is for models with an SD control suffix only Power Up Mode When power is applied to the tumbler the JV USE light flashes factory status information Following this the control goes into READY Mode light off or RUN Mode if power was interrupted during a cycle light on time remaining unchanged Ready Mode In READY Mode light off the control waits for the vend to
7. Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 33 Gas Requirements High Altitude Burner Orifice Sizing For proper operation at altitudes above 2000 feet 610 meters the gas burner orifice size must be reduced to ensure complete combustion Refer to Table 8 For CE models consult local gas supplier Altitude Burner Orifice New Rate pce ee Feet Meters No Inches mm Quantity Part Btu hr Number T30 Natural Gas 2001 4000 610 1220 22 0 1570 4 0 M402996 134 320 4001 6000 1221 1830 24 0 1520 3 9 M402980 122 640 6001 8000 1831 2440 26 0 1470 3 7 M401000 110 960 8001 10 000 2441 3050 28 0 1405 3 6 2 M401014 99 280 L P Gas 2001 6000 610 1830 42 0 0935 2 4 M403017 134 320 6001 8000 1831 2440 43 0 0890 2 3 M406184 110 960 8001 10 000 2441 3050 44 0 0860 2 2 M401011 99 280 T45 Natural Gas 2001 4000 610 1220 15 0 1800 4 6 M411511 183 000 4001 6000 1221 1830 17 0 1730 4 4 M411374 168 400 6001 8000 1831 2440 18 0 1695 4 3 M402988 155 000 8001 10000 2441 3050 20 0 1610 4 1 2 M401002 142 600 L P Gas 2001 4000 610 1220 36 0 1065 2 7 M402487 183 000 4001 6000 1221 1830 37 0 1040 2 6 M411375 168 400 6001 8000 1831 2440 38 0 1015 2 6 M411376 155 000 8001 10000 2441 3050 40 0 0980 2 5 M406361 142 600 Btu hr d
8. KEES SeSe Ee sed ge soe EE 27 Gas Reguirements eie ee ee ee ee ee ee ee AA ee ee ee 30 Gas Supply Pipe Sizing and Looping 0 00 0 esse esse ese ee GR Re ee 32 High Altitude Burner Orifice Sizing esse esse ese esse ee Ge ee ee se 34 Electrical Reguirements esse see see ee ee Re GR RA ee Re ee RA 35 Grounding Instructions nenese n i ees tatai 35 For CE Models Only nier mee ese sever EE E aeS 35 Service Ground Lo atot secin a A i risi 36 Connecting Electrical Servic iese sees sk Se ee ee ee ee 37 Configuring Your Tumbler for Other Service Voltages 37 Electrical Connection sesse esse se ee ge iN aa 37 Conversion Instructions Lees see see e se AG Ge ee ee GR ee ee Ge 38 Electrical Requirements for Gas and Steam Models esse esse ese ee 40 Electrical Requirements for Electric Models esse ses see see se ese ee 42 Steam Reguirements esse ee ee ee EA RA GR ee RA RA GR 43 Piping Recommendations 000 0 ee esse see see ee ee Ge GR AR Re ee se 43 Installing Steam Trap and Making Condensate Return Connections 44 Copyright 2008 Alliance Laundry Systems LLC All rights reserved No part of the contents of this book may be reproduced or transmitted in any form or by any means without the expressed written consent of the publisher 2 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or
9. TRANSMIT Single Drop Timer RO ER IE N N 46 PowerUp Mode is 27a ER EES N eg ee ie ee ge eg De ea Eg de Ee bg 46 Ready Mode ict vei ninth cate en apenas DE eN eigen eee tant 46 Start de RE EE EE adores oes eri RE N OO 46 Run Mod ae SE casas DEE iat ae a aes Geeta 46 Setting Dry Time DipswitcheS iese sesse see ee Ge SR ee Ge GR de 46 Dipswitch Settings sessie see eo LESS se tb eiia og gee ie gee dee gede Ee 47 Adjustments se ee EE nee EE Ee aden vcd ta cde be Ge eg cates tees 49 Loading Door S Witch is Ese sg EES ces ane gee pe ee Ee a geed 49 Piel Ad ie EE EE N RS KE e eieh 49 Door Sol GEE AE ae a NE 50 Removing Tumbler from Service iis ee sa AR ee ee RA 51 Introduction Model Identification Information in this manual is applicable to these models Gas Steam Electric CHD30STG2 CAT30L IPD30STG2 ITT30L CHD30STS2 CTT30S CHD30STE2 CTT30E CHD30STG2 CAT30N IPD30STG2 ITT30N CHD30STS2 CUT30S CHD30STE2 CUT30E CHD30STG2 CTT30L MTT30N DRST30S2 BTT30S DRST30E2 BTT30E CHD30STG2 CTT30N NTT30N DRST30S2 BUT30S DRST30E2 BUT30E CHD30STG2 CUT30L SAT30L HTT30S HTT30E CHD30STG2 CUT30N SAT30N HUT30S HUT30E DRST30G2 BAT30L STT30D IPD30STS2 ITT30S IPD30STE2 ITT30E DRST30G2 BAT30N STT30L STT30S STT30E DRST30G2 BTT30D STT30N SUT30S SUT30E 730 DRST30G2 BTT30L SUT30L UTT30S UTT30E DRST30G2 BTT30N SUT30N UUT30S UUT30E DRST30G2 BUT30L UAT30L DRST30G2 BUT30N UAT30N HAT30L UTT30L HAT30N UTT30N HTT30D UUT30L HTT30L UUT30N HTT3
10. air inlet shutter as required Refer to Adjustments section 18 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 9 Wipe out the cylinder using an all purpose cleaner or detergent and water solution Refer to Figure 5 Va T4521 Figure 5 If the tumbler does not meet ANY of the listed requirements remove tumbler from use Refer to Removing Tumbler from Service section Required for CE Models Only Once machine is installed please be sure to complete the following items e Review and verify machine operation with customer e Leave all literature and a signed Declaration of Conformity with customer e Review machine warranty information with customer e Apply warning sticker on front panel of machine in language appropriate to country of sale included in literature packet 70304601 Installation Installing CE Gas Drying Tumblers To reduce the risk of electric shock fire explosion serious injury or death e Disconnect electric power to the tumbler before servicing e Close gas shut off valve to gas tumbler before servicing e Close steam valve to steam tumbler before servicing Never start the tumbler with any guards panels removed Whenever ground wires are removed during servicing these ground wires must be reconnected to ensure that the tumbler is properly grounded W002 General Information This information is to be used wh
11. each additional 20 feet 6 1 m Cross sectional area of a rectangular or square duct must be increased 20 for each additional 20 feet 6 1 m Refer to Table 5 or Table 6 to determine equivalent ducting sizing The collector duct may be rectangular or square in cross section as long as the area is not reduced Provisions MUST be made for lint removal and cleaning of the collector duct The vent collector system must be designed so the static back pressure measured 12 inches 305 mm from the exhaust outlet does not exceed the maximum allowable pressure specified on the installation sticker on the rear of tumbler Static back pressure must be measured with all tumblers vented into the collector operating 70304601 Exhaust Requirements NOTE Never connect a tumbler duct at a 90 angle to the collector duct Refer to Figure 10 Doing so will cause excessive back pressure resulting in poor performance Never connect two tumbler exhaust ducts directly across from each other at the point of entry to the collector duct With the tumbler in operation and both pockets running airflow at any point in the duct should be at least 1200 feet per minute 366 meters per meter to ensure that lint remains airborne If 1200 feet per minute cannot be maintained schedule monthly inspections and cleaning of the ductwork OR T4381 Figure 10 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 27 Exhaust Requi
12. guards and or panels removed DO NOT operate the tumbler if it is smoking grinding has missing or broken parts Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 29 30 31 DO NOT bypass any safety devices Solvent vapors from dry cleaning machines create acids when drawn through the heater of the drying unit These acids are corrosive to the tumbler as well as to the laundry load being dried Be sure make up air is free of solvent vapors Failure to install maintain and or operate this machine according to the manufacturer s instructions may result in conditions which can produce bodily injury and or property damage To reduce the risk of serious injury install lockable door s to prevent public access to rear of tumblers W055 70304601 Specifications and Dimensions Specifications T30 T45 Noise level measured during operation at operator 66 dBA 67 dBA position of 3 3 feet 1 meter in front of machine and 5 2 feet 1 6 meters from floor Net Weight approximate 544 673 Pounds kg 247 305 Cylinder Size 30 x 26 33 x 30 Inches mm 762 x 660 838 x 762 Cylinder Capacity dry weight 2 x 30 2x45 Pounds kg 2 x 13 6 2 x 20 5 Drive Motor Horsepower 1 4 1 2 Fan Motor Horsepower 1 4 1 2 50 Hertz 340 N A Maximum Airflow per Pocket 160 C F M Vsec 60 Hertz 400 600 189 283 50 Hertz 0 8 N A Ma
13. if the airflow switch does not operate properly Faulty airflow switch operation may cause an explosive gas mixture to collect in the tumbler W072 IMPORTANT Airflow switch vane must remain closed during operation If it opens and closes during the drying cycle this indicates insufficient airflow through the tumbler If switch remains open or pops open and closed during the cycle the heating system will shut off The cylinder and fan will continue to operate even though the airflow switch is indicating insufficient airflow NOTE To properly mount the airflow switch bracket or in case of a load not drying the airflow switch bracket may need to be checked for proper alignment Be sure the locator pins are securely in their respective holes before tightening the bracket mounting screws This will assure proper alignment of the airflow switch arm in the channel of the airflow switch bracket and prevent binding of the arm Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 49 Adjustments Door Strike The door strike must be adjusted to have sufficient tension to hold loading door closed against force of the load tumbling against it There is proper adjustment of pull force when 8 to 15 pounds 35 6 N 66 7 N is required to open door If adjustment is required refer to Figure 17 and proceed as follows To adjust open door loosen acorn nut and turn door strike screw in or out as required Retighte
14. l 3 31 and ground 230 240V 50Hz L1 Neutral 15 0 20 1 12 3 31 1ph and ground 200 208V 60Hz L1 L2 L3 6 4 10 3 14 2 08 3ph and ground 240V 60Hz 3ph HELE 6 4 10 3 14 2 08 and ground L1 L2 L 1 14 2 08 200V 50Hz 3ph fed one ae a 208 and ground 230 240V 50Hz LI L2 L3 7 0 10 3 14 2 08 3ph and ground 380V 50 or 60Hz L1 L2 L3 3 0 10 3 14 2 08 3ph and ground 400 415V 50Hz L1 L2 L3 3 2 10 3 14 2 08 3ph and ground 460 480V 60H2 L1 L2 L3 3 3 10 3 14 2 08 3ph and ground 3 Phase machines should not have fuses breakers only Table 10 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 40 For T45 Gas Models For Total Machine Electrical Requirements Serial Plate Terminal Block Curren Recommended Fuse Breaker Minimum Voltage Required Amps Amps Poles Conductor Size AWG mm 208 240V 60Hz 1ph L1 L2 Neutral and ground 12 0 15 2 14 2 08 200 208V 60Hz 3ph L1 L2 L3 and ground 9 6 15 3 14 2 08 240V 60Hz 3ph L1 L2 L3 and ground 9 6 15 3 14 2 08 200V 50Hz 1ph L1 Neutral and ground 11 2 15 1 14 2 08 230 240V 50Hz 1ph L1 Neutral and ground 10 8 15 1 14 2 08 Table 11 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 41 Electrical Requirements Electrical Requirements for Electric Models Refer to Table 12 NOTE Minimum wire sizes are obtained from Canadian Electrical Cod
15. on the rear of the tumbler NOTE Static back pressure must be measured with both pockets running The maximum allowable length venting of the same diameter as the exhaust thimble is 14 feet 4 3 m and two 90 elbows or equivalent If the equivalent length of a duct required for an installation exceeds the maximum allowable equivalent length the diameter of a round duct must be increased by 10 for each additional 20 feet 6 1 m Cross section area of a rectangular duct must be increased by 20 for each additional 20 feet 6 1 m Refer to Table 4 to determine equivalent venting 70304601 Exhaust Requirements Duct Equivalent Length of Diameter Straight Duct 10 in 254 mm One 90 elbow 11 6 ft 3 5 m 12 in 305 mm One 90 elbow 14 ft 4 3 m 14 in 355 6 mm One 90 elbow 16 ft 4 9 m 16 in 406 4 mm One 90 elbow 18 7 ft 5 7 m 18 in 457 2 mm One 90 elbow 21 ft 6 4 m Equivalent Length feet 1 17 x Duct Diameter inches Table 4 Example A 12 inch 305 mm diameter duct s equivalent length of 14 feet 4 3 m of duct and two 90 elbows is Equivalent Length 14 feet 2 90 elbows 14 feet 14 feet 14 feet 42 feet 12 8 m With the tumbler in operation and both pockets running airflow at any point in the duct should be at least 1200 feet per minute 366 meters per meter to ensure that lint remains airborne If 1200 feet per minute cannot be m
16. regulations and any other relevant statutory regulations Due to varied requirements applicable local codes should be thoroughly understood and all pre installation work arranged for accordingly Material Required Obtain Locally One fused disconnect switch or circuit All Models Eier One gas shut off valve for gas service Gas Models line to each tumbler One steam shut off valve for steam service line to be connected upstream of solenoid steam valve Steam Models Steam shut off valve for each condensate return line Flexible steam hoses with a 125 psig pounds per sguare inch gauge 8 78 kg sq cm working pressure for connecting steam coils Refer to Figure 15 for sizing and connection configurations Steam trap for steam coil outlet to condensate return line Optional Vacuum breaker for condensate return line Table 1 70304601 Location Requirements The tumbler must be installed on a level floor Floor covering materials such as carpeting or tile should be removed To assure compliance consult local building code requirements The tumbler must not be installed or stored in an area where it will be exposed to water and or weather IMPORTANT DO NOT block the airflow at the rear of the tumbler with laundry or other articles Doing so would prevent adequate air supply to the combustion chamber of the tumbler A typical tumbler enclosure is shown in Figure 1 Note th
17. tumbler This gall iur servida appliance is not intended for use by young 17 Tumbler will not operate with lint panel open children or infirm persons without supervision DO NOT bypass lint panel safety switch to Young children should be supervised to ensure permit the tumbler to operate with the lint panel that they do not play with the appliance open 5 Before the tumbler is removed from service or 18 Do not put articles soiled with vegetable or cooking discarded remove the door to the drying oil in the tumbler as these oils may not be compartment and the door to the lint removed during washing Due to the remaining compartment oil the fabric may catch on fire by itself 6 Do not reach into the tumbler if the cylinder is 19 To reduce the risk of fire DO NOT put clothes revolving which have traces of any flammable substances 7 Do not install or store the tumbler where it will sohan machined de be exposed to water and or weather 8 Do not tamper with the controls thinner etc or anything containing wax or chemicals such as in mops and cleaning cloths or anything dry cleaned at home with dry cleaning solvent in the tumbler 9 Do not repair or replace any part of the tumbler or attempt any servicing unless specifically 20 Use the tumbler only for its intended purpose recommended in the user maintenance drying fabrics oe publishes Use tena 21 ALWAYS disconnect and lockout the electrical instructions that you understand
18. 0 80 2 5 63 50 2 5 63 50 2 5 63 50 2 5 63 50 3 76 20 1 400 000 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 3 76 20 3 76 20 1 500 000 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 3 76 20 3 76 20 1 600 000 2 50 80 2 5 63 50 2 5 63 50 3 76 20 3 76 20 3 76 20 1 700 000 2 50 80 2 5 63 50 2 5 63 50 3 76 20 3 76 20 3 76 20 1 800 000 2 5 63 50 2 5 63 50 3 76 20 3 76 20 3 76 20 3 76 20 1 900 000 2 5 63 50 2 5 63 50 3 76 20 3 76 20 3 76 20 3 76 20 2 000 000 2 5 63 50 2 5 63 50 3 76 20 3 76 20 3 76 20 3 5 88 90 2 200 000 2 5 63 50 3 76 20 3 76 20 3 76 20 3 5 88 90 3 5 88 90 2 400 000 2 5 63 50 3 76 20 3 76 20 3 76 20 3 5 88 90 3 5 88 90 2 600 000 2 5 63 50 3 76 20 3 76 20 3 5 88 90 3 5 88 90 3 5 88 90 2 800 000 2 5 63 50 3 76 20 3 76 20 3 5 88 90 3 5 88 90 3 5 88 90 3 000 000 2 5 63 50 3 76 20 3 5 88 90 3 5 88 90 3 5 88 90 4 101 60 For L P Gas correct the total Btu hr by multiplying it by 0 6 The answer is the equivalent Btu on the above chart The installation must conform with local codes or in the absence of local codes e with the latest edition of the National Fuel Gas Code ANSI Z223 1 NFPA 54 in the U S A with CAN CSA B149 1 or Natural Gas and Propane Installation Code in Canada and Australian Gas Association Australian L P Gas Association requirements in Australia 70304601 Table 7
19. 0N HUT30L HUT30N CTT45L MTT45N CTT45N NTT45N DRST45G2 BTT45D STT45D DRST45G2 BTT45L STT45L DRST45G2 BTT45N STT45N T45 ped Sna Not Applicable Not Applicable HTT45N UTT45L HUT45L UTT45N HUT45N IPD45STG2 ITT45L IPD45STG2 ITT45N Includes models with control suffixes 30 DX4 OPL NC NetMaster coin SX single drop prep for coin 3V DX4 vended NR NetMaster card ZC NetMaster network coin 3X DX4 prep for coin NX NetMaster prep for coin ZR NetMaster network card BC basic electronic coin NY NetMaster prep for card ZX NetMaster network prep for coin BL basic electronic central pay OM OPL micro ZY NetMaster network prep for card BX basic electronic prep for coin QT dual digital timer BY basic electronic prep for card SD single drop 4 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Customer Service If literature or replacement parts are required contact the source from which the machine was purchased or contact Alliance Laundry Systems at 920 748 3950 for the name and address of the nearest authorized parts distributor For technical assistance call 920 748 3121 Wiring Diagram The wiring diagram is located in the upper junction or upper contactor box The wiring diagram part number is located in the lower portion of the electrical data on the serial plate Introduction Serial Plate Location When calling or writing for information about
20. 1 minute of minimum cool down time for a total time of 9 minutes for a coin pulse For dipswitch settings refer to Table 14 The control reads the dipswitch settings at power up The control must be powered down to change the dipswitch settings To change the time for a coin pulse the desired dry time dipswitches must be set to ON position All other dipswitches must be in OFF position 70304601 Single Drop Timer Dipswitch Settings Heat Switch Number pened Nes Cael ET De Ha Ui drs 1 5 3 4 5 6 7 8 Cycle in Minutes 1 OFF OFF OFF OFF OFF OFF OFF OFF 1 factory default 2 ON OFF OFF OFF OFF OFF ON OFF 2 3 OFF ON OFF OFF OFF OFF OFF ON 3 4 ON ON OFF OFF OFF OFF ON ON 4 5 OFF OFF ON OFF OFF OFF 6 ON OFF ON OFF OFF OFF 7 OFF ON ON OFF OFF OFF 8 factory default ON ON ON OFF OFF OFF 9 OFF J OFF OFF ON OFF OFF 10 ON OFF OFF ON OFF OFF 11 OFF ON OFF ON OFF OFF 12 ON ON OFF ON OFF OFF 13 OFF OFF ON ON OFF OFF 14 ON OFF ON ON OFF OFF 15 OFF ON ON ON OFF OFF 16 ON ON ON ON OFF OFF 17 OFF OFF OFF OFF ON OFF 18 ON OFF OFF OFF ON OFF 19 OFF ON OFF OFF ON OFF 20 ON ON OFF OFF ON OFF 21 OFF OFF ON OFF ON OFF 22 ON OFF ON OFF ON OFF 23 OFF ON ON OFF ON OFF 24 ON ON ON OFF ON OFF 25 OFF OFF OFF ON ON OFF 26 ON OFF OFF ON ON OFF 27 OFF ON OFF ON ON OFF 28 ON ON OFF ON ON OFF 29 OFF OFF ON
21. 2W amp G in junction box area Remove the 208 Volt jumper and replace it with the 100 Volt jumper located T30 Models Only in the literature packet from cylinder Remove small access cover from back of the fan motor Locate the two internal jumper wires brown and blue connected to motor terminals 6 and 2 Move brown wire from terminal 6 to terminal 2 and blue wire from terminal 2 to terminal 4 Be careful not to confuse light blue motor harness wire with the dark blue internal jumper Carefully check motor wire connections with wiring diagram and verify that the motors are configured for low voltage operation before replacing covers Repeat steps 1 through 4 for each upper and lower unit Sign and date conversion sticker located on back of tumbler Follow the instructions covered in Connecting Electrical Service section 380 Volt 50 Hertz 400 415 Volt 50 Hertz 3 Phase Models 3 Phase 3W amp G 3W amp G 1 Prior to connecting electric service locate transformer configuration jumper T30 Models Only in junction box area Remove the 380 Volt jumper and replace it with the 415 Volt jumper located in the literature packet from cylinder 3 Repeat steps 1 and 2 for each upper and lower unit Sign and date conversion sticker located on back of tumbler 5 Follow the instructions covered in Connecting Electrical Service section 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 39 El
22. 5N 1 Size Stamped on Burner Orifice Figure 8 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Installation 23 Exhaust Requirements A drying tumbler produces combustible lint To reduce the risk of fire the tumbler must be exhausted to the outdoors W057 To reduce the risk of fire and accumulation of combustible gases DO NOT exhaust tumbler air into a window well gas vent chimney or enclosed unventilated area such as an attic wall ceiling crawl space under a building or concealed space of a building w059 Layout Whenever possible install tumblers along an outside wall where duct length can be kept to a minimum and make up air can be easily accessed Elbows and long vents tend to increase drying time Construction must not block the airflow at the rear of the tumbler Doing so would prevent adequate air supply to the tumbler s combustion chamber Make Up Air A tumbler is forced air exhausted and requires provisions for make up air to replace air exhausted by the tumbler IMPORTANT Do not obstruct the flow of combustion and ventilation air Make up air openings should be as close to the tumbler s as possible The required make up air opening to the outside for each tumbler includes both pockets is 220 square inches 1418 sq cm for T30 models 288 square inches 1856 sq cm for T45 models Make up air openings with louvers will restrict airflow The opening must
23. Drying Tumblers Stacked 30 Pound Capacity Stacked 45 Pound Capacity Starting Serial No 0602004144 Refer to Page 4 for Model Identification NOTA Para bajar una copia de estas instrucciones en espanol visite www comlaundry com Keep These Instructions for Future Reference If this machine changes ownership this manual must accompany machine ili il a Mm Cc e Part No 70304601R8 Laund ry S ys tems www comlaundry com September 2008 UOT eIIEISUI Installation must conform with local codes or in the absence of local codes with In the U S A installation must conform to the latest edition of the American National Standard Z223 1 NFPA 54 National Fuel Gas Code and Standard ANSI NFPA 70 National Electric Code In Canada installation must comply with Standards CAN CSA B149 1 or Natural Gas and Propane Installation Code and CSA C22 1 latest edition Canadian Electric Code Part I In Australia installation must comply with the Australian Gas Association Installation Code for Gas Burning Appliances and Equipment A wanne FOR YOUR SAFETY the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or death W033 e Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not
24. ON ON OFF 30 ON OFF ON ON ON OFF 31 OFF ON ON ON ON OFF 32 ON ON ON ON ON OFF 33 OFF OFF OFF OFF OFF ON 34 ON OFF OFF OFF OFF ON 35 OFF ON OFF OFF OFF ON Table 14 Continued 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 47 Single Drop Timer Table 14 Continued Heat Switch Number uas EE Be a sje 36 ON ON OFF OFF OFF ON 37 OFF OFF ON OFF OFF ON 38 ON OFF ON OFF OFF ON 39 OFF ON ON OFF OFF ON 40 ON ON ON OFF OFF ON 41 OFF OFF OFF ON OFF ON 42 ON OFF OFF ON OFF ON 43 OFF ON OFF ON OFF ON 44 ON ON OFF ON OFF ON 45 OFF OFF ON ON OFF ON 46 ON OFF ON ON OFF ON 47 OFF ON ON ON OFF ON 48 ON ON ON ON OFF ON 49 OFF OFF OFF OFF ON ON 50 ON OFF OFF OFF ON ON 51 OFF ON OFF OFF ON ON 52 ON ON OFF OFF ON ON 53 OFF OFF ON OFF ON ON 54 ON OFF ON OFF ON ON 55 OFF ON ON OFF ON ON 56 ON ON ON OFF ON ON 57 OFF OFF OFF ON ON ON 58 ON OFF OFF ON ON ON 59 OFF ON OFF ON ON ON 60 ON ON OFF ON ON ON 61 OFF OFF ON ON ON ON 62 ON OFF ON ON ON ON 63 OFF ON ON ON ON ON 64 ON ON ON ON ON ON Total Cyc
25. Z223 1 NFPA 54 in the U S A with CAN CSA B149 1 or Natural Gas and Propane Installation Code in Canada e and Australian Gas Association Australian L P Gas Association requirements in Australia Obtain specific gas service pipe size from the gas supplier Refer to Table 7 for general pipe size 30 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT The following must be furnished and installed by the customer for the gas service line to each tumbler Refer to Figure 13 e Sediment traps e Shut off valves e Supply pressure taps It is important that equal pressure be maintained at all tumbler gas connections This can best be done by installing a one inch 25 mm pipe gas loop Refer to Figure 14 To reduce the risk of fire or explosion if the tumbler is to be connected to Liquefied Petroleum L P gas a vent to the outdoors must be provided in the room where the tumbler is installed NATURAL GAS line pressure must be maintained at 6 5 water column inches 1 62 kPa with no less than 5 water column inches 1 24 kPa and no more than 10 5 water column inches 2 61 kPa with all gas appliances running tumblers water heaters space heaters furnace etc An in line pressure regulator may be required if the line pressure exceeds 8 water column inches 2 0 kPa with all gas appliances running LIQUID PETROLEUM GAS L P line pressure must be maintained at 11 water column inches 2 74 kPa w
26. ailure to remove wire tie from rear of persists remove tumbler from service machine Refer to Figure 4 e Clogged lint screen 8 Load the cylinder with a full load of clean rags e Lack of make up air Refer to Exhaust and run to remove oil or dirt from cylinder Requirements section e Obstruction in the exhaust duct Refer to A WA R NIN G Exhaust Reguirements section Do not operate tumbler if airflow switch is faulty An explosive gas mixture could collect in tumbler if airflow switch does not operate properly W407 Prepurge Trial for To Reset Models Location Time Ignition Lockout seconds seconds Condition Press lighted CE and reset button in 18 10 Australia rear contactor T30 box All others 1 3 10 Open Igadimig door l l TMB2104N T45 1 3 10 Open loading 1 Wire Tie door Table 2 Figure 4 4 Turn on electrical supply to tumbler 5 Open the supply valve for gas or steam heated tumblers 6 After performing the previous checks start the tumbler by pressing START Refer to the Operating Manual for detailed instructions Release the start button and open the loading door The cylinder should stop rotating within seven seconds after the door is opened a maximum of 2 inches 51 mm If it does not adjust the loading door switch Refer to Adjustments section 7 Gas tumblers Start the tumbler and check the burner flame Adjust the
27. aintained schedule monthly inspections and cleaning of the ductwork Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 25 Exhaust Requirements QA OND Removable strip of panel in framing wall to permit removal of tumbler from framing wall Partition or bulkhead Minimum distance between exhaust opening and roof ground or other obstruction 36 in 914 mm 2 in 61 mm minimum clearance on both sides of duct Exhaust airflow maximum length of duct 14 ft 4 3 m TMB2103N Figure 9 NOTE Do not install wire mesh or screen in exhaust duct opening to avoid lint build up or impacting proper discharge of air from tumblers NOTE Where exhaust duct pierces a combustible wall or ceiling the opening must be sized per local codes NOTE Inside of duct must be smooth Do not use sheet metal screws to join sections Consult your local building code for regulations which may also apply 26 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Manifold Venting While it is preferable to exhaust tumblers individually to the outdoors a main collector duct may be used if it is sized according to Figure 11 or Figure 12 This illustration indicates minimum diameters and should be increased if the collector length exceeds 14 feet 4 3 m and two 90 elbows The diameter of a round duct must be increased by 10 for
28. al emergency stop button may be installed as specified on the machine wiring diagram NOTE Activation of the emergency stop button stops all machine control circuit functions but DOES NOT remove all electrical power from machine Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 35 Electrical Requirements Service Ground Location Model Heat Source Ground and Terminal Block Locations Terminal Block Ground Screw T30 T45 T30 Gas or Steam D Joa Non CE T45 Gas ed ER Teh oHa la LEED epp
29. and have the ee skills to carry out power to the tumbler before servicing Disconnect power by shutting off appropriate breaker or fuse w EE ede oer e 22 Install this tumbler according to the f INSTALLATION INSTRUCTIONS All manufacturer of the fabric softener or product connections for electrical power grounding and 11 Toreduce the risk of fire DO NOT DRY plastics gas supply must comply with local codes and be or articles containing foam rubber or similarly made by licensed personnel when required textured rubberlike materials 12 Always clean the lint filter daily 13 Keep area around the exhaust opening and adjacent surrounding area free from the accumulation of lint dust and dirt 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 7 Safety Information 23 24 25 26 27 28 Remove laundry immediately after tumbler stops Always read and follow manufacturer s instructions on packages of laundry and cleaning aids Heed all warnings or precautions To reduce the risk of poisoning or chemical burns keep them out of reach of children at all times preferably in a locked cabinet Do not tumble fiberglass curtains and draperies unless the label says it can be done If they are dried wipe out the cylinder with a damp cloth to remove particles of fiberglass Always follow the fabric care instructions supplied by the garment manufacturer Never operate the tumbler with any
30. at the enclosure touches the tumbler top and side panels Also note the minimum and maximum dimensions Local codes and ordinances must be complied with To reduce the risk of serious injury install lockable door s to prevent public access to rear of tumblers W055 IMPORTANT Install tumblers with sufficient clearance for servicing and operation Refer to Figure 1 IMPORTANT Keep tumbler area clear and free from combustible materials gasoline and other flammable vapors and liquids Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 15 Installation To reduce the risk of severe injury clearance of tumbler cabinet from combustible construction must conform to the minimum clearances U OLS ay EGO LD Lp ED EG DLE 7 TMB2110N NOTE Shaded areas indicate adjacent structure 1 0 5 in 13 mm recommended between machines for removal or installation 2 Allow 2 4 in 51 102 mm opening at top of machine to aid in removal or installation A removable trim piece may be used to conceal the opening zero clearance allowed for trim 3 4 in 102 mm Maximum Header Thickness 4 12 in 305 mm Minimum Clearance 5 24 in 610 mm Minimum 36 in 914 mm recommended for maintenance purposes 6 Provision for Make Up Air Minimum 1 5 square feet T30 models minimum 2 square feet T45 models Location for reference only May be anywhere behi
31. be increased to compensate for area taken up by louvers Make up air openings for a room containing tumbler s and or gas fired hot water heater or other gravity vented appliances must be increased sufficiently to prevent downdrafts in any of the vents when all tumblers are in operation Do not locate gravity vented appliances in the same room as tumblers If it is necessary to duct make up air to the tumbler s increase the area of the ductwork by 25 to compensate for any restriction in air movement 24 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Venting To reduce the risk of fire due to increased static pressure do not install in line secondary lint filters or lint collectors W730 IMPORTANT Installing in line filters or lint collectors will cause increased static pressure which will decrease tumbler efficiency and will void machine warranty For maximum efficiency and minimun lint accumulation tumbler air must be exhausted to the outdoors by the shortest possible route Proper sized exhaust ducts are essential for proper operation All elbows should be sweep type Exhaust ducts must be assembled so the interior surfaces are smooth so the joints do not permit the accumulation of lint DO NOT use plastic or thin foil flexible ducts Use exhaust ducts made of sheet metal or other non combustible material Use duct tape or pop rivets on all seams and joints Verify that old ducts are tho
32. be satisfied When vend is satisfied the control goes into START Mode Start Mode In START Mode light on the vend has been satisfied but the start button has not been pressed Time remaining in the cycle will not change until the start button is pressed When the start button is pressed the machine goes into RUN Mode Run Mode In RUN Mode light on the machine is running a cycle and the time remaining is counting down When time remaining counts down to zero the control goes into READY Mode 46 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Setting Dry Time Dipswitches To change the dry time on the tumbler combinations of dipswitches can be set on the control There are eight dipswitches on the tumbler control The first six switches are used to program the amount of additional heat time given for each coin pulse The additional drying time is added to the factory default minimum heat time of one minute A valve of 1 to 64 minutes of additional drying time is available for each coin drop pulse The last two switches are used to program the amount of additional cool down time The additional cool down time is added to the factory default minimum cool down time of 1 minute A value of 1 to 3 additional minutes is available The control is shipped from the factory programmed with 1 minute of minimum heat time preset with 7 additional minutes of drying time dipswitches 1 2 and 3 in ON position and
33. dry Systems LLC DO NOT COPY or TRANSMIT 70304601 Steam Requirements NOTE Machines require a constant 80 to 100 psig 5 62 to 7 03 kg sq cm steam service for optimum operation The maximum allowable steam pressure for use with 60 Hertz or 50 Hertz tumblers is 125 psig 8 6 bar In no case may the pressure exceed the above value Obtain specific steam service pipe sizes from the steam system supplier or a qualified steam fitter e Refer to Figure 15 for proper steam pipe configurations e To prevent condensate draining from headers to tumbler piping should have a minimum 12 inch 305 mm rise above respective header Do not make steam connection to header with a horizontal or downward facing tee or elbow e Whenever possible horizontal runs of steam lines must drain by gravity to respective steam header Water pockets or an improperly drained steam header will provide wet steam causing improper operation of tumbler If pockets or improper drainage cannot be eliminated install a bypass trap to drain condensate from the low point in the steam header to the return e In both steam supply and steam return line it is recommended that each have a pipe union and shut off valve This will enable you to disconnect the steam connections and service the tumbler while your laundry facility is in operation e Connect the steam solenoid valve to the related steam coil inlet connection with nipples flex hoses unions and t
34. e cleaned periodically by qualified service personnel Important Safety Instructions 14 Save These Instructions 15 If not installed operated and maintained in accordance with the manufacturer s instructions or if there is damage to or mishandling of this product s components use of this product could expose you to substances in the fuel or from fuel combustion which can cause death or serious Hazardous Voltage Can cause shock burn or cause death Allow machine power to remain off for two minutes prior to working in and around AC inverter drive W359 illness and which are known to the State of California to cause cancer birth defects or other reproductive harm 1 Read all instructions before using the tumbler 2 Refer to the GROUNDING INSTRUCTIONS 16 Tumbler will not operate with the loading door for the pioper rounding of the tumbler open DO NOT bypass the door safety switch to i permit the tumbler to operate with the door open 3 Do not dry articles that have been previously The tumbler will stop tumbling when the door is cleaned in washed in soaked in or spotted with opened Do not use the tumbler if it does not stop gasoline dry cleaning solvents other flammable tumbling when the door is opened or starts or explosive substances as they give off vapors tumbling without pressing or turning the START that could ignite or explode mechanism Remove the tumbler from use and 4 Do not allow children on or in the
35. e for 75 C Conductors and are intended for use as a guideline only Electrical connections should be made only by a gualified electrical contractor in accordance with all applicable local and national reguirements NOTE Electrical specifications below are subject to change without notice Always refer to product serial plate for most current specifications of product being installed NOTE Connect to individual branch circuit NOTE 3 Phase Only Each tumbler must be connected to its own individual branch circuit breaker not fuses to avoid the possibility of single phasing and causing premature failure of the motor s For 21 kW T30 Electric Models j Recommended Serial Plate eed ke Current nee Sker ha rhe Breaker Minimum Voltage Amps g Poles Conductor Size Required Amps ANE 200 208V 60Hz 3ph eae 62 80 3 4 21 2 and ground 200V 50Hz 3ph EA LL 60 80 3 4 21 2 and ground 230 240V 50Hz 3ph Pele ss 70 3 4 21 2 and ground 240V 60Hz 3ph L1 L2 L3 54 70 3 4 21 2 and ground 380V 50 or 60Hz 3ph 1L 33 45 3 8 8 37 and ground 400 415V 50Hz 3ph ROTE 31 40 3 8 8 37 and ground 460 480V 60Hz 3ph EES 27 35 3 8 8 37 and ground These serial plate voltages are only options available on the T30 electric models Current Amp is for one pocket only Per heater on T30 electric models each has two heaters 42 Table 12 Copyright Alliance Laun
36. ectrical Requirements Electrical Requirements for Gas and Steam Models Refer to Table 10 and Table 11 NOTE Minimum wire sizes are obtained from Canadian Electrical Code for 75 C Conductors and are intended for use as a guideline only Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements NOTE Electrical specifications below are subject to change without notice Always refer to product serial plate for most current specifications of product being installed NOTE Use copper conductors only NOTE 3 Phase Only Each tumbler must be connected to its own individual branch circuit breaker not fuses to avoid the possibility of single phasing and causing premature failure of the motor s For T30 Gas and Steam Models For Total Machine Recommended Recommended Serial Plate Sila Eer Current Fuse or Breaker Minimum Voltage Required Amps Breaker Rating Poles Conductor Size q Amps AWG mm 120V 60 Hz 1ph L1 Neutral 16 0 20 1 12 3 31 and ground 208 240V 60H2z L1 L2 Neutral 8 0 10 2 14 2 08 1ph and ground I 2 100V 60Hz 1ph L1 Neutral 22 0 30 1 10 5 26 and ground 200 220 V 60Hz L1 Neutral 11 6 15 1 14 2 08 1ph and ground I 37 100V 50Hz 1ph L1 Neutral 24 2 35 1 8 8 37 and ground I 12 3 31 200V 50Hz 1ph Hi Neutal 15 0 20
37. ed to be configured to operate with those gases In the CE there are Natural Gas configurations that do not allow for machine regulation and L P Gas configurations that must be regulated For L P Gas third family B P at 50 mbar order regulated Natural Gas machines and convert according to Table 3 Basic Configuration 1 Determine the necessary conversion operations to convert from the factory supplied configuration to the desired configuration 2 Perform the conversions required so the machine is properly configured for the desired country and gas refer to Specific Conversion Procedures section e How to Convert Gas Valve from Regulated to Unregulated NOTE Conversion from regulated to unregulated is only needed when regulated tumblers were ordered but unregulated tumblers were needed or if the gas supply type is changed at a later date e How to Change Burner Orifice Size e How to Adjust Gas Valve Governor Regulator e How to Change Regulator Spring DE AT Only 3 If applicable peel off the appropriate country sticker included with machine and apply it to the serial plate over the existing country information 4 If applicable peel off the appropriate conversion sticker included with machine and apply it to the data plate over the ADJUSTED FOR GAS information 5 Commission tumbler for use 20 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT When converting the tumbler t
38. ee e Strainers may require cleaning due to materials from hoses or pipes e Install vacuum breaker optional bucket trap with built in strainer and check valve For successful operation of tumbler install trap 18 inches 457 mm below coil and as near to the tumbler as possible Inspect trap carefully for inlet and outlet markings and install according to trap manufacturer s instructions If steam is gravity returned to boiler omit trap but install optional vacuum breaker and check valve in return line near tumbler Gravity return requires entire return plumbing be below steam coil outlet e Install union and shut off valve in return line and make final pipe connections to return header NOTE To prevent water hammering route return lines below outlets of steam coils Piping Recommendations e Trap each steam coil individually Always keep the trap clean and in good working condition e When tumbler is on the end of a line of equipment extend header at least 4 feet 1 2 meters beyond tumbler Install shut off valve union check valve and bypass trap at end of line If gravity return to boiler omit trap e Insulate steam supply and return line for safety of operator and safety while servicing tumbler e Keep tumbler in good working condition Repair or replace any worn or defective parts All system components must have a 125 psig 8 6 bar working pressure Shut off valves must be installed upstream of the s
39. en installing gas tumblers in countries and or on gases different than the machine s factory configuration Tumblers are supplied from the factory for operation on Natural Gas 1000 Btu cu ft 8914 kcal m or L P Gas 2500 Btu cu ft 22 250 kcal m in the countries of GB IE PT ES IT GR LU CH To install machines in any other country or on any other gas requires some level of modification Burner orifices stickers block open kits regulator springs and other parts needed for conversions are to be ordered separately Models are built in two different configurations e Regulated Natural Gas Burner orifice is sized for Natural Gas second family group H E at 20 mbar inlet pressure Regulator governor is operational Gas valve CAN be field converted to a non regulating type e Unregulated L P Liquefied Petroleum Gas Burner orifice is sized for L P third family group 3 at 28 37 mbar inlet pressure Regulator governor is blocked open Gas valve CANNOT be field converted to a regulating type Serial plates supplied from the factory are configured for the countries of GB TE PT ES IT GR LU CH These instructions pertain to the situations when the country of use or gas supply is different than that on the serial plate Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 19 Installation Table 3 describes the different gases that are available in different CE countries and how the machines ne
40. erate of 4 per 1000 feet 305 meters of altitude Table 8 34 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Electrical Requirements To reduce the risk of electric shock fire explosion serious injury or death Disconnect electric power to the tumbler before servicing Close gas shut off valve to gas tumbler before servicing e Close steam valve to steam tumbler before servicing Never start the tumbler with any guards panels removed Whenever ground wires are removed during servicing these ground wires must be reconnected to ensure that the tumbler is properly grounded woo2 To reduce the risk of fire and electric shock check with a qualified serviceman for proper grounding procedures Improper connection of the equipment grounding conductor may result in a risk of electric shock W068 To reduce the risk of fire and electric shock if electrical supply is coming from a three phase service DO NOT connect a High Leg or Stinger Leg to a single phase machine On a three phase machine if there is a High Leg or Stinger Leg it should be connected to L3 Wwo69 Grounding Instructions NOTE To ensure protection against shock this tumbler MUST be electrically grounded in accordance with the local codes or in the absence of local codes with the latest edition of the National Electrical Code ANSI NFPA No 70 In Canada the electrical co
41. he Ne pas toucher aux interrupteurs lectriques ne pas utiliser le t l phone des lieux Evacuer la pi ce le b timent ou la zone de tous les occupants Appeler imm diatement le fournisseur de gaz de la maison d un voisin Respecter les instructions communiqu es par le fournisseur Si vous ne pouvez pas joindre le fournisseur de gaz appeler le service d incendie L installation et l entretien doivent tre effectu s par un installateur service d entretien qualifi s ou par le fournisseur de gaz W052R5QU POUR VOTRE SECURITE Ne pas entreposer ou utiliser d essence ou toutes autres vapeurs et liquides inflammables a proximit de cette unit ou de tout autre appareil W053R2QU IMPORTANT Information must be obtained from a local gas supplier on instructions to be followed if the user smells gas These instructions must be posted in a prominent location Step by step instructions of the above safety information must be posted in a prominent location near the tumbler for customer use Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 1 ERLA ER RR N N N RE RE N 4 Tab l e of Model Identification 4 C GuStOMEr Service su eke Ee eed Ee N oek EL Se see See Ese 5 on t en t S Wiring DEE EO AE N OO nA 5 Serial Plate Location ee ste se n eee ete ected ee GEE etek 5 Safety Information sees ee ee ee ee Re ee ee AA ee ee ee ee 6 Explanation of Safety Messages cs se
42. housing to stabilize the tumbler Refer to Figure 3 After leveling with the four cabinet leveling legs lower the fifth leveling leg so it contacts the floor and then secure the screws CAUTION The stacked drying tumbler has a 5th leveling leg on the blower housing It is very important to properly adjust this leg Unit is back heavy and could rock or tip W250 T4671 1 Fifth Leg Figure 3 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 17 Installation Before Placing Tumbler into Service IMPORTANT The electronic ignition system will attempt to light the gas by sparking for the trial 1 Remove or open all panels and check accessible for ignition period Refer to Table 2 If gas does bolts nuts screws terminals and fittings for tightness not ignite within this period the ignition control will go into a safety lockout and the valve will no 2 Replace all panels and guards longer open until the control is reset It may be 3 Remove and discard wire tie from the airflow necessary to retry several times to bleed air from switch so it can swing freely Refer to Figure 4 the gas lines To reset open and close the loading d d restart tumbler IMPORTANT Airflow switch operation may be RE wena ree affected by If lockout condition persists check that the manual gas shut off valve is in the ON position and that the gas service is properly connected If condition still e F
43. ith no less than 10 water column inches 2 49 kPa and no more than 13 water column inches 3 23 kPa with all gas appliances running tumblers water heaters space heaters furnace etc For converting Non CE models from Natural Gas to L P Gas T30 M4707P3 T45 M4880P3 CE GASES refers to Installing CE Gas Drying Tumblers sections the above data does not apply to the CE 70304601 Gas Requirements Turn on gas and check all pipe connections internal and external for gas leaks with a non corrosive leak detection fluid Purge air in gas service line by operating the tumblers in the drying mode If burner does not light and unit goes into lockout open and close the door and restart Repeat these steps until burner ignites Use pipe compound resistant to actions of L P gas on all pipe threads Check all pipe connections internal and external for gas leaks using a non corrosive leak detection fluid To reduce TMB2007N the risk of explosion or fire DO NOT USE 1 Gas Line to Tumbler AN OPEN FLAME TO CHECK FOR GAS 2 Shut Off Valve LEAKS Gas connections should be 3 Gas Supply Piping System checked twice a year for leakage 4 Gas T Fitting 5 6 in 152 mm Minimum Gas Pipe 6 Gas Pipe Cap 7 Sediment Trap 8 Supply Pressure Tap Figure 13 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 31 Gas Requirements Gas Supply Pipe Sizing and Looping
44. k and the motor relay or contactor Refer to figure below 120 V LOCATION AS RECEIVED 208 or 240 V LOCATION AS CONVERTED TO MOTOR RELAY OR CONTACTOR BLK RED TERMINAL BLOCK Disconnect the black red lead from L1 of the terminal block and connect to L2 of the terminal block Repeat steps 1 and 2 for upper and lower junction box areas Sign and date conversion sticker located on back of tumbler Follow the instructions covered in Connecting Electrical Service section 240 Volt 60 Hertz 200 208 Volt 60 Hertz 3 Phase Models 3 Phase 3W amp G 3W amp G Prior to connecting electric service locate transformer configuration jumper in junction box area Remove the 240 Volt jumper and replace it with the 208 Volt jumper located in the literature packet in cylinder Repeat steps 1 and 2 for each upper and lower unit Sign and date conversion sticker located on back of tumbler Follow the instructions covered in Connecting Electrical Service section 38 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Electrical Requirements If serial plate voltage is Tumbler can be converted to the following voltages 200 220 Volt 60 Hertz 100 Volt 60 Hertz 1 Phase INTERNATIONAL Models 1 Phase 2W amp G 2W amp G 100 Volt 50 Hertz 1 Phase INTERNATIONAL Models 200 Volt 50 Hertz 2W amp G 1 Phase Prior to connecting electric service locate transformer configuration jumper
45. le Time Heat Time Cool Down Time 48 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Table 14 70304601 Adjustments Loading Door Switch The door switch should be adjusted so the cylinder stops when door is opened 2 inches 51 mm plus or minus 0 25 inch 6 mm This switch is a normally open switch and is closed by the hinge cam when the door is closed If adjustment is required refer to Figure 16 and proceed as follows 1 Close door and start tumbler slowly open loading door Cylinder and heat system should shut off when door is open 2 inches 51 mm plus or minus 0 25 inch 6 mm 2 Slowly close the loading door When door is 2 inches 51 mm from being fully closed the door switch actuating bracket located on the door should depress the button and the switch arm with an audible click 3 Ifthe actuating bracket does not operate the switch at the appropriate door closure bend the actuating switch bracket in or out to achieve proper actuation N 1 Airflow Switch Actuating Bracket TMB2077N Figure 16 70304601 Airflow Switch The airflow switch is set at the factory for proper operation No adjustment necessary The airflow switch operation may be affected by shipping tape still in place lack of make up air or an obstruction in the exhaust duct These should be checked and the required corrective action taken The tumbler must not be operated
46. n acorn nut TMB1990N 1 Door Strike Screw Acorn Nut Figure 17 50 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Removing Tumbler from Service If the tumbler is to be removed from service perform the following steps where applicable Turn off electrical supply external to machine Turn off electrical disconnect on machine Turn off gas supply external to machine Turn off manual gas shut off valve on machine Turn off steam supply external to machine Remove all electric gas and steam connections 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 51
47. nd tumbler 7 0 25 in 6 mm recommended for removal or installation purposes zero clearance allowed Figure 1 16 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Position and Level the Tumbler Unscrew the four shipping bolts one at each corner Remove tumbler from skid carefully to avoid putting pressure on the lower blower housing or motor assembly NOTE Do not throw bolts away they are the leveling legs Remove four nuts from the literature package and screw one fully on to each leveling leg Screw the four leveling legs bolts back into the level adjusting fittings from the bottom Slide tumbler to its permanent location Adjust the leveling legs until the unit is level within 0 125 inch 32 mm higher in the front Refer to Figure 2 Tumbler must not rock Lock leveling legs with nuts previously installed NOTE The front of the tumbler should be slightly higher than the rear approximately 0 125 inch 3 18 mm This will prevent the clothes while tumbling from wearing on the door glass gasket IMPORTANT Keep tumbler as close to floor as possible The unit must rest firmly on floor so weight of tumbler is evenly distributed TMB1975N 1 Leveling Leg Figure 2 70304601 Installation The stacked tumbler has a fifth leveling leg which is shipped in the up position The fifth leveling leg MUST BE installed properly on the lower left side of the blower
48. nnections are to be made in accordance with CSA C22 1 latest edition Canadian Electrical Code or local codes 70304601 This tumbler must be grounded In the event of malfunction or breakdown grounding will reduce the risk of electric shock by providing a path of least resistance for electric current This tumbler must be connected to a grounded metal permanent wiring system or an equipment grounding conductor must be run with the circuit conductors and connected to the appropriate ground location e Metal conduit and or BX cable is not considered ground e Connecting the Neutral from the electrical service box to the tumbler ground screw does not constitute a ground e A dedicated ground conduit wire must be connected between the electrical service box ground bar and tumbler ground screw To reduce the risk of electrical shock de energize the electrical circuit being connected to the tumbler before making any electrical connections All electrical connections should be made by a qualified electrician Never attempt to connect a live circuit CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing wo71 For CE Models Only All manually operated models are factory equipped with an emergency stop button on the front panel If the emergency stop function is desired on coin operated models an extern
49. ns and Dimensions Steam Connection Locations A B TMB1972N Inlet Outlet Models A C B D T30 73 93 in 6 29 in 62 71 in 2 39 in Upper 1877 mm 160 mm 1592 mm 61 mm T30 36 35 in 6 29 in 25 13 in 2 39 in Lower 923 mm 160 mm 638 mm 61 mm NOTE All connections use 3 4 inch NPT pipe 14 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Installation Pre Installation Inspection Upon delivery visually inspect the crate carton and parts for any visible shipping damage If the crate carton or cover is damaged or signs of possible damage are evident have the carrier note the condition on the shipping papers before the shipping receipt is signed or advise the carrier of the condition as soon as it is discovered Remove the crate and protective cover as soon as possible and check the items listed on the packing list Advise the carrier of any damaged or missing articles as soon as possible A written claim should be filed with the carrier immediately if articles are damaged or missing IMPORTANT Warranty is void unless tumbler is installed according to instructions in this manual Installation should comply with minimum specifications and requirements detailed herein and with applicable local gas fitting regulations municipal building codes water supply regulations electrical wiring
50. o TMB2041N Ground Lug ee i er EET ETO BT EE Power Distribution SE 1E T30 P BI k 5 PL 2 222 Electric oc da o Non CE cij ota ie ie ofh TMB2113N Power 7 Disconnect T30 T45 T30 Gas or Steam CE T45 Gas Ground Screw ol 6 a Oho TMB2114N Oldb Power Distribution Block FT nd sae T30 Ground Lug Electric i CE TMB2115N 36 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Connecting Electrical Service The following steps outline the procedure for connecting electrical service to the tumbler e 3 Phase models Each tumbler must be connected to its own individual branch circuit breaker not fuses to avoid the possibility of single phasing and causing premature failure of the motor s e Electrical service must be connected using the appropriate permanent rigid metal conduit system e Service conductors must be copper only For an existing service determine your service voltage and conductor amperage Carefully review the tumbler serial plate ratings and Electrical Requirements section of this manual If service is inadequate it must be upgraded by a qualified electrical contractor Never connect an improper or inadequate service to any machine Configuring Your Tumbler for Other Service Voltages Several gas and steam tumbler models have been designed to be field convertible to other service voltages Refer to Table 9 for these models
51. o a different gas or pressure first verify that the supply inlet pressure is equipped with a pressure regulator located ahead of the tumbler that will maintain the gas supply at the inlet pressure specified W430 SPECIFIED LOCAL INLET PRESSURE T103K 1 Gas Shut Off Valve Ahead of pressure tap 2 Pressure Tap 3 Gas Shut Off Valve Shown in closed position Figure 6 70304601 Gases and Configurations Installation Burner Supply as F Burner Country Gas Type Group Pressure Oritice Capacity Diameter Quantity Orifice Code Pressure Model mm mbar Part No mbar DK NO Natural Gas H 20 8 0 T30 4 0 2 M402992 SE FI CZ T45 4 6 M411371 EE LV LT LP Gas B P 30 No Governor T30 2 2 2 M401011 SISK T45 2 5 M401007 Natural Gas E 20 8 0 T30 4 0 2 M402992 T45 4 6 M411371 DE L P Gas LL 30 No Governor T30 2 2 2 M401011 T45 2 5 M401007 Natural Gas L 25 11 0 T30 4 0 2 M402992 NE T45 4 6 M411371 L P Gas B P 30 No Governor T30 22 2 M401011 T45 2 5 M401007 Natural Gas E 20 or 25 No Governor T30 33 2 MAO1021 T45 3 7 M401000 BE FR L P Gas 28 or 37 No Governor T30 2 2 2 M401011 T45 2 5 M401007 Natural Gas H 20 8 0 T30 4 0 2 M402992 GB IE PT T45 4 6 M411371 ES IT GR LU CH L P Gas 28 or 37 No Governor T30 22 2 M401011 T45 2 5 M401007 Natu
52. ral Gas H 20 8 0 T30 4 0 2 M402992 pe T45 4 6 M411371 L P Gas B P 30 No Governor T30 2 2 2 M401011 T45 2 5 MAO1007 L P Gas B P 30 No Governor T30 22 2 M401011 CY S MT T45 25 M401007 Natural Gas H 25 8 0 T30 4 0 2 M402992 T45 4 6 M411371 HU L P Gas B P 30 No Governor T30 2 2 2 M401011 T45 2 5 M401007 Natural Gas H 20 8 0 T30 4 0 2 M402992 ni T45 4 6 M411371 L P Gas 3P 37 No Governor T30 2 2 2 M401011 T45 2 5 M401007 Burner orifice information at 0 2000 feet 0 600 meters altitude For Natural Gas Group E applications convert using L P Gas model and replace burner orifice s Table 3 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 21 Installation Specific Conversion Procedures 2 Follow instructions in Conversion Kit Part No 431485 Johnson Part No GM 70 CBP How to Convert Gas Valve from Regulated to Unregulated NOTE This kit does not contain any burner orifices NOTE Conversion from regulated to unregulated EN l is only needed when regulated tumblers were 3 Change burner orifice size as required by the ordered but regulated tumblers were needed appropriate table according to How to Change Burner Orifice Size Johnson GM7000 gas valve 1 Disconnect electrical power from tumbler Close gas shut off valve to tumbler Refer to Figure 7 4 Commission tumbler for use
53. rements 1 NOTE Where the exhaust duct pierces a combustible wall or ceiling the opening MUST be sized per local codes I H LIAS I a 2 3 ONE MANIFOLD ASSEMBLY Outlet Duct Diameter 45 Typical TMB2019N Figure 11 Duct T30 T45 Station 8 in 203 mm Duct 10 in 254 mm Duct A 8 in 203 mm 10 in 254 mm B 12 in 305 mm 15 in 381 mm Cc 15 in 381 mm 18 in 457 mm D 17 in 432 mm 21 in 533 mm E 19 in 483 mm 24 in 610 mm F 21 in 533 mm 26 in 660 mm G 23 in 584 mm 28 in 711 mm H 24 in 610 mm 30 in 762 mm I 26 in 660 mm 32 in 813 mm J 27 in 686 mm 33 in 838 mm K 28 in 711 mm 35 in 889 mm L 30 in 762 mm 36 in 914 mm Table 5 28 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Exhaust Requirements I J kx CONTINUE SG TOA N 1 NOTE Where the exhaust duct pierces a 2 combustible wall or ceiling the opening 3 MUST be sized per local codes TWO MANIFOLD ASSEMBLIES Outlet Duct Diameter CONTINUE TOA TMB2018N 17 in 432 mm 22 in 559 mm Figure 12 Duct T30 T45 Station 8 in 203 mm Duct 10 in 254 mm Duct A 12 in 305 mm 15 in 381 mm 22 in 559 mm 26 in 660 mm 25 in 635 mm 30 in 762 mm 27 in 686 mm 34 in 864 mm 30 in 762 mm 37 in 940 mm 33 in 838 mm
54. roughly cleaned out before installing new tumbler s Improperly sized or assembled ductwork causes excess back pressure which results in slow drying lint collecting in the duct lint blowing back into the room and increased fire hazard W355 NOTE Exhaust ducts must be constructed of sheet metal or other noncombustible material Such ducts must be equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel not less than 0 0195 inches 0 495 mm thick Local codes may require additional thickness Where the exhaust duct pierces a combustible wall or ceiling the opening must be sized per local codes The space around the duct may be sealed with non combustible material Refer to Figure 9 70304601 IMPORTANT For best performance provide an individual exhaust duct for each tumbler Do not install a hot water heater in a room containing tumblers It is better to have the water heater in a separate room with a separate air inlet Individual Venting For maximum efficiency and performance it is preferred to exhaust tumbler s individually to the outdoors IMPORTANT At no point may the cross sectional area of installed venting be less than the cross sectional area of the exhaust outlet of the tumbler The exhaust duct must be designed so the static back pressure measured 12 inches 305 mm from the exhaust outlet does not exceed the maximum allowable pressure specified on the installation sticker
55. round wire to the grounding screw or lug Attach service conductors to appropriately labeled positions on the terminal block Make sure all connections are secure 4 Check electrical service phase sequence 3 Phase models only as follows a Energize the electrical service and momentarily start the tumbler Check the direction of cylinder rotation If the cylinder rotates clockwise as viewed from the front the phase sequence is correct If the cylinder rotates counterclockwise proceed with step b b Disconnect power to machine disconnect and reverse the L1 and L2 connections on the terminal block Electrical Connections All gas and steam tumblers require a single service connection to TB1 of the upper unit junction box only The serial plate reflects current draw breaker fuse size and conductor amperage required for the entire machine All electric tumblers require separate service connections for each upper and lower unit Serial Plate ratings reflect current draw breaker fuse size and conductor amperage required per unit Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 37 Electrical Requirements Conversion Instructions If serial plate voltage is Tumbler can be converted to the following voltages 120 Volt 60 Hertz 208 240 Volt 60 Hertz 1 Phase Models 1 Phase 3W amp G 2W amp G 1 Prior to connecting service locate the black red wire which runs between T30 Models Only terminal bloc
56. rsonal injury or death CAUTION Indicates a hazardous situation that if not avoided may cause minor or moderate personal injury or property damage Additional precautionary statements IMPORTANT and NOTE are followed by specific instructions IMPORTANT The word IMPORTANT is used to inform the reader of specific procedures where minor machine damage will occur if the procedure is not followed NOTE The word NOTE is used to communicate installation operation maintenance or servicing information that is important but not hazard related 6 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT AL wanne Failure to install maintain and or operate this machine according to manufacturer s instructions may result in conditions which can produce serious injury death and or property damage Wo051R1 NOTE The WARNING and IMPORTANT instructions appearing in this manual are not meant to cover all possible conditions and situations that may occur It must be understood that common sense caution and carefulness are factors which CANNOT be built into this tumbler These factors MUST BE supplied by the person s installing maintaining or operating the tumbler Always contact your dealer distributor service agent or the manufacturer on any problems or conditions you do not understand 70304601 Safety Information The interior of the tumbler and the exhaust duct should b
57. sse se ese ee ee RA Ge ee ee ed 6 Important Safety Instructions 2 0 0 esse sesse se ee ee Ge RA Ge ee ee ee 7 Specifications and DimensiOnS iese see ee ee ee ee ee ee 9 Cabinet Dimensions iese seve cides SEER SG ES AG se i SE Ee Seg 10 Exhaust Outlet Location ees see see se se Ge ee ee Ge RA GR ee ee ee 11 Gas Connection Locations ee ese se ee ee ee Ge GR ee ee 12 Electrical Connection Locations ces sees see ee Ge GR ee ee se 13 Steam Connection Locations ees sesse se ee ee ee ee ee Ge GR de 14 El EL RE AE N AO RE N 15 Pre Installation Inspection esse esse see se Se ee ee Ge RA Ge ee ee ed 15 Location Reguirements sesse see se se ee Se AG ee GR Ge ee ee 15 Position and Level the Tumbler eee esse see ee Ge GR ee ee Ge 17 Before Placing Tumbler into Service iese se se ee GR Re ee 18 Required for CE Models Only esse se esse ees ee ee ee Ge Ge ee ee 19 Installing CE Gas Drying Tumblers e iese esse esse ese ee se de Gee ee ee ee se 19 General Information ESE nen Se Ee SEE Ee Ese ESE GESE os se bede ged Ee 19 Basic Configuration i s Ee SR sig ees SEGE E Gee reg ED Eps SE de ee gers 20 Specific Conversion Procedures iss ee ee ee ee ee ee 22 Exhaust Requirement esse see see ee ee Re AA ee Re ee RA 24 EMOSIE EE DI BE tndeiess 24 Make OE ER AE EE EO ON RE 24 TR OE MR EE E EEN 24 Individual Venting sissies bie erreren ee RR RE aiat 25 Manifold Venting iese bee se see Se eel OS EERS
58. sure Equivalent Length 25 feet 50 feet 75 feet 100 feet 125 feet 150 feet Gas 7 63 m 15 25 m 22 88 m 30 50 m 38 13 m 45 75 m Appliances Total Btu hr Based on 0 3 in Water Column Pressure Drop for Length Given Sizes shown in inches mm 100 000 0 75 19 05 0 75 19 05 1 25 40 1 25 40 1 25 40 1 25 40 120 000 0 75 19 05 1 25 40 1 25 40 1 25 40 1 25 40 1 25 40 140 000 0 75 19 05 1 25 40 1 25 40 1 25 40 1 25 40 1 25 31 75 160 000 0 75 19 05 1 25 40 1 25 40 1 25 31 75 1 25 31 75 1 25 31 75 180 000 1 25 40 1 25 40 1 25 40 1 25 31 75 1 25 31 75 1 25 31 75 200 000 1 25 40 1 25 40 1 25 31 75 1 25 31 75 1 25 31 75 1 5 38 10 300 000 1 25 40 1 25 31 75 1 25 31 75 1 5 38 10 1 5 38 10 1 5 38 10 400 000 1 25 31 75 1 25 31 75 1 5 38 10 1 5 38 10 1 5 38 10 2 50 80 500 000 1 25 31 75 1 5 38 10 1 5 38 10 2 50 80 2 50 80 2 50 80 600 000 1 5 38 10 1 5 38 10 2 50 80 2 50 80 2 50 80 2 50 80 700 000 1 5 38 10 2 50 80 2 50 80 2 50 80 2 50 80 2 5 63 50 800 000 1 5 38 10 2 50 80 2 50 80 2 50 80 2 5 63 50 2 5 63 50 900 000 2 50 80 2 50 80 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 1 000 000 2 50 80 2 50 80 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 1 100 000 2 50 80 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 2 5 63 50 1 200 000 2 50 80 2 50 80 2 5 63 50 2 5 63 50 2 5 63 50 2 5 63 50 1 300 000 2 5
59. team solenoid valve and downstream of each steam trap so components can be isolated for maintenance or emergency purposes All components solenoid valve traps must be supported to minimize loads on the tumbler steam coil connections W480R2 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 43 Steam Requirements Installing Steam Trap and Making Condensate Return Connections The steam trap must be installed and the coil outlet connections must be connected to the condensate return lines The following steps outline the procedure for installing the steam trap and connecting the condensate return lines Refer to Figure 15 for typical installations 1 Use flexible lines between steam inlet solenoid and steam coils as well as outlet between steam coil and traps 2 If necessary install a strainer at the end of each flexible hose 3 Install a steam trap to each strainer IMPORTANT Steam trap must be installed a minimum of 18 inches 457 mm below the steam coil outlet connections 4 Install a shut off valve to each steam trap 5 Connect to the condensate return lines 6 For steam solenoid valve wiring connections refer to Wiring Diagram supplied with tumbler 44 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT The flexible steam hoses connecting the coil outlet connections and steam traps must have a minimum of 125 psig pounds per square inch gauge 8 79 kg
60. touch any electrical switch do not use any phone in your building Clear the room building or area of all occupants Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier W052 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance W053 The following information applies to the state of Massachusetts USA e This appliance can only be installed by a Massachusetts licensed plumber or gas fitter e This appliance must be installed with a 36 inch 91 cm long flexible gas connector e A T Handle type gas shut off valve must be installed in the gas supply line to this appliance e This appliance must not be installed in a bedroom or bathroom 70304601 Al MISE EN GARDE POUR VOTRE SECURITE les informations de ce guide doivent tre respect es afin de r duire les risques d incendie d explosion ou d viter les dommages mat riels personnels ou blessures mortelles W033R3QU e Ne pas entreposer ou utiliser d essence ou toutes autres vapeurs et liquides inflammables a proximit de cette machine ou de tout autre appareil QUE FAIRE EN CAS D ODEUR DE GAZ Ne pas mettre d appareil en marc
61. ximum Static Back Pressure 2 0 Inches W C mbar 60 Hertz 0 9 0 9 2 3 2 3 Gas Models Gas Connection 1 2 in NPT 1 2 in NPT Gas Burner Rating 73 000 95 000 Btu hr kW Mj hr 21 4 77 27 8 100 2 Electric Models Heating Element Rating 21kW N A Steam Models Steam Connection 3 4 in NPT N A Steam Coil Rating at 100 psig 3 2 N A Boiler Horsepower Btu hr 111 000 Steam Coil Rating at 15 psig 2 2 N A Boiler Horsepower Btu hr 74 000 with both pockets running for each pocket N A Not Applicable 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT Specifications and Dimensions Cabinet Dimensions B C Y Y G gt TMB2230N Models A B C D E T30 28 In 48 in AA in 11 in 10 in 711 mm 1219 mm 1118 mm 279 mm 254 mm 31 88 in 49 in 9 in T45 810 mm 1245 mm NA NA 229 mm Models F G H I J T30 25 02 in 42 76 in 27 38 in 31 5 in 76 25 in 636 mm 1086 mm 695 mm 800 mm 1937 mm T45 29 37 in 48 62 in 30 50 in 34 5 in 81 25 in 746 mm 1235 mm 775 mm 876 mm 2063 75 mm N A Not Applicable NOTE To meet ADA compliance install a 4 inch 102 mm riser on T30 models only 10 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 70304601 Specifications and Dimensions Exhaust Outlet Locations Da AT TMM A
62. your product be sure to mention model and serial numbers Model and serial numbers are found on serial plate on the rear of machine and inside door Tol ER al EE ETA TMB1974N 1 Serial Plate Conversion Table Multiply By To Obtain Multiply By To Obtain Btu 0 252 kCal Pounds sq inch 0 06895 Bars Btu 1055 Joules Pounds sq inch 0 070 kg sq cm Inch 25 4 Millimeters Pounds Ibs 0 454 Kilograms Inches W C 0 036 Pounds sq inch Boiler Horsepower 33 479 Btu hr Inches W C 0 249 kPa Boiler Horsepower 34 5 Ibs steam hr Ib inch psi 6 895 kPa CFM 0 471 liters second fr 28 32 Liters kW 3414 Btu hr 70304601 Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 5 Safety Information Explanation of Safety Messages Precautionary statements DANGER WARNING and CAUTION followed by specific instructions are found in this manual and on machine decals These precautions are intended for the personal safety of the operator user servicer and those maintaining the machine DANGER Indicates an imminently hazardous situation that if not avoided will cause severe personal injury or death Indicates a hazardous situation that if not avoided could cause severe pe

Download Pdf Manuals

image

Related Search

Related Contents

DreamLine DL-6710-01 Installation Guide  取 扱 説 明 書 - ヤマト科学株式会社  1 - Sony  une possibilité technologique pour la modernisation des tribunaux  Herunterladen  Fan-coil “Cassette” serie “CT”  Printer Management Utility Scanner Mode for Fiery S300 31C-M    Capcom Video Games PlayStationPortable User's Manual  Dataram 8GB DDR2-667, PC2-5300  

Copyright © All rights reserved.
Failed to retrieve file