Home
        Honeywell 68-0287-04 Thermostat User Manual
         Contents
1.                                                       Calibration Table 14  VisionPRO   IAQ Error Codes   The C7189U1005 Wall Mount Temperature Sensor is    calibrated at the factory and cannot be recalibrated in the field  Error Code Meaning  027 Faulty thermostat  must be replaced   035 Duplicate thermostat zone detected  Table 13  Sensor Resistance at Room Temperature  036 Duplicate UV timer  Room Room 037 Duplicate filter timer  Temperature Ohms of Temperature Ohms of 038 Duplicate humidifier pad timer  F s Resistance F S Resistance 039 Duplicate indoor humidity sensor  a9 ier ERII 12 2225 11100 040 Compressor should be running but it is not  42 5 6  21516 74 23 3  10644    050 Duplicate outdoor temperature sensor  44 6 7  20546 76 24 4  10210 FERRE  052 Faulty post coil air discharge sensor  46 7 8 19626 78 25 6  9795  053 Faulty outdoor temperature sensor  ai  SIME Qd an gO eee 054 Faulty indoor humidity sensor  50 10 0  17926 82 27 8  9020       ae  089 Heating cooling equipment is missing  32 VET  E190 84 28 9 1 8659 090 Data interface is continuously busy  as ion no 28 30018913 091 Thermostat is not receiving data from other  56 13 3  15675 88 31 1  7986 equipment  58 14 4  14999 90 32 2 7672 118 Faulty discharge air temperature sensor  60 15 6  14356 92 33 3  7372 119 Faulty temperature sensor  62 16 7  13743 94 34 4  7086 121 Duplicate post coil air discharge sensor                               35                68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SY
2.                        Operation  When installed with Thermostat Installer Setup Number 0340  set to 1  the remote inside temperature is displayed on the  thermostat home screen as Inside Temperature  The  thermostat internal temperature sensor is not used  When    C7189U1005 Remote Indoor Temperature  Sensor       installed with Thermostat Installer Setup Number 340 set to 2   the temperature displayed on the thermostat home screen as  Inside Temperature will be a 50 50 average between the  temperature sensed at the remote sensor location and the  temperature sensed at the thermostat location     The C7189U1005 Wall Mount Temperature Sensor converts  room temperature to a resistance that the thermostat can  interpret     The C7189U1005 has a negative temperature coefficient   NTC   which means that resistance decreases as the  temperature increases  See Table 13     The C7189U1005 can be used to provide one remote sensor  input  see Fig  26  or as a temperature averaging network with    multiple C7189U 1005 Sensors connected  as shown in Fig  27     Checkout    For best results  allow C7189U1005 Wall Mount Temperature  Sensor to absorb the air moving through the room for a  minimum of twenty minutes before taking a resistance  measurement     With an accurate thermometer   1  F  0 5  C   measure the  temperature at the sensor location  allowing time for the  thermometer to stabilize before reading     To verify sensor resistance  remove one wire from one of  C7189U1005 wirin
3.           FIELD INSTALLED  JUMPER BETWEEN  H1                            DHM 1 AND VNT 1 U    SOM  BLUE  Sp Us  H  ORA  YELLOW y Si  GREEN LS T2  r              RED       M23495    Fig  20  Hookup of Honeywell DH90 with fresh air intake for  ventilation     68 0287   04 8    POWER THE THERMOSTAT      24 Vac common wire only to EIM or zone panel     Wiring 24 Vac Common      Single Transformer System   Connect the common side of  the transformer to the C screw terminal of the EIM  Leave  the metal jumper wires in place between R  Rc  and RH      Two Transformer System   Connect the common side of  the cooling transformer to the C screw terminal of the EIM   Remove the metal jumper wire between Rc and Rh   Connect the hot side of heating transformer to Rh and leave  the jumper wire between R and Rc and connect the hot side  of cooling transformer to R or Rc     1  Locate and remove the tab labeled  Remove  in the  lower left corner on the thermostat back  See Fig  21     REMOVE  TAB    A    REMOVE DURING   INSTALLATION                 M19920    Fig  21  Remove tab labeled  Remove  on thermostat back    Mount Thermostat to Wallplate    1  Align the terminal screw blocks with the pins on the back  of the thermostat  Push the thermostat straight onto the  wallplate until it snaps into place  See Fig  22     WALLPLATE                   PINS ON  BACK OF  THERMOSTAT             M23542    Fig  22  Mount thermostat to wallplate     Locate and Mount C7089U1006 Outdoor  Temperature Senso
4.      THERMOSTAT  AND WALLPLATE     a 1 3 8      THERMOSTAT        6 152                             e                                            M23539    Fig  1  VisionPRO   IAQ Comfort System  dimensions in in   mm         Honeywell    Equipment Interface Module  7 9 32   185     6 57 64   175                                          e 4 35 64        1 2164      116   34   FRONT VIEW SIDE VIEW  M23544    Fig  2  THM5421C1008 Equipment Interface Module  dimensions in in   mm      VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM             1 1 2  38        M4488    Fig  3  C7089U1006 Outdoor Sensor Mounting Clip    dimensions in in   mm        lt  7 7 8  200              ____       4       3 5 16  84                          M22139    Fig  4  32003796 001 Cover Plate dimensions in in   mm      68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Honeywell    I 1 1 2  38            gt     M23522 FRONT VIEW    L  45 64 a    SIDE VIEW           1 1 2  38                FRONT VIEW  COVER OFF     Fig  5  C7189U1005 Remote Indoor Sensor dimensions in in   mm      INSTALLATION    When Installing this Product       1  Read these instructions carefully  Failure to follow the  instructions can damage the product or cause a hazard   ous condition    2  Check the ratings given in the instructions to make sure  the product is suitable for your application    3  Installer must be a trained  experienced service  technician    4  After completing installation  use these instructions to  ver
5.      WITH FROST PROTECTION   Controlling humidification with frost protection requires an  outdoor temperature sensor  The Frost Index  scale 1   10  will  limit the amount of humidity added to the air based on outdoor  temperature  with 1 most dry and 10 most humid  This  prevents frost from accumulating on windows     c laj    Inside m   Tl 06        os pan f  JL v  FROST    HUMIDIFIER     4      ILJ  Humidity w    xL E EL E ee    M23518          WITHOUT FROST PROTECTION  The frost setpoint is not displayed  but a humidity setpoint can  still be set     21    VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    1  Press the More key until the inside humidity level set   point is shown    2  Use Up and Down arrow keys  located to the right of the  humidity setpoint  to set desired humidity level    3  Press Done key     Control Dehumidification Level    The VisionPRO   IAQ Touchscreen Thermostat reads the  inside humidity level and allows for a dehumidification setting   and can be set to dehumidify using the air conditioner or a  whole house dehumidifier     CURRENT  INDOOR  HUMIDITY                                        DEHUMIDIFIER  SETTING   AUTO OFF     HUMIDITY SET  POINT  M23496    With Air Conditioner    The set range for dehumidification is 40 to 80   and can be set  in 5  increments  The thermostat must be in Cool mode or  Auto mode when the previous call was a call for cooling     Inside m     96    at     DEHUMIDIFIER    rr   Il    Lv   Loa O JL    M23514       Dehumidi
6.   1 Conventional Selection of a specific system setting will  2 Heat Pump automatically modify some default settings and or  3 Heat Only No Fan hide other installer setup options that follow   E Auto Discover  173 Heat Pump Type  0 Air to Air heat pump  1 Geothermal heat pump  174 Number of Cool   1 1 Not shown if ISU172   3   Compressor 0 none Conventional systems   number of cooling stages   Stages 2 2 Heat Pump systems   number of compressor  E Auto Discover stages   176 Number of 1 1 Conventional systems   number of heating stages  Conventional 0 none  maximum of 3    Heat or Heat 2 2 Heat Pump systems   number of auxiliary heat  Pump Aux Stages 3 3 stages  maximum of 2    E Auto Discover  180 Fan Operation 0 Gas or oil furnace equipment controls fan Only shown if ISU172   1  conventional system    Conventional in heating Use 0 for fossil fuel systems  equipment controls  heat only 1 Electric furnace   thermostat controls fan in fan    heating Use 1 for electric systems  thermostat controls fan    2 Equipment controls stage 1  thermostat Use 2 if stage 1 is radiant heating and stage 2  is a  controls stage 2  hot water fan coil   E Auto Discover                      13    68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                                                     ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  190 Reversing Valve  0 Changeover valve   O B terminal i
7.   then move up one setting to the minimum  passing value   405 Ventilation Fan  1 Vent on will force fan on also  Action 2 Vent will not force fan ON  406 Ventilation in 1 On Only shown if ISU372 and ISU400 are not set to 0   High Humidity 0 Off When set to On will use ventilation to remove  humidity when thermostat is in the heat mode   430 Ventilation 0 Disabled Outdoor temperature sensor required for high and  lockout 1 Lockout for high temperatures low temperature lockouts   2 Lockout for low temperatures  3 Lockout for high and low temperatures  431 Ventilation 100 38  100 F 38  C  lockout high 90 32  90 F 32  C  temperature 95 35  95  F 35  C  105 40 5 105 F 40 5  C  110 43 5  110  F 43 5  C  432 Ventilation  10  23 5  10 F  23 5  C  lockout low  20  29   20  F  29 0  C  temperature  15  26   15  F       26 0C   5  20 5   5  F  20 5  C   0  18  0  F  18 0  C  450 DATS Inhibit 0 Disabled The DATS will cycle the cooling off at the selected  35 1 5  35  F 1 5  C temperature to prevent coil freezing   40 4 5  40  F 4 5  C  45 7  45  F 7 0  C  50 10  50  F 10 0  C  55 13  55  F 13 0  C  60 15 5  60  F 15 5  C  65 18 5  65  F 18 5  C  500 Furnace Filter E Auto Discover  USU Change 0 Disabled  Reminder 1 10 R T  Days  2 30 R T  Days  3 60 R T  Days  4 90 R T  Days  5 120 R T Days  6 180 R T  Days  7 270 R T  Days  8 365 R T  Days  9 30 C Days  10 60 C Days  11 90 C Days  12 120 C Days  13 180 C Days  14 365 C Days  502 Furnace filter 0 Counts runtime Heat and Cool       remind
8.  5  15  5  F  15 0  C outdoor temperature sensor present   Lockout 10  12  10  F  12 0  C  Temperature 15  9 5  15  F  9 5  C  20  6 5  20  F  6 5  C  25  4  25  F  4 0  C  30  1  30 F  1 0  C  35 1 5  35  F 1 5  C  40 4 5  40  F 4 5  C  45 7  45  F 7 0  C  50 10  50  F 10 0  C  55 13  55  F 13 0  C  60 15 5  60  F 15 5  C  65 18 5  65  F 18 5  C   Show 1 2 degree C   365 Discharge Temp  E Auto Discover  Sensor 0 None  1 Remote  366 Zoning High 160 160  F  71  C  Only Shown if ISU110   1  Master Zone Controller   Temperature 0 Disabled and Discharge Temperature Sensor is available   Limit 110 170 110  F to 170  F  43 5  C to 76 5  C   367 Zoning Low 40 160  F  71  C  Only Shown if ISU110   1  Master Zone Controller   Temperature 0 Disabled and Discharge Temperature Sensor is available   Limit 35 50 35  F to 50  F  1 5  C to 10  C                       15    68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                                                     ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  368 Staging 110 110  F  43 5  C  Only Shown if ISU110   1  Master Zone Controller   Discharge 0 Disabled and ISU174   2 or more  Must have Discharge  Temperature 80 130 80  F to 130  F  26 5  C to 54 5  C  Temperature Sensor present   High Limit  369 Staging 55 55  F  13  C  Only Shown if ISU110   1  Master Zone Controller   Discharge 0 Disabled and ISU176   2  Must have Dischar
9.  C      Operating Relative Humidity  Non condensing      VisionPRO   IAQ Thermostats  5  to 90    THM5421C1008  5  to 90    C7089U1006  5  to 95     C7189U1005  5  to 95      Humidification Setting Range   Heating  10  to 60  RH     Dehumidification Setting Range   Heating  40  to 80  RH     Humidity Display Range   0  to 99      Cycle Rates  at 50  Load      Heating  Selectable 1   12 cycles per hour   Cooling  Selectable 1   6 cycles per hour     68 0287   04       Finish    VisionPRO   IAQ Thermostats  Premier White   color    THM5421C1008  Premier White   color    C7189U1005 Wall Mount Remote Indoor Sensor  Premier  White   color     Clock Accuracy      1 minute per year     Resistance Characteristics of Remote Sensors    C7089U1006 Outdoor Sensor  Negative temperature coeffi   cient  NTC  means that resistance decreases as the tem   perature increases  See Table 12 in the Operation section  for sensor resistance characteristics    C7189U1005 Remote Indoor Sensor  Negative temperature  coefficient  NTC   means that resistance decreases as the  temperature increases  See Table 13 in the Operation sec   tion for sensor resistance characteristics     Cool Indication   VisionPRO   IAQ Comfort Systems show    Cool On    on the  thermostat screen when Cool is activated     Heat Indication   VisionPRO   IAQ Comfort Systems show  Heat On    on the  thermostat screen when Heat is activated     Auxiliary Heat Indication   VisionPRO   IAQ Comfort Systems show    Aux  Heat On    on  
10.  Off This can be used to remove condensation from A   time Cool  Blower  30 30 seconds coil  however  could re introduce humidity into the  Off Delay Heat   60 60 seconds living space   90 90 Seconds  120 120 Seconds  670 Keypad Lockout  0 Unlocked  USU 1 Partial Locked  2 Full Locked  680 Temp Control 2 Standard  recommended   Heat 1 Less Aggressive temp control  may cause  temp undershoot   3 More Aggressive temp control  may cause  temp overshoot   690 Temp Control 2 Standard  recommended   Cool 1 Less Aggressive temp control  may cause  temp undershoot   3 More Aggressive temp control  may cause  temp overshoot   700 Temperature 0 0  F 0   C      no difference in  Display Offset displayed temperature and actual room  temperature    3  3  F  1 5  C   2  2  F  1  C   1  1  F   5  C  1 1  F 56  C  2 2  F 1  C  3 3  F 1 5  C  68 0287   04 18       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                    ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  701 Humidity Display  0 0   Offset  12  12     11  11    10  10    9  9    8  8    7  7    6  6    5  5    4  4    3  3    2  2    1  1   1 1   2 2   3 3   4 4   5 5   6 6   7 7T   8 8   9 9   10 10   11 11   12 12    710 Restore Factory  0 No Restoring factory defaults will re set installer setup   Defaults 1 Yes and programming                 INSTALLER SYSTEM TEST    Use the Installer System Test to test the heating  cooling and  fa
11.  SCREW M23484    Fig  8  Mounting EIM     WIRING    All wiring must comply with local electrical codes and  ordinances  See Fig  10   20     1     2     Select set of terminal identifications  Table 1  that corre   sponds with system type    Loosen the screws for the appropriate system type  selected  see Table 1  See Table 2 for terminal designa   tion descriptions  Insert wires in the terminal block under  the loosened screw  See Fig  9    Securely tighten each screw    Push excess wire back into the hole    Plug the hole with nonflammable insulation to prevent  drafts from affecting the thermostat    See Fig  10   20 for typical wiring hookups     Table 1  Selecting Terminal Identifications for System Type                                      Wallplate Terminal   Wiring Diagram  System Type Identifications Reference  Standard Heat Cool   Conventional 10  11  Standard Multistage   Conventional 12  up to 3 Heat 2 Cool  Heat Pump with Heat Pump 13  Auxiliary Heat  68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM          a QR  VY       Q  QE  y     M23541    Fig  9  Inserting wires in terminal block     IMPORTANT    Use 18 gauge thermostat wire     Table 2  Terminal Designation Descriptions           THM5421C1008  Terminal  Designations    Function                                                                            1 Terminal 1   data to from thermostat   2 Terminal 2   power from thermostat  24Vac    3 Terminal 3   common from thermostat   24Vac    C 24 Vac Tr
12.  and Screen Status                    Fan  Fan Call Status  Fan Program for Energize   shownon  Setting   Schedule   Action   Terminal Screen  Auto Auto None None Auto  Auto On Fan G Auto On  Auto Circ None None Auto Circ  Auto Circ Fan G Auto Circ                         Manual Override of Fan Schedule   Auto   fan is automatically following the Fan schedule  choices  are Auto  On or Circulate     On   overrides Fan schedule  Fan is continuously On     Circ   overrides Fan schedule  Fan circulates randomly for  approximately 35  of time until the Auto position is selected     Table 11  Manual Override of Fan Schedule Operation                                         Screen  Fan Message  Schedule Call Under  Fan Override for Energize Fan  Setting Setting Action   Terminal Setting  Auto On Fan G On  Auto Circ None None Circ  Auto Circ Fan G Circ  On Auto    E      On Circ None None Circ  On Circ Fan G Circ  Circ Auto  m m D  Circ On Fan G On    4Auto Override resumes the Fan Program in each schedule  period  Wake  Leave  Return and Sleep     OPERATE VISIONPRO  IAQ    Set Time    1  Press Clock   2  Use arrows to set current time        eg  WIT r 2  x  D LE EL            CANCEL    M19958       3  Press Done key     IMPORTANT  The current day of the week should already be set  correctly  If not  see Installer Setup to set the day     Set Temperature Overrides    The thermostat has four temperature override options  Hold  Temperature Until  Permanent Hold  Vacation Hold  and  Sou
13.  j  O   Wwe LI  6  coo    JL Mole    Humidity             ka HOLD e MORE                  M23678    If thermostat is set to Auto Changeover System mode  press  the More key until the humidity level is shown on the screen     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Inside LI l T      J       Twice    M23679          C7089U1006 Outdoor Temperature Sensor    Operation   When installed with Thermostat Installer Setup Number 0342  set to 1  the outside temperature can be displayed on the  thermostat  See Fig  34     Inside Ul   Set To 7  m  4   i   C     Following  Schedule  Outside    TL MNT  au  r           peus   HOLD   CLOCK lia   MORE         M22453    Fig  34  Outside temperature reading on  VisionPRO  IAQ Thermostat     The C7089U1006 Outdoor Sensor converts outdoor ambient  temperature to a resistance that the thermostat can interpret     The C7089U1006 has a negative temperature coefficient   NTC   which means that resistance decreases as the  temperature increases  See Table 12     Checkout    Allow C7089U1006 Outdoor Sensor to absorb outdoor air for a  minimum of twenty minutes before taking a reading     With an accurate thermometer   1  F  0 5  C   measure the  temperature at the sensor location  allowing time for the  thermometer to stabilize before reading     To verify sensor resistance  remove one wire from one of the  C7089U1006 60 in  leadwires  Use an ohmmeter to measure  the resistance across the sensor  Then verify the sensor  accuracy wit
14.  matches the screen below                     M22442       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    4  See screen below to review how the thermostat keys are  used during Installer Setup  See Table 3 4 for the    Installer Setup Numbers and Settings     INSTALLER 4  SETUP  NUMBER    r  ADVANCE TO NEXT  INSTALLER SETUP    CURRENT  SETTING       PRESS TO EXIT  INSTALLER SETUP                                     CHANGE THE  CURRENT    SETTING M22443    5  Press the Done key to exit the Installer Setup screen     Table 3  Installer Setup Menu                                                  ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  110 Zone Number 0 Not zoned Select zone number   1 9 Zone number Zone 0   not zoned  Zone 1   master zone controller   Zone 2 9   satellite thermostat    Only change if used with Envirazone Panel   120 Date  Year 20 Select first two digits of current calendar year  2006  USU Upper  21 for example     2001 2178 available    130 Date  Year 01 99 Default   06 Select last two digits of current calendar year  2006  USU Lower  for example     2001 2178 available    140 Date  Month  1 12 Default   06  USU Select number that represents current  calendar month   150 Date  Day  1 31 Default   15  USU Select number that represents current  calendar date   160 Schedule Options  4 Seven day programmable  USU 0 Non programmable  165 Restore energy  0 No  USU saving default 1 Yes  schedule  172 System Selection
15.  to Heat    and or temperature setting is not set    above room temperature     Action    Set the system setting to Heat and set the temperature  setting above the room temperature        Cool On is not in the display     System setting is not set to Cool  and or the temperature setting is  not set below room temperature     Set the system setting to Cool and set the temperature  setting below the room temperature        Wait is in the display     Compressor minimum off timer is  active     Wait up to five minutes for the cooling or heating  heat  pump  equipment to turn on         Screen Locked  appears on the  screen and all or some of the  keys do not respond           The keypad is fully or partially  locked        Check Installer Setup Number 0670 to change keypad  locked options        68 0287   04    38       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    COMPATIBILITY    Recommend the following products for use with the VisionPROQG IAQ     Table 16  Humidifiers          HE440A1005   Powered Steam Humidifier with 13 gpd capacity  HE365A1006   Powered Bypass Flow through humidifier with 18 gpd capacity  HE265A1007   Bypass Flow through humidifier with 17 gpd capacity  HE225A1006    Bypass Flow through humidifier with 12 gpd capacity                      Table 17  Dehumidifier  DH90A1007   90 Pint Whole House Dehumidifier                   Table 18  Ventilation          HR150B1005   heat recovery ventilator 150cfm with built in defrost  HR200B1005   heat recovery ventilato
16. 1  Choose correct heat pump application in Installer Setup  Number 0172    2  Choose Fossil Fuel Option as the backup heat source  in Installer Setup Number 0200    3  Choose No External Fossil Fuel Kit Option is control   ling back up heat in Installer Setup Number 0210    4  Choose Outdoor Temperature Sensor for Heat Pump    Temperature Lockouts in Installer Setup Number 0342     5  Choose appropriate Balance Point Temperature in  Installer Setup Number 0350     Dual Fuel Heat Pump Control    Balance Point Only  ISU345   0     NOTE  System must have an outdoor temperature sensor     When the outdoor temperature is above the selected balance  point temperature  only the compressor operates and the fan   G terminal  energizes when the thermostat calls for heat  See  Fig  30  When the outdoor temperature is below the selected  balance point temperature  only the fossil fuel  auxiliary heat   operates and the fan  G terminal  does not energize when the  thermostat calls for heat     COMPRESSOR ONLY    BALANCE    30 POINT       FOSSIL FUEL ONLY    OUTDOOR TEMPERATURE       M22441    Fig  30  Dual Fuel Heat Pump Operation in Heat mode with  Balance Point Set     Balance Point Plus Droop  ISU345   1    The fossil fuel will turn on when the outdoor temperature is  above the balance point if the room temperature droops below  the selected droop temperature setting  and the compressor  will be disabled     23    VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Balance Point Auxiliary Hea
17. 23502    2  Press and hold the center blank key for approximately  five seconds until the screen changes     25    3           TUE    Inside r rV  l     EM HEAT     OFF  COOL    Set To      ZI  4     II   v     Following  Schedule    Humidity       DONE          em                   Honeywell       gieo e     v     zn     o             M23503    Release the center blank key when the screen on the  thermostat matches the screen below     M22440    68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    4  Seethe screen below to review how the thermostat keys          are used during the User Setup  See Table 8 for the User                                     Table 8  User Setup Menu   Continued                                                                                               Setup numbers and settings  gr Wear Setup  ADVANCE TO NEXT No  Name Settings  USER SETUP 500  Furnace Filter  0 Disabled  MUMBEE ME d CURRENT Change 1  10 R T  Days  SETTING Reminder 2 30 R T  Days  3 60 R T  Days  4 90 R T  Days  5 120 R T Days  6 180 R T  Days  7 270 R T  Days  8 365 R T  Days  9 30 C Days  10 160 C Days  11 90 C Days  12 120 C Days  13 1180 C Days  14 1365 C Days  E Auto Discover  510  Humidifier Pad  O Disabled  Replacement 1 90 C Days  Reminder 2 180 C Days  3 365 C Days  E Auto Discover  PRESS TO EXIT CHANGE THE    520  UV Lamp 0 Disabled  USER SETUP aa Waz Replacement  1 365 Days  Reminder 2 730 Days  2 years   5  Press the Done key to exit the User Setup screen  E A
18. ACTORY INSTALLED  JUMPER BETWEEN R   RC AND RH    A WIRE TO TERMINALS ON THERMOSTAT  M23485  Fig  10  Typical hookup of conventional single stage heat  and cool system with single transformer   1H 1C conventional               COMMUNICATION   CONV  HP  TERMINALS W1 OB    QW2 AUX  Yamo  W3 AUX2  Qv Y  Qy2 v2  HGe c               COMMUNICATION LED C                                                                 OIL PRIMARY   AQUASTAT    FACTORY INSTALLED JUMPER BETWEEN R   AND RC  REMOVE FACTORY INSTALLED  JUMPER BETWEEN RC AND RH       A WIRE TO TERMINALS ON THERMOSTAT  M23486    Fig  11  Typical hookup of conventional single stage heat  and cool system with oil primary  1H 1C conventional      VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM       KEY      NORMALLY OPEN  DRY CONTACTS         NORMALLY CLOSED  DRY CONTACTS    M23685                   r  HEAT 1 RELAY   COMMUNICATION LED L    COMMUNICATION   CONV  HP  TERMINALS W1 OB HEAT 2 RELAY H      f Swe AUX H HEATS RELAY                                   24VAC     4     H   ws aux2 Fig   Qv Y COOL 1 RELAY                                                                                                                                                                                                                                        Qv v2  COOL 2 RELAY   Gc G RY  FACTORY INSTALLED   FAN RELAY f  2  JUMPER BETWEEN R  G3  RC AND RH  Sc A  A WIRE TO TERMINALS ON THERMOSTAT  M23487 R        FIELD INSTALLED BE  Fig  12  Typical hookup o
19. Auto                period          68 0287   04    26                   Program Heating and Cooling Schedule    Your thermostat can control up to four different schedule    periods per day     Wake   Period when you awaken and want your home at a    comfortable temperature     Leave   Period when you are away from home and want an    energy saving temperature     Return   Period when you return home and want your home    back to a comfortable temperature     Sleep   Period when you are asleep and want an energy     saving temperature           NOTE  Schedule times are in 15 minute intervals     Edit Schedule    1  Press Sched key     Inside T n t Tm    ILI Hel    Following    Schedule    I   Lyr    ugm  Humidity               HOLD   CLOCK  ee            M23504    2  Press Edit key     Com  ve  wo  w vm oe on   _ran_     21 5  AUTO JL  EN  Ly   PERIOD  z  A    Hs f  COOL    Lit  Lv  Lv         OK TO PICK MULTIPLE DAYS          a          am   7  WAKE   LEAVE Lom SLEEP Jue    MN M22553             3  Itis OK to pick multiple days  Select any combination of  days to edit  These days are scheduled with the same  times and temperatures  Check marks appear next to  days selected     V MON       TUE   v WED    v THU    v FRI SAT    OK TO PICK MULTIPLE DAYS    ON    m  AUTO ILI  CIRC   PERIOD  I nn  J  IrLILI  v                 ome    WAKE   LEAVE E zm CANCEL  M19955          HEI  ILI          Flo  S9      DONE                  4  Press Wake key  Once pressed  Wake flashes to show i
20. Device  functions correctly even when not level    6  Install C7189U1005 cover           S                  G             M23523    Fig  26  Wiring a single C7189U1005 Indoor Sensor         2 22    C7189        C7189 C7189       C7189       C7189    M23524    Fig  27  Wiring Multiple C7189U1005 Sensors     If a remote indoor temperature sensor is installed  the  thermostat has several options for displaying the current indoor  temperature  This is configured in ISU 340  The thermostat can  display either the temperature measured at the thermostat  location  the sensor location  or a 50 50 average of both     ONE REMOTE INDOOR SENSOR INSTALLED  OPTIONAL    If one remote indoor temperature sensor is used  based on  configuration during installer setup  either of the following  options are available       The thermostat will display the temperature measured at  the sensor location  internal thermostat sensor is disabled       The thermostat will display a 50 50 average of the  temperature measured at the thermostat location and the  remote indoor sensor location     MULTIPLE REMOTE INDOOR SENSORS INSTALLED  OPTIONAL   If more than one remote indoor sensor is used  based on  configuration during installer setup  either of the following  options are available     VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM      The thermostat will display the temperature measured at  the sensor locations  internal thermostat sensor is  disabled   Sensors must be in square numbers  e g   4  9   16  a
21. ORE       M22453  If thermostat is set to Auto Changeover System mode  press    the More key until the outside temperature is shown on the  Screen     Outside          CANCEL    M22448       Locate and Mount C7189U1005 Remote  Indoor Temperature Sensor  Optional     1  Choose a location  see Fig  25  for mounting the sensor  on an inside wall about 5 ft  1 5m  above the floor    2  Besure wire distance between C7189U1005 and EIM is  less than 200 feet    3  Make sure there is good air circulation at average tem   perature at the chosen location  Avoid the following loca   tions because they can introduce errors in sensor  measurements  See Fig  25    a  Hotareas caused by    a Concealed pipes or ducts    b Drafts from fireplaces or other heat sources    c Convection or radiant heat from the sun or  electrical equipment   b  Cold areas caused by    a Concealed pipes or ducts    b Drafts from windows and doors    c Unheated areas on the other side of the wall  location   c  Dead air areas    a Behind doors  furniture and curtains    b In corners and alcoves    4  Mark the area on the wall selected for mounting the  C7189U1005 Sensor    5  Run wire cable to a hole at the selected wall location   Pull approximately three inches of wire through the  opening  Color coded  18 gauge thermostat wire is  recommended     68 0287   04 10                      5FEET   1 5 METERS                                   M4476    Fig  25  Typical location for C7189U1005 Indoor Sensor     Wire C7189
22. Outdoor Temperature Sensor in Installer  Setup Number 0342    4  Choose Compressor Lockout Temperature in Installer  Setup Number 0350    5  Choose Auxiliary Lockout Temperature in Installer  Setup Number 0360     NOTE  There is a 5  F deadband between the Compressor  and Auxiliary Heat Lockout Temperatures     Operation in Heat Mode    When the outdoor temperature is below the Compressor  Lockout Temperature  only the Auxiliary Heat operates     When the outdoor temperature is above the Auxiliary Lockout  Temperature  only the Compressor operates  See Fig  32     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM          AUXILIARY ONLY    Ww  a   p COMPRESSOR ONLY      50   a     BOTH COMPRESSOR AND  E AUXILIARY HEAT   S 35   o   a   E   3   O       AUXILIARY  LOCKOUT  TEMPERATURE    COMPRESSOR  LOCKOUT  TEMPERATURE    M19950    Fig  32  Heat Pump Operation with Lockout    Temperatures Set     When the outdoor temperature is between the two    temperatures  both the Compressor and Auxiliary Heat operate     Operation in Emergency Heat Mode    Once the thermostat is placed into the Emergency Heat mode   the compressor and auxiliary lockout features are turned off  In  the Emergency heat mode  the compressor is locked out  The  first stage of heat is whatever is connected to the AUX   terminal  The second stage of heat is connected to the AUX2     terminal     Operating Sequence    The thermostat energizes specific terminal s   depending on  the demand for heating  cool
23. PAD    RESET    DW ows      DONE   EDIT I    To view or reset the reminder before it expires  follow these  steps using the More key           al es     M23516       1  Press the More key until the Humidifier Pad change  reminder appears on the screen  This is the number of  calendar days remaining on the Humidifier Pad reminder    2  Press the Edit key    3  Use the Up and Down keys to change the number of cal   endar or run time days    4  Press the Done key to go back to the viewing screen    5  Press the Reset key to activate the new number of days  selected in the previous screen    6  Press the Done key to return to the Home Screen     UV Lamp Reminder   The UV Lamp change reminder must be turned on from the  Installer Setup  Once expired  the screen flashes   Change UV  Lamp  and a Reset key appears  Press the Reset key to reset  the change reminder     The remaining calendar days can be viewed by pressing the  More key     68 0287   04 32    NOTE  While the reminder is set according to calendar days     the display shows the equivalent run time days           MORE    CANCEL    M23517       The remaining days can be edited using the More key or from  the Installer Setup  To view or reset the reminder before it  expires  follow these steps using the More key     1  Press the More key until the UV Lamp change reminder  appears on the screen  This is the number of run time  days remaining on the UV Lamp reminder     2  Press the Edit key    3  Use the Up and Down keys to 
24. STEM    TROUBLESHOOTING    Table 15  Troubleshooting           Symptom  Display does not come on    Temperature setting does not  change    Possible Cause  Thermostat is not being powered    The upper and lower temperature  limits reached    Action    Check if the thermostat is mounted and latched on the wall  plate  If not    Mount and latch the thermostat on the wallplate   Check if the circuit breaker is tripped or the fuse is blown  if  it is     Reset the circuit Breaker or replace the fuse   Check if the power switch at the equipment is in the off  position  if it is    Set to the on position    Check for 24 Vac between terminals 2 and 3 at the  thermostat    Replace any broken wires if 24Vac is not present   Replace thermostat if 24Vas is present    Check for 24 Vac between terminals R and C at the  Equipment interface module    If 24Vac is not present consult electrician    If 24 Vac is Present replace Equipment interface  module     Check temperature setpoints   Check installer setup Numbers 0600 and 610  modify as  needed        Keypad is fully locked    Check Installer Setup Number 670 to change keypad  locked options        Heating or cooling does not  come on and thermostat is not  calling for heat or cool     Thermostat minimum off timer is  activated    Wait up to 5 minutes for the system to respond  Wait is  displayed on the Thermostat home screen        System selection is not set to Heat  or Cool    Set system selection to correct setting        Heating or c
25. U1005 Indoor Sensor     N CAUTION    Electrical Interference  Noise  Hazard    Can cause erratic system operation    Keep wiring at least one foot away from large inductive  loads such as motors  line starters  lighting ballasts and  large power distribution panels     IMPORTANT  Erratic temperature readings from a sensor can occur  as a result of any of the wiring practices described  below  Avoid these practices to assure correct  operation         Be sure wires have a cable separate from the thermo   stat cable        Do not route temperature sensor wiring with building  power wiring  next to control contactors or near light  dimming circuits  electric motors or welding equipment        Avoid poor wiring connections        Avoid intermittent or missing building earth ground      N CAUTION    Electrical Shock Hazard   Can cause electrical shock or equipment damage   Disconnect power supply before connecting wiring     Wiring must comply with applicable codes  ordinances and  regulations     1  Wire C7189U1005 Indoor Sensor to IN1and IN2 termi   nals on the EIM  For an example of general wiring of  C7189U1005  see Fig  26 to wire one sensor and Fig  27  to wire multiple sensors    2  Push excess wire back into the hole  Plug the hole using  nonhardening caulk  putty or insulation to prevent drafts  from affecting performance    3  Remove C7189U1005 cover    4  Mount C7189U1005 to the wall using the screws and  anchors provided    5  Level the C7189U1005 for appearance only  
26. URRENT SET  TEMPERATURE           a   Ly     Set To          a   a    Following  Schedule                SYSTEM TIME FOLLOWING  SHOWS DISPLAY CURRENT SCHEDULE  CURRENT TIME OF DAY  HOLD SHOWS THE  SYSTEM TIME REMAINING OR THERMOSTAT IS  POSITION NUMBER OF VACATION FOLLOWING THE    DAYS REMAINING    PROGRAMMED  SCHEDULE    M23501    System and Fan Settings    System    The System key selections vary based on your heating and or  cooling system type     Heat     Thermostat controls the heating system   Off     Both heating and cooling systems are off   Cool     Thermostat controls the cooling system     Auto     Thermostat automatically changes between heating  and cooling operation  depending on indoor temperature     Em  Heat     Emergency heat cycles to maintain temperature   Compressor is locked out and auxiliary heat turns on as  needed     Fan    The Fan key selections vary based on the heating and or  cooling system type     On     Fan runs continuously  Use this setting for improved air  circulation or for more efficient central air cleaning    Auto     fan follows the fan program schedule    Circ     fan runs randomly approximately 35  of the time  Use  this setting for improved air circulation or for more efficient  central air cleaning when you do not want the fan running  continuously     Control Humidification Level    The VisionPRO  IAQ Touchscreen Thermostat reads the  inside humidity level and allows for a humidification setting with  or without frost protection
27. VisionPRO   IAQ    Honeywell    Total Home Comfort System       APPLICATION    The VisionPRO   IAQ Total Home Comfort System features an  effortless  7 Day programmable touchscreen thermostat that  provides control of temperature  humidification   dehumidification  and ventilation     PRODUCT DATA    FEATURES      Large  clear display with backlight shows the current  and set temperature and time   even in the dark       Touchscreen interaction      Real time clock keeps time during power failures and  automatically updates to daylight savings       Change check reminders let you know when to service  or replace filters       Various Hold options allow you to override the  program schedule  as desired       Controls humidification to increase homeowner  comfort while protecting woodwork and furnishings       Controls dehumidification using air conditioner with  high or low speed fan or a whole house dehumidifier       Controls ventilation with other HRV  ERV  or Freshair  damper  Vent on demand and automatically using  patented advanced ventilation control       Advanced heat pump control featuring balance point  plus temperature droop control to increase  homeowner comfort     Contents  Application Features                        ssssssssseeeneene 1  Specifications Ordering Information                                    2  Installation  1    inier tte to recorre tu 4  Ullal  coan TTE DE 5  Power the Thermostat                   ssssssssssssseeee 8  Installer Setup         ue
28. YSTEM    Set To TITI  IL     HEAT    kc 7h m jut  Permanent  Hold    siens    Humidity            CANCEL    M23507       3  Press Cancel key to cancel  Permanent Hold  and  resume the schedule     VACATION HOLD  Changes temperature setting for a designated number of days   1  Press the Up and Down arrow keys to set the desired  temperature while away on vacation  Notice that  Hold  Temperature Until  time is shown on the screen   This is  the time the Vacation Hold override expires after the  number of days ends    2  Press Hold key twice  Screen shows  Hold Temperature  Until  one day   3  Press Up and Down arrow keys to change the number of  Days you desire thermostat to override the schedule     NOTE  Days Up and Down arrows appear for approximately  Seven seconds  Pressing just below Hold Tempera     ture Until on the screen allows the Days Up and Down  arrows to reappear     Inside   mr    AUTO D d    SYSTEM    Set er pa  a    LL   Cv     Hold Temperature  HEAT Until    DAYS    j    SCHED CLOCK   SCREEN  CANCEL    M23508       4  Tocancel the Vacation Hold override early  press the  Cancel key     NOTE  When the number of days of Vacation Hold expires     the screen shows    Following Schedule    to indicate  that Vacation Hold has ended     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    SOUTHERN DEHUMIDIFICATION AWAY SETTING   Southern Dehumidification Away Setting is an option that only  appears if ISU number 390 is set to yes  It can be used to  maintain 
29. ansformer Common   R 24 Vac Transformer   RC 24 Vac Cooling Transformer   RH 24 Vac Heating Transformer   HUM1 HUM2 Humidification Connection  normally open    DHM1 DHM2 Dehumidification Connection  normally  open or closed based on installer setup    VNT1 VNT2 Ventilation connection  normally open    W1 O B Stage 1 Heating Relay  Conventional   Change over Relay  Heat Pump    W2 AUX Stage 2 Heating Relay  Conventional   Auxiliary Heat  fossil fuel or electric   Heat  Pump    W3 AUX2 Stage 3 Heating Relay  Conventional   Auxiliary Heat  fossil fuel or electric   Heat  Pump    Y Stage 1 Compressor Relay   Y2 Stage 2 Compressor Relay   G Fan Relay   L Heat Pump Equipment Monitor   OUT1 OUT2 Outdoor Temperature Sensor   IN1 IN2 Remote Indoor Temperature Sensor   DATS1 DATS2  Discharge Air Temperature Sensor   68 0287   04 6    NOTES    1  When used in a single transformer system  leave  the metal jumper wires in place between R and Rc   and Rc and Rh  If used on a two transformer sys   tem  remove metal jumper wire between Rc and Rh    2  If thermostat is configured for a heat pump system  in the Installer Setup  configure changeover valve  for cool  O factory setting  or heat  B      For wiring to a W8835 Zone panel please refer to the product  data sheet included with the panel              COMMUNICATION  TERMINALS      24 VAC    CONV  HP  QW OB     w2 AUX   W3 AUX2  Qv v  Qy2 v2  Qc G         COMMUNICATION LED C                                                                F
30. ats  See Fig  33     THERMOSTAT  COOL SETPOINT              PROPORTIONAL COOL  CONTROL POINT    P   CONTROL  a POINT     s PROPORTIONAL HEAT  CONTROL POINT        P   CONTROL POINT E    TEMPERATURE    THERMOSTAT  HEAT SETPOINT                HEATING        COOLING                    100 50 0 50 100  PERCENT LOAD M4414    Fig  33  Proportional temperature control versus P     temperature control     33    VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Minimum Off Timer    The Thermostat has built in compressor protection  minimum   off timer  that prevents the compressor from restarting too  early after a shutdown  The minimum off timer is activated after  the compressor turns off     If there is a call during the minimum off timer  the thermostat  shows    Wait    in the display     Set To Ni  a    v    Inside  Ul   l    AUTO r  I    M aiino   SYSTEM  Schedule    loe    Humidity                pos   HOLD G l       M23513    a    When the minimum off timer expires     Cool On    or    Heat On  appears in the display and the compressor and fan turn on     aHeat Pumps only     Inside Humidity Level  The humidity level in the home is shown in the lower right  corner of the Home Screen     NOTE  If an outdoor temperature sensor is present  the out   door temperature will be displayed in this location  rather than the indoor humidity  To see indoor humid   ity  display the humidity settings menu        TUE    CEAN Inside Tl T    zum   4           AUTO  ic  Followii  SYSTEM  Schedule 
31. c met sexs evens sdncsavacszanscacbaccecces these 12  Soc                        20  Programming MAPE 26    Troubleshooting                        sssssssssesseneeeeneren    68 0287 04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    SPECIFICATIONS    Thermostat Description                                                     Feature Description  Powering method    Common wire only  System types  up to  e Gas  oil or electric heat with air  4 heat 2 cool  conditioning  e Warm air  hot water  high efficiency  furnaces  heat pumps  steam and  gravity  e Heat only with fan    Coolonly  Changeover Manual or Auto changeover selectable  System setting Heat Off Cool Auto  Fan setting Auto On Circ  Electrical Ratings   Terminal Voltage  50 60 Hz    Running Current  W1 Heating 20   30 Vac  02   1 0A  W2 Aux Heating  20   30 Vac  02   1 0A  W3 Aux2 Heating  20   30 Vac  02   1 0A  Y Cooling 20   30 Vac  02   1 0A  Y2 Cooling 20   30 Vac  02   1 0A  G Fan 20   30 Vac  02   1 0A             Temperature Setting Range   Heating  40  F to 90  F 4 5  C to 32  C    Cooling  50  F to 99  F  10  C to 37  C      Operating Ambient Temperature     VisionPRO   IAQ Thermostats  0  F to 120  F      18  C to 49  C      THM5421C1008   30  F to 150  F   34  C to 66  C    C7089U1006   40  F to 120  F   40  C to 49  C      C7189U1005  45  F to 88  F  7  C to 32  C      Shipping Temperature   VisionPRO   IAQ Thermostats   30  F to 150    34  C to 66  C      ARP    THM5421C1008   30  F to 150  F   34  C to 66 
32. cable separate from the thermo   stat cable        Do not route temperature sensor wiring with building  power wiring  next to control contactors or near light  dimming circuits  electric motors or welding  equipment        Avoid poor wiring connections        Avoid intermittent or missing building earth ground      N CAUTION    Electrical Shock Hazard   Can cause electrical shock or equipment damage   Disconnect power supply before connecting wiring     Wiring must comply with applicable codes  ordinances and  regulations     1  Wire C7089U1006 Outdoor Sensor to OUT1and OUT2  terminals on the EIM  If leadwire provided is not long  enough  60 in    run a cable to a hole at C7089U1006  location    a  Using color coded  18 gauge thermostat wire is  recommended  For example of general wiring of  C7089U1006  see Fig  24    b  Pigtail wiring can be used    2  Mount C7089U1006 in its mounting clip    3  Plug wiring hole using nonhardening caulk or putty     A        WIRING HOLE  a THROUGH A    STRUCTURE    TYPE OF STRUCTURE     A PLUG WIRING HOLE WITH NON HARDENING CAULK  OR PUTTY  M23525    Fig  24  Wire C7089U1006 Outdoor Sensor to the EIM   If an outdoor temperature sensor is installed  the thermostat    displays the outside temperature in the lower right corner of the  Home Screen     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    TUE    Inside  Ul   Set To 7   ic    Following  Schedule     Ies     m     Outside  LI  ILI    TRE au             Pee   HOLD   CLOCK m M
33. change the number of cal   endar days    4  Press the Done key to go back to the viewing screen    5  Press the Reset key to activate the new number of days    selected in the previous screen   6  Press the Done key to return to the Home Screen     Temperature Recovery    The thermostat feature  Adaptive Intelligent Recovery      eliminates all guesswork when setting the thermostat schedule     Simply set the program schedule to the time that the comfort  temperature is desired  The thermostat then turns on the  heating or cooling at just the right time to have the home reach  the scheduled temperature at the scheduled time     For example   get up at 6 00 AM and want the temperature to  be 70  F  Set the Wake period for 6 00 AM and 70  F  The  thermostat then turns on the heat before 6 00 AM to raise the  temperature to 70  F by 6 00 AM     The thermostat alerts that the heating or cooling system is  coming on before a scheduled time by showing  Recovery  on  the screen      PAN Inside j  ma   Set To TN    oe    SYSTEM Following  Ss    Schedule  Recovery    HEAT    22     Humidity          V      D   HOLD   E en  MORE             M23512    NOTE  It takes about a week for the thermostat to adjust to  local weather  the schedule  the construction of the  home and the heating and or cooling system  Each  day it adjusts the next day s recovery start time  accordingly     P   Control    The thermostat microprocessor based control requires that the  user understands temperature co
34. ciency  9096 or better  furnaces Default varies based on types of heating   Heat or 2nd 5   5 cph for standard fossil fuel forced air  less  Stage Auxiliary than 90  efficient  systems  9   9 cph used for electric furnaces or electric  auxiliary heat for heat pump systems  2  4  6  7  8  10  11  12   other cycle rate  settings  E Auto Discover  260 CPH for 3rd 1 12 1   1 cph used for steam and gravity Only shown if ISU176   3   Stage Heat 3   3 cph for hot water systems and high Default varies based on types of heating   efficiency  9096 or better  furnaces  5   5 cph for standard fossil fuel forced air  less  than 90  efficient  systems  9   9 cph used for electric furnaces or electric  auxiliary heat for heat pump systems  2  4  6  7  8  10  11  12   other cycle rate  settings  E Auto Discover  270 CPH for 9 Default  Emergency Heat  1 12 Only shown if heat pump is selected   280 Continuous 0 Backlight not on continuously  Thermostat  If backlight is on continuously  it is low intensity   USU Backlight backlight comes on with each key press    Light changes to full brightness after pressing any  1 Backlight is on continuously  key   300 Changeover 0 Manual Auto Changeover allows user to choose heat  cool   1 Auto off or auto  When set to Auto the thermostat will  automatically choose heat or cool based on room  temperature and heat cool set points  Manual  changeover allows the user to manually toggle  between heat  cool and off   310 Deadband 3 2 0  3  F 2 0  C Only shown i
35. e  Installer Setup Number 0172  to match  the installed heating and or cooling equipment        Heating and cooling wires are  shorted together     Separate the shorted heating and cooling wires        Heating equipment is running in  the cool mode     Heating equipment is not a heat  pump but System Type  Installer  Setup Number 0172  is set to Heat  Pump     Set System Type  Installer Setup Number 0172  to match  the installed heating and or cooling equipment        Heating equipment does not turn  off and heat temperature setting  is set below room temperature   Heat On is not in the display      Heating equipment is not a heat  pump but System Type  Installer  Setup Number 0172  is set to Heat  Pump     Set System Type  Installer Setup Number 0172  to match  the installed heating and or cooling equipment        Cannot set the system setting to  Heat     System Type  Installer Setup  Number 0172  is set to Cool Only     Set System Type  Installer Setup Number 0172  to match  the installed heating and or cooling equipment           Cannot set the system setting to  Cool        System Type  Installer Setup  Number 0172  is set to Heat Only or  Heat Only with Fan        Set System Type  Installer Setup Number 0172  to match  the installed heating and or cooling equipment        37    68 0287   04       VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Table 15  Troubleshooting   Continued           Symptom  Heat On is not in the display     Possible Cause  System setting is not set
36. e ventilation setting to Off  The  user can still use the timer to request ventilation     ON DEMAND   User can also set a vent timer that will circulate fresh air into  the home for a set period of time from 20 to 180 minutes in 20   minute increments  The vent timer is enabled whether  ventilation is set to  Auto  or  Off            ie    L Ia     M23519       VENTILATION IN HIGH HUMIDITY CONDITIONS  SETUP FUNCTION 0406   If Ventilation Control is available  setup function 0400 set to 1  or 2   this allows the ventilation equipment to turn on if the  humidity rises approximately 1096 above the RH setting in  heating mode to exhaust the extra humidity     HEAT PUMP OPERATION    Heat Pump LED Indication    A red LED indication is located in the upper right corner of the  thermostat  It is only visible when lighted     When the L terminal is wired to an equipment monitor  the LED  signals when a check or fail signal is sent to the thermostat  from the system  This is operational in the Heat  Off  Cool or  Auto positions     Heat Pump Emergency Heat LED Indication    The thermostat uses a red LED indicator that lights when the  thermostat is in the Emergency Heat mode  The LED is located  in the upper right corner of the thermostat  It is visible only  when on     Heat Pump Temperature Lockouts    Dual Fuel Heat Pump and Outdoor Temperature    Sensor    In this operation  there is no external fossil fuel kit  dual fuel kit   installed  the thermostat controls this function     
37. eat 0 Off  1 Heat Stage 1  2 Heat Stages 1 2  3 Heat Stages 1 2 3  4 Heat Stages 1 2 3 4  Test 4 Emergency Heat Test 0 Off  1 AUX Heat Stage 1  2 AUX Heat Stages 1 and 2  Test 5 Installer Test Humidifier 0 Off  1 Humidifier On  Test 6 Installer Test Dehumidifier 0 Off  1 Dehumidifier On  Test 7 Installer Test Ventilator 0 Off  1 Ventilator On  Err Diagnostic Recall 00 99 See  Communication Error Codes  on page 35  Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer System Test     When VisionPRO   IAQ is used in a zoning system you must exit the installer test on one thermostat before entering the installer    test on another thermostat     OPERATION    Thermostat Keys    SYSTEM  SELECTS EM   HEAT HEAT OFF COOL    FAN  SELECTS  ON AUTO CIRC              Iside ge   1                SYSTEM  HEAT    Imi  woe          DOWN ARROW  LOWERS TEMPERATURE  SETTING    UP ARROW  RAISES  TEMPERATURE  SETTING    srr I  A      d    Following  Schedule       SCHED            SCHED CLOCK   ENTERS SETS THE   SCHEDULING TIME   MODE FORWARD  OR BACK   HOLD   SETS A PERMANENT   HOLD AND ACTIVITIES    VACATION HOLD    68 0287   04    MORE   SHOWS ADDITIONAL  ACCESSORY AND  MAINTENANCE  OPTIONS    SCREEN  LOCKS OUT THE  SCREEN TO ALLOW    FOR CLEANING     v    20    Thermostat Display   TUE INSIDE TEMPERATURE   SHOWS CURRENT DAY SHOWS THE CURRENT INSIDE   OF THE WEEK TEMPERATURE   FAN SET TO   SHOWS FAN TEMPERATURE   SETTING SHOWS THE  C
38. er run time  equipment counts       Counts runtime Cool only             17    68 0287   04       VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                                                                       ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  510 Humidifier Pad  E Auto Discover Display will show Calendar Days if ISU372   0  Run  USU Replacement 0 Disabled Time Days if ISU372   1 or 3   Reminder 1 90 C Days or 30 R T  Days  2 180 C Days or 60 R T  Days  3 365 C Days or 90 R T  Days  520 UV Lamp E Auto Discover  USU Replacement 0 Disabled  Reminder 1 365 Days  2 730 Days  2 years   530 Adaptive 1 Adaptive See Temperature Recovery on page 32   USU Intelligent 0 Conventional  Recovery  540 Number of 4 4 Periods 4 periods   Wake  Leave  Return  and Sleep  USU Periods 2 2 Periods 2 periods   Wake and Sleep  550 Number of 4 4 Periods  Periods  2 2 Periods  Weekdays  560 Number of 4 4 Periods  Periods  2 2 Periods  Weekend Days  580 Min Compressor  5 5 minutes  Off Time 0  1 1 minute  2 2 minutes  3 3 minutes  4 4 minutes  600 Heat Temp 90 Default   90  F  Range Stops 40 90 40  F 90  F  Show 1 2 degree C   610 Cool Temp 60 Default   60  F  Range Stops 60 99 60  F 99  F  Show 1 2 degree C   640 Clock Format 12 12 Hour  USU 24 24 Hour  650 Extended Fan on  0 Off  time Heat  Blower  30 30 seconds  Off Delay Heat   60 60 seconds  90 90 seconds  120 120 seconds  660 Extended Fan on  0
39. f ISU300   0  The deadband indicates  2 1 5  2  F 1 5  C the minimum number of degrees that are allowed  4 25  4 F 25  C between the heat and cool settings when in auto  5 3 0  5  F 3 0  C changeover  For example  if the deadband is set to  6 3 5 GF 35  C ae and a ed setpoint SII the warmest heat  7 40 TF 10  C setpoint allowed would be    8 4 5  8  F 4 5  C  9 5 0  9  F 5 0  C  Note  degrees C is not same as degrees F  320 Temperature 0 Fahrenheit temperature display  USU Indication Scale  1 Celsius temperature display  330 Daylight Saving  2 Enabled  US 2007  Set to 0 in areas that do not follow daylight savings  USU 0 Disabled time   1 Enabled  US 1987                       68 0287   04    14       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                                         ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  340 Indoor Temp 0 Thermostat location only Indoor temperature sensors will display the  Sensor 1 Remote indoor sensor s  location s  only temperature at the sensor location or an average of  2 Average between thermostat and sensor two indoor temperature sensors  not including the  locations temperature sensor in the thermostat  The  temperature sensor in the thermostat is disabled  when using remote indoor temperature sensor s    342 Outdoor Temp E Auto Discover An outdoor temperature sensor is required for heat  Sensor 0 None pump compressor lockout  ISU350   
40. f conventional system with up to M R BI TWEEN RH  three stage heat and two stage cool with one transformer   3H 2C  2H 2C  2H 1C  1H 2C  1H 1C conventional   Hima  M2  D1        EUM  DEHUMIDIFIER   CHANGEOVER       mao  COMMUNICATION LED L   1 ST    COMMUNICATION   CONV  HP  TERMINALS 4 Ly wi oB AUX 1  HEAT 3  M23491  TH FTGW2 AUX H Rx 2 WERT ay        pes H LE ws aux Fig  16  Typical hookup of variable speed blower for  Qv Y compi M dehumidification in low speed  contacts normally closed    Qv v2      Q6 c COMP2 H NOTE  Connect DHM  to low speed fan terminal on air han   dler for dehumidification with air conditioner and a  FACTORY INSTALLED X FAN RELAY f low speed fan   JUMPER BETWEEN R   RC AND RH  A WIRE TO TERMINALS ON THERMOSTAT  M23488       Fig  13  Typical hookup of heat pump system   up to 4H 2C heat pump               k   24 VAC  POWERED  H OR  FIELD INSTALLED DEHUMIDIFIER Z  JUMPER BETWEEN    R AND HUM 1                      HUMIDIFIER  OR    Fig  17  Typical hookup of powered whole house  dehumidifier  contacts normally open         M23489    Fig  14  Typical hookup of non powered humidifier     7 68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM              FIELD INSTALLED  JUMPER BETWEEN  R AND VNT 1                   NON POWERED  VENTILATOR    Fig  18  Typical hookup of fresh air damper           M23493    NOTE  Use this hookup for ventilation using a fresh air  damper                       M23494       Fig  19  Typical hookup of powered ventilation   
41. fying in this manner runs the air conditioner longer  than simply cooling the house would require  and can be set to  run 1  2  or 3  F below the temperature setpoint  This feature is  called Dehumidification Droop Control     NOTE  You must use this setting if       No powered  whole house dehumidifier is present   and        The system uses the air conditioner as the  dehumidifier     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    DEHUMIDIFICATION DROOP CONTROL   In extremely high humidity conditions  the thermostat keeps  the air conditioner running  energizing Y Y2 and G  for up to  3  F below the temperature setpoint  It does this while trying to  achieve the desired humidity setpoint and balancing that with  the temperature setpoint  The thermostat controls up to 3   F  below the temperature setting until either the humidity setpoint  is satisfied or conditions change     With Whole House Dehumidifier    Controls humidity levels in the house by dehumidifying without  the use of the air conditioner  This setting requires a dedicated  unit for dehumidification  Dehumidification with a whole house  dehumidifier will take place when the thermostat is in the Cool   Off  Auto  Heat or Em Heat modes  If the system is installed  with a whole house humidifier  dehumidification with a whole  house dehumidifier will only take place when the thermostat is  in Cool  Off or Auto modes  Auto only if the previous call was a  call for cooling      When controlling a whole h
42. g a locked key  while Screen Locked is  shown  flashes  Screen Locked  on the screen     In this mode  all keys are locked except the Temperature Up  and Down arrow keys         User can change temperature up or down but cannot  change schedule settings        Temporary temperature change lasts until next scheduled  period and that time shows on screen        To cancel temperature override and begin following  schedule  press Cancel key        To unlock screen  see Installer Setup section     Fully Locked Screen   In this mode  all keys are locked and not functional  To unlock  Screen  see Installer Setup section  The screen continuously  displays  Screen Locked      Humidification Control    If you have a humidifier and outdoor temperature sensor  you  can use Frost Control to reduce window condensation     1  Press MORE until the humidifier screen is displayed    2  Press the Up or Down arrow to set the humidity and  Frost Control level   Use a lower Frost Control level if  frost appears on windows  Use a higher setting if the air  is too dry     3  Press DONE to save and exit  or press CANCEL to exit  without saving changes    NOTE   f you do not have an outdoor temperature sensor  the  Frost Control level will not be displayed     Dehumidification Control    If installed to control a dehumidifier  the thermostat can activate  it as needed to reduce humidity     If you don t have a dehumidifier  the thermostat activates the  air conditioner to reduce humidity  may cool as 
43. g terminals  Use an ohmmeter to measure  the resistance across the sensor  Then verify the sensor  accuracy with the temperature resistance in Table 13     VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 13  Sensor Resistance at Room Temperature                             Room Room  Temperature Ohms of Temperature Ohms of    F   C Resistance   F   C Resistance  64 17 8  13161 96 35 6  6813  66 18 9  12607 98 36 7  6551  68 20 0  12081 100 37 8  6301  70 21 1 111578                             COMMUNICATION ERROR CODES    VisionPRO   IAQ can alert the homeowner and installer to  problems with the HVAC equipment  thermostat  or equipment  interface module by using error codes  Please see Table 14 for  a list of error codes  When an error is active  the condition  causing the error is still present  it will be displayed in the time  field on the thermostat home screen  The home screen can  display up to 5 active errors  The time field will flash the time      Err     and a list of up to 5 error codes  beginning with the most  critical  and repeat until the errors have been remedied     A log of error codes can be viewed at the end of the installer  setup after the system tests  Active errors will be shown first   The Error Log will log the last ten errors  active and inactive    Pressing the reset button will clear all inactive errors from the  error log  active errors can not be cleared until the condition  has been remedied                                                  
44. g wallplate     Installing Equipment Interface Module  EIM      N CAUTION    Electrical Hazard   Can cause electrical shock or equipment damage   Disconnect power before wiring     The EIM can be mounted vertically on the HVAC equipment or  on a wall in the equipment room     1   2   3     Position the EIM    Use a pencil to mark the mounting holes    Remove the wallplate from the wall and  if drywall  drill  two 3 16 in  holes in the wall  as marked  For firmer  material such as plaster  drill two 7 32 in  holes  Gently  tap anchors  provided  into the drilled holes until flush  with the wall    Position the wallplate over the holes  pulling wires  through the wiring opening    Insert the mounting screws into the holes and tighten   See Fig  8     Communication LED    The EIM has an LED  see Fig  8  that communicates the EIM  status as follows     LED blinks rapidly  Normal information transfer   LED blinks once  Incoming message to EIM   LED blinks continuously  Wiring problem  Check wiring to    terminals 1  2  3     LED always off  Wiring problem  Check wiring to terminals  1 2 3   LED always on  EIM may need replacement     NOTE     VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    It is normal for the LED to blink continuously during  startup  and while checking equipment status  Auto  Discover mode           WALL ANCHOR    COMMUNICATION LED    DRILL 3 16 IN  HOLES  FOR DRYWALL  DRILL  7 32 IN  HOLES FOR  PLASTER                                                       MOUNTING
45. ge Temperature  Temperature 50 60 50  F to 60  F  10  C to 15 5  C  Sensor present   Low Limit  370 Indoor Humidity  1 Internal   sensor in thermostat If there is a remote sensor installed and the setting  Sensor 0 Disabled is either auto discover or  remote  the internal  2 Remote thermostat humidity sensor is disabled  If set to  E Auto Discovered  internal  the internal thermostat sensor is  presented on the screen  If set to  disabled  the  internal sensor and any remote sensors are  disabled  there will be no humidity displayed and will  have no humidification dehumidification control   372 Indoor E Auto Discover  Humidification 0 Shown only if ISU370   1  2 or E   Control 1 Humidify  no frost protection   3 Humidify  with frost protection   8 Desert Humidity Control on heat  cool  and off    DATS required for Desert Humidification   no frost protection    9 Desert Humidity Control on heat  cool  and off   with frost protection    374 Hum Fan Action  0 Humidify only while fan or heat is on Setting O will run the humidifier only during a call for  1 Humidify will force fan on heat or if the fan is running   2 Humidify only when heat is on Setting 1 will force the fan to run if there is a call for  3 Humidifier operates independent of fan humidification   Setting 2 will humidify only during a call for heat   Setting 3 assumes the humidifier has it own internal  fan and will not require the system fan or heat to be  operating during a call for humidification   379 Dehumidif
46. h the temperature resistance in Table 12     Calibration  The C7089U1006 Outdoor Sensor is calibrated at the factory    and cannot be recalibrated in the field     68 0287   04 34    Table 12  Sensor Resistance at  Outdoor Temperature                                                                                                                                Outdoor Outdoor  Temperature Ohms of Temperature Ohms of    F   C Resistance   F   C Resistance   20    28 9 106926 52 11 1 17136   18    27 8 100923 54 12 2 16387   16    26 7 95310 56 13 3 15675   14    25 6 90058 58 14 4 14999   12    24 4 85124 60 15 6 14356   10    23 3 80485 62 16 7 13743   8  22 2 76137 64 17 8 13161   6  21 1 72060 66 18 9 12607   4  20 0 68237 68 20 0 12081   2  18 9 64631 70 21 1 11578  0  17 8 61246 72 22 2 11100  2  16 7 58066 74 23 3 10644  4  15 6 55077 76 24 4 10210  6  14 4 53358 78 25 6 9795  8  13 3 49598 80 26 7 9398  10  12 2 47092 82 27 8 9020  12  11 1 44732 84 28 9 8659  14  10 0 42506 86 30 0 8315  16  8 9 40394 88 31 1 7986  18  7 8 38400 90 32 2 7672  20  6 7 36519 92 33 3 7372  22  5 6 34743 94 34 4 7086  24  4 4 33063 96 35 6 6813  26  3 3 31475 98 36 7 6551  28  2 2 29975 100 37 8 6301  30  1 1 28558 102 38 9 6062  32 0 0 27219 104 40 0 5834  34 1 1 25949 106 41 1 5614  36 2 2 24749 108 42 2 5404  38 3 3 23613 110 43 3 5203  40 4 4 22537 112 44 4 5010  42 5 6 21516 114 45 6 4826  44 6 7 20546 116 46 7 4649  46 7 8 19626 118 47 8 4479  48 8 9 18754 120 48 9 4317  50 10 0 17926
47. he installer set up  It is not  recommended to use Auto Discover with an equipment  interface module     When using the VisionPRO   IAQ thermostat with a W8835  zone panel  configure the zone panel  using the DIP switches  on the panel  for the proper system settings  Enter the installer  setup on each thermostat and assign zone numbers  and  change the system settings  ISU 172   180  to Auto Discover   E  then press the discover button on the zone panel  The zone  panel will then communicate those settings back to the  thermostats and the thermostats will automatically configure  the ISU settings in Auto Discover  again it is important to verify  that the auto discovered values are correct     NOTE  When a VisionPRO   IAQ thermostat is being added  to an existing zoning system with T8635 Thermostats  the new VisionPRO   IAQ must be set up as the Zone  One Thermostat  master zone controller   and can  only be used with a W8835 zone panel     Follow these steps to enter the Installer Setup     68 0287   04 12    Press and release the System Key           Following  Schedule    2o    Humidity    WALI  ILE d 10M        scie   HOLD caka                     M23498    Press and hold the two blank keys on either side of the  center blank key for approximately five seconds until  screen changes                 Tu    Inside y          Set  7 TI A   I          LL   v     Following  Schedule    zi    Humidity                Release the two blank keys when the screen on the ther   mostat
48. heat pump  1 Yes auxiliary lockout  ISU360   dual fuel heat pump  balance point  ISU360  and Humidification with  Frost Protection  ISU372    345 Dual Fuel Heat   1 Droop Control See Dual Fuel Heat Pump control on page 23   Pump Control 0 No Droop Control  2 Droop Control with Auxiliary heat lockout  346 Dual Fuel Heat  1 1 hr  See Dual Fuel Heat Pump control on page 23   Pump Upstage to  0 Disabled  Furnace Timer  in  0 5 0 5 hrs   hours  1 5 1 5 hrs   2 2 hrs   3 3 hrs   4 4 hrs   5 5 hrs   6 6 hrs   8 8 hrs   10 10 hrs   12 12 hrs   14 14 hrs   16 16 hrs   347 Droop 2 2  F 1 0  C The fossil fuel will turn on when the outdoor  Temperature 3 3  F 1 5  C temperature is above the balance point if the room  4 4  F 20  C temperature droops below the selected droop  5 5  F 25  C temperature setting  and the compressor will be     disabled   350 Heat Pump 40 4 5  40  F 4 5  C Only shown for heat pump applications with an  Balance Point 0 No heat pump compressor lockout outdoor temperature sensor present    also compressor  5  15  5  F  15 0  C If electric backup is selected then the default is No  lockout  10  12 MO F  12 0  C Compressor lockout   Temperature 15  95 M5 F  9 5 C  20  6 5  20  F  6 5  C  25  4  25  F  4 0  C  30  1  30  F  1 0  C  35 1 5  35  F 1 5  C  45 7  45  F 7 0  C  50 10  50  F 10 0  C  55 13  55  F 13 0  C  60 15 5  60  F 15 5  C   Show 1 2 degree C   360 Heat Pump 0 No heat pump auxiliary lockout Only shown for heat pump applications with an  Auxiliary Heat
49. ication  0 None Option 1 uses dehum terminal as a normally closed  Control 1 Dehumidify with Air Conditioning relay to wire to a low speed fan terminal   3 Whole house Dehumidifier Option 3 uses dehum terminal as a normally open  relay to wire to a whole house dehumidifier   382 Dehumidification  0 Dehumidifier in Cool or Auto  when last call  System modes was for cooling   Dehumidifier in Cool  Off  Heat  EmHeat  or  Auto  3 Dehumidifier in Cool  Off  or Auto  when last  call was for cooling   383 Over Cooling 3 1 5  3  F 1 5  C Only shown if ISU379   1   Limit 1 0 5  1  F 0 5  C  2 1 0  2  F 1 0  C   Show 1 2 degree C   384 Dehumidification  0 System fan turns on with dehumidifier Only shown if ISU379   3   Fan Action 1 Dehumidifier operates independent of system  fan  386 Whole house 0 Disabled  dehumidification  1 Enabled  lockout  390 Southern 0 No Not shown if ISU379   0   Dehumidification  1 Yes ISU 391 394 will only be shown if ISU390   1   Away Mode  391 Southern 0 Fan Auto If ISU391   1 or 2 to help remove condensation  Dehumidification  1 Fan On from the air handler and the A coil  some humidity  Away Mode Fan 2 Fan Circulate may be re introduced into the living space   Setting  392 Southern 76 Default   76  F The air conditioner will be allowed to cool the living  Dehumidification  70 80 70 F 80 F space to this temperature to meet the humidity  Away Mode Low setting that set in ISU394   Limit  Temperature  Setting  393 Southern 85 Default   85  F The A C will main
50. ify the product operation     Selecting Location    Install the thermostat about 5 ft   1 5m  above the floor in an area  with good air circulation at average temperature  See Fig  6                     1 5 METERS            M19925    Fig  6  Selecting thermostat location     68 0287   04 4    Do not install the thermostat where it can be affected by        Drafts or dead spots behind doors and in corners        Hot or cold air from ducts        Radiant heat from sun or appliances        Concealed pipes and chimneys        Unheated  uncooled  areas such as an outside wall behind  the thermostat     Installing Wallplate     N CAUTION    Electrical Hazard   Can cause electrical shock or equipment damage   Disconnect power before wiring     The thermostat can be mounted horizontally on the wall or on a  4 in  x 2 in   101 6 mm x 50 8 mm  wiring box     1  Position and level the wallplate  for appearance only     2  Use a pencil to mark the mounting holes    3  Remove the wallplate from the wall and  if drywall  drill  two 3 16 in  holes in the wall  as marked  For firmer  material such as plaster  drill two 7 32 in  holes  Gently  tap anchors  provided  into the drilled holes until flush  with the wall     4     5           Position the wallplate over the holes  pulling wires  through the wiring opening  See Fig  7   Insert the mounting screws into the holes and tighten   WALL  WIRES THROUGH WALL  AND WIRE SLOT  a  Na  Ss  MOUNTING  HOLES  MOUNTING  SCREWS  2     Fig  7  Mountin
51. ing or fan  The thermostat screen  shows the time  inside temperature  system and fan selections   Additional indicators are shown when the heating  cooling or  fan is energized  See Table 5 and 6 for specification    information     Table 5  Sequence of Operation for Conventional Systems                                         System Setting Fan Setting Call for Action Energize Terminals Screen Message  Off Auto None None  Cool or Auto Auto None None  Cool or Auto Auto Stage 1 Cooling Y G Cool On  Cool or Auto Auto Stage 1 and Stage 2 cooling Y  Y25  G Cool On  Heat or Auto Auto None None  Heat or Auto Auto Stage 1 heating W1  G  Heat On  Heat or Auto Auto Stage 1 and Stage 2 heating W1  W2    Ge Heat On  Heat or Auto Auto Stage 1  Stage 2 and Stage 3 heating w4  w2    W39  Ge Heat On         G energizes only if Installer set up number 180 is set to Option 1  Electric Heat       gt  If installer setup  ISU174  is configured for two stages of cooling       If installer setup  ISU 176  is configured for two or more stages of heating   d If installer setup  ISU 176  is configured for three stages of heating      G energizes only if Installer set up number 180 is set to Option 1  Electric Heat  or 2  Hot water coil      Table 6  Sequence of Operation for Heat Pump Systems                                                        System Setting  Fan Setting Call for Action Energize Terminals Screen message  Off Auto none O B  None   Cool or Auto Auto none O B None   Cool or Auto Aut
52. le period  press arrow keys to  set desired time and temperatures     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM       Cere we  wo     sss   Y     a  tv                                WAKE   LEAVE ER SLEEP    CANCEL    M19957       OK TO PICK MULTIPLE DAYS            DONE            7  Press Done key     Fan Schedule   Press Fan key while in the Scheduling Screen to program the  System Fan  Choices available from the Scheduling Screen   Auto  default position    fan runs with equipment   Programmable for all schedule periods  Wake  Leave  Return  and Sleep     On   fan runs continuously  programmable for all schedule  periods     Circ   fan runs randomly for approximately 3596 of schedule  period  programmable for all schedule periods          v won  v ne   V WED   V THU lv FRI   SAT   SUN    OK TO PICK MULTIPLE DAYS       mm  a  Il HEAT  BOO            v     e fime fm mm oes    M22447          Loc     Fan Control   If the Fan program is scheduled  Auto is shown and any  programmable mode that is set  for example  if during Wake  period  Fan is set to Auto  only Auto is shown in the Fan area   However  if during the Wake period  fan is scheduled to On   both Auto and On are shown  Auto indicates fan is running its  schedule  On indicates Fan schedule is set to On           m s  md DR       i 0J    SYSTEM Following    Schedule    HEAT    W  07    m  ILE d  0          Humidity       M      E              M23505    68 0287   04 28    Table 10  Fan Program Operation
53. much as 3  F  lower than your temperature setting      VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    1  Press MORE until the dehumidifier screen is displayed  1  Press the More key until the filter reminder appears on  2  Press the Up or Down arrow to set the desired humidity the screen  This is the number of fan run time or calen   level and operation  Auto or Off   dar days remaining on the filter reminder     3  Press DONE to save and exit  or press CANCEL to exit  without saving changes     Ventilation Control PER  You can ventilate your home at any time   1  Press MORE until the ventilation screen is displayed   2  Press the Up or Down arrow to set the ventilation timer   You can set the timer to ventilate from 20 to 180 minutes     in 20 minute increments  To turn off the ventilator  select or DAYS  0  a  3  Press DONE to save and exit  or press CANCEL to exit aE  without saving changes    GERE   Ent     FA  M22449             If programmed for auto ventilation by the installer  the    thermostat will ventilate your home as needed   Press the Edit key            Use the Up and Down keys to change the number of run   Indoor Air Quality Reminders time or calendar days     an    Filter Change Reminder   The filter change reminder must be turned on from the Installer  Setup  Once expired  the screen flashes     Change Filter    and a  Reset key appears  Press the Reset key to reset the change  reminder  The installer can configure the Filter Change  Reminder to display remai
54. n  and emergency heat for heat pump systems       N CAUTION    Equipment Damage Hazard    Minimum compressor off time is bypassed during  Installer System Test   Avoid cycling compressor quickly     How to Use the Installer System Test    The Installer Test is part of the Installer Setup Menu     1     2     Enter the Installer System Test by entering the Installer  Setup    Note that the test appears at the end of the Installer  Setup Numbers    See Fig  28 to review how the thermostat buttons are  used during the Installer System Test  See Table 6 for  available Installer System Tests    If installed with a Discharge Air Temperature Sensor   ISU365 1  press the    MORE    button to view the dis   charge temperature  and press Cancel to return to the  Installer test screen     19          TURNS THE  SYSTEM ON    NUMBER    NUMBER    SYSTEM po SYSTEM STATUS p UP ARROW                            DONE KEY UP ARROW KEY    DOWN ARROW  EXITS INSTALLER ADVANCES TO TURNS THE  SYSTEM TEST NEXT SYSTEM SYSTEM OFF   TEST NUMBER M22428    Fig  28  Review thermostat buttons used during Installer    System Test     68 0287   04    VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Installer System Tests    Table 4  Installer System Test                                               System Test Number Test Type ISU Value System Status Number and Description  Test 1 Installer Test Cool 0 Off  1 Cool Stage 1  2 Cool Stages 1  amp  2  Test 2 Installer Test Fan 0 Off  1 Fan On  Test 3 Installer Test H
55. n  the EIM  if the connection is good replace the EIM        68 0287   04    36       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 15  Troubleshooting   Continued           Symptom    Cooling does not turn on   Cool  On    is solid in the display     Possible Cause  Cooling Equipment failure    Action    Check for 24 Vac at the equipment on the secondary side  of the transformer between power and common  If voltage  is not present check the cooling equipment to find the  cause of the problem    Check for 24 Vac between the cool terminal s  on the  equipment interface Module and transformer common  If  present check cooling equipment to find the cause of the  problem        Loose or broken wire connection  between Equipment Interface  Module and cooling equipment     Check for 24 Vac between the cool terminal s  on the  cooling equipment and system transformer common  If  voltage is not present check for loose or broken wires  between the EIM and cooling equipment        Communication is not being  completed    End the call for cool at the thermostat then repeat the call  for cool  Check the communication LED on the EIM board   If the LED does not blink  check communication  wiring  wire between terminal 1 on both the EIM  and thermostat    If the LED does blinks correctly  check for 24 Vac  between heating terminals on the EIM and the sys   tem common    If 24 Vac is not present check the R to Rh connection on  the EIM  if the connection is good replace the EIM        2
56. nd so on  and the displayed temperature will be an  average of the temperatures measured at each location      The thermostat will display a 50 50 average of the  temperature measured at the thermostat location and the  average of the temperatures measured at the remote indoor  sensor locations  In this case  the thermostat sensor still  carries a 5096 weighting of the displayed temperature     Install Discharge Air Temperature Sensor   Optional    Prior to installing Discharge Air Temperature Sensor  DATS     refer to the installation instructions included with the product for  more information on placement and wiring     When using a DATS with network zoning the DATS will monitor  the duct air temperature and communicate with the thermostat  and will disable the heating and or cooling if installer set high or  low temperature limits are reached     When using a DATS with an Equipment Interface Module the  DATS is for testing only  When the installer is in any of the  Installer Tests pressing the  More  button will display the  temperature measured at the DATS  This allows the installer  to view the temperature of each stage of heating and or  cooling  The DATS will not be used for control and will not  disable heating or cooling based on duct air temperature     Set Calendar and Time    Thermostat keeps current time and day for up to ten years  under normal use after the calendar is set     When the thermostat is first powered  the display is ready to  set the calendar and 
57. nd stage heat or cool does not  energize    Stage configuration is not set  correctly to match the number of  selected stage    Set the stage configuration in installer setup for additional  stages of cool  ISU 174  or additional stages of heat  ISU  176         Terminals not connected properly at  EIM    Check that 24 Vac is present at W2 AUX and W3 AUX  for  2nd and 3rd stages of conventional heating and for 3rd and  4th stages of heat pump heating  Also check that 24VAC is  present at Y2 for 2nd stage of cooling or 2nd stage heat in  heat pump applications           Err    appears in time field of  home screen on thermostat    Thermostat has detected an error  on the communication bus    Refer to error code section for more information        Fan does not turn on in a call for  heat  electric furnace      Fan Control in Heating is set to Gas  or Oil Furnace  Setting 0180      Set Fan Control in Heating to Electric Furnace  Setting  0180         Heat pump puts out cool air in  the heat mode and warm air in  the cool mode     Changeover Valve  Installer Setup  Number 0190  is not configured to  match the changeover required by  the installed heat pump     Set Changeover Valve  Installer Setup Number 0190  to  match the changeover required by the installed heat pump        Both the heating and cooling  equipment are running at the  same time     The heating equipment is not a heat  pump but the System Type  Installer  Setup Number 0172  is set to Heat  Pump     Set System Typ
58. ning run time or calendar days     FILTER    TUE    Fan   CHANGE FILTER     a   Fm Set To   l  AUTO LIL  w     Following   SYSTEM  Schedule          M22450    4  Press the Done key to go back to the viewing screen   HEAT  II   pa      Humidity             FILTER    Ga   HOLD Jess  ie MORE            M23511    RESET    NOTE  When using run time days  the days are counted as             fan run time  so anytime the fan is running  the rn  reminder is counting that time against the number of  ILI  days selected   MORE  The remaining days can be viewed by pressing the More key  DONE   EDIT     iP  the remaining days can be edited using the More key or from M22449    the Installer Setup  To view or reset the reminder before it  expires  follow these steps using the More key     31 68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    5  Press the Reset key to activate the new number of days  selected in the previous screen     FILTER    RESET    2n  Iii    MORE  DONE EDIT CANCEL    M22451    DAYS       6  Press the Done key to return to the Home screen     Humidifier Pad Reminder    The Humidifier Pad change reminder must be turned on from  the Installer Setup  Once expired  the screen flashes     Change  Humidifier Pad    and a Reset key appears  Press the Reset key  to reset the change reminder     The remaining calendar or run time days can be viewed by  pressing the More key  The remaining days can be edited  using the More key or from the Installer Setup     HUMIDIFIER 
59. ntrol and thermostat  performance  A conventional mechanical or electronic  thermostat does not control temperature precisely at setpoint   Typically there is an offset  droop  in the control point as the  system load changes  This is a phenomenon that most people  in the industry know and accept  Many factors contribute to  offset including switch differential  thermal lag  overshoot  cycle  rates and system load     The thermostat microprocessor simultaneously gathers   compares and computes data  Using this data  it controls a  wide variety of functions  The special proprietary algorithm   program  in the thermostat eliminates the factors causing  offset  This makes temperature control more accurate than the  conventional mechanical or electronic thermostats  The  temperature control algorithm is called proportional plus  integral  P 1  control     The thermostat sensor  located on the thermostat or remote   senses the current space temperature  The proportional error  is calculated by comparing the sensed temperature to the  programmed setpoint  The deviation from the setpoint is the  proportional error     The thermostat also determines integral error  which is a  deviation based on the length of error time  The sum of the two  errors is the  P I  error  The cycle rate used to reach and  maintain the setpoint temperature is computed using the P    The addition of the integral error is what differentiates the  thermostat from many other electronic and mechanical  thermost
60. o Stage 1 cooling Y  G  O B Cool On  Cool or Auto Auto Stage 1 and Stage 2 cooling Y  Y2   G  O B  Cool On  Heat or Auto Auto none O B8 None   Heat or Auto Auto Stage 1 heating Y  G  O B  Heat On  Heat or Auto Auto Stage 1 and Stage 2 heating Y  Y2    G  O B  Heat On  Heat or Auto Auto Stage 1  Stage 2 and Stage 3 heating yf  Y2  f AUX     G  O B Aux Heat On  Heat or Auto Auto Stage 1  Stage 2  Stage 3 and Stage 4 heating yf y2cf AUxd  AUX2    G  O B2 Aux Heat On  Em Heat  Auto None O B  None  Em Heat  Auto Stage 1 Heating AUX     G  O B  Aux Heat On  Em Heat  Auto Stage 1 and Stage 2 heating AUX  AUX2    G  O B  Aux Heat On         Configure O B in Installer Setup  Based on last piece of equipment called  cooling   O or Heating   B     gt  Red LED is on  See LED indication section for more details  page 22        If installer setup  ISU 174  is configured for 2 compressor stages     d If installer setup  ISU 176  is configured for one or more stages of Auxiliary Heat      If installer setup  ISU 176  is configured for two stages of Auxiliary Heat   f If thermostat is controlling backup heat  see temperature lockout section  page 23      68 0287   04          VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 7  Indoor Air Quality Operation                                                  Last call Energize  System Setting Call For Action Heat Cool terminals  Auto Humidification HUM1 and HUM2 Close    Nothing  None  Auto Dehumidification Nothing  DHM1 and DHM2 close  None  Au
61. one Controller  zone 1 thermostat     Table 20  UV Lights          UV100E2009  UV100E1043  UV100E3007                   39 68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    Automation and Control Solutions  Honeywell International Inc    1985 Douglas Drive North   Golden Valley  MN 55422    Honeywell Limited Honeywell Limit  e  35 Dynamic Drive   Toronto  Ontario M1V 4Z9  customer honeywell com    Honeywell       U S  Registered Trademark       2011 Honeywell International Inc    US Patent No  6 208 263  6 373 376  6 448 901  6 926 076   7 044 397  D509151  H25192  H25193 and other patents pending  68 0287   04 M S  Rev  03 11   Printed in U S A     
62. ooling does not  come on and thermostat is  calling for heat or cool     Heat does not turn on     Heat On   is solid in the display        Heating or cooling equipment is not  operating    Heating Equipment failure    Check Wiring    Check installer setup number 172 and verify the correct  system type is chosen    Verify operation of equipment in system test mode     Check for 24 Vac at the equipment on the secondary side  of the transformer between power and common  If voltage  is not present check the heating equipment to find the  cause of the problem    Check for 24 Vac between the heat terminal s  on the  equipment interface Module and transformer common  If  present check heating equipment to find the cause of the  problem        Loose or broken wire connection  between Equipment Interface  Module and heating equipment     Check for 24 Vac between the heat terminal s  on the  HVAC equipment and system transformer common  If  voltage is not present check for loose or broken wires  between the EIM and heating equipment           Communication is not being  completed       End the call for heat at the thermostat then repeat the call  for heat  Check the communication LED on the EIM board   If the LED does not blink  check communication  wiring  wire between terminal 1 on both the EIM  and thermostat    If the LED does blinks correctly  check for 24 Vac  between heating terminals on the EIM and the sys   tem common    If 24 Vac is not present check the R to Rh connection o
63. ouse dehumidifier the user can    toggle between auto  dehumidify when needed based on  setpoint and current humidity level  and off  see Fig  29      Inside     06  IL     DEHUMIDIFIER     v     7 Joes    M23515    a o A  woo  v  zl  Esse    I I    rr             Fig  29  Display when controlling a whole house  dehumidifier     1  Press the More key until the inside humidity percent and  dehumidification setpoint are shown    2  Use Up and Down arrow keys  located to the right of the  dehumidifier setpoint  to set desired humidity level for  dehumidification in the summer    3  Press Done key     Ventilation Control    Ventilation setup options include ISUs 400  401  402  403  and  404  Combined  these will determine a percentage of  maximum ventilation limit  The thermostat will calculate  whether or not this level of ventilation meets ASHRAE  standard 62 2  If ASHRAE 62 2 is met a P will appear in the  display above the setup number  If ASHRAE 62 2 is not met an  F will appear in the display above the setup number     Passing ASHRAE 62 2 is only applicable when vent is running   For example  if installer has set to not vent during sleep period   ASHRAE 62 2 would be met at all times except during sleep  period     68 0287   04 22    FN HI  aj  LI IId  w   i  1 1  J    Ventilation occurs two ways              M23520    AUTOMATIC   Uses installer setup to determine amount of ventilation  required based on house and equipment size  To disable  automatic ventilation  switch th
64. r  Optional     Mount the sensor where  see Fig  23       cannottamper with settings    there is good air circulation    it can measure true outdoor ambient temperature   surface is flat    wire distance between C7089U1006 and EIM is less than  200 feet     Do not mount the sensor      jn direct sunlight      where hot or cold air blows on the sensor  Discharge line  from an outdoor compressor unit  vent or fan causes  inaccurate temperature readings      where snow  ice or debris can cover it     Use the following steps to mount the sensor   1  Remove the sensor from the mounting clip   2  Markthe area on the location selected for mounting the  sensor mounting clip   3  Mount the clip                                      M7514    Fig  23  Typical locations for C7089U1006 Outdoor Sensor     Wire C7089U1006 Outdoor Sensor     N CAUTION    Electrical Interference  Noise  Hazard    Can cause erratic system operation    Keep wiring at least one foot away from large inductive  loads such as motors  line starters  lighting ballasts and  large power distribution panels    Use shielded cable to reduce interference when  rerouting is not possible     VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    IMPORTANT  Erratic temperature readings from a sensor can occur  as a result of any of the wiring practices described  below  Avoid these practices to assure correct opera   tion  Use shielded cable to reduce interference if  rerouting sensor wiring is not possible         Be sure wires have a 
65. r 200cfm with built in defrost  ER150B2006   energy recovery ventilator 150cfm with built in defrost          ER150C2004   energy recovery ventilator 150cfm with no defrost  ER200B2006   heat recovery ventilator 200cfm with built in defrost  ER200C2004   heat recovery ventilator 200cfm with no defrost    EARD5   5  round damper NC Power Open Sping Close        EARD6   6    round damper NC Power Open Spring Close  EARD7   7  round damper NC Power Open Spring Close                EARD8   8  round damper NC Power Open Spring Close             Following is a list of compatible communicating products   Table 19  Communicating Products          THM5421C   Equipment Interface Module Universal up to 4H2C systems  T8635L1013    3H3C communicating Thermostat  W8635A1006   Equipment Interface Module for 2H2C conventional systems  W8635B1004   Equipment Interface Module for 2H2C heat pump systems  W8735A1005   EnviraCOM Serial Port Adapter   W8735B1003    Telephone Access Module   W8735D1009    Telephone Access Module two Channel communicating                         W8735D1017    Telephone Access Module four channel communicating  W8835A1004   Envirazone Zone Panel   C7835A1009   Communicating Discharge Air Sensor  W8703A1003   Damper Interface Module   L7224C1004   120VAC Electronic Aquastat   L7248   Aquastat   R7184   Oil Primary                                 T8635L thermostats used with TH9421C thermostats must be used with a W8835A Zone Panel and the TH9421C must be the  Master Z
66. s Only shown if ISU172   2   O B energized in cooling  1 Changeover valve   O B terminal is energized  in heating  200 Back up Heat E Auto Discover Only shown if ISU172   2 and ISU176   1 or  Source Applies to  0 Electric backup heat greater   both Aux and 1 Fossil fuel backup heat  EmHeat  210 External Fossil  1 External Fossil Fuel kit controls backup  Cannot control dual fuel when used with W8835  Fuel Kit 0 heat  Envirazone Panel   Thermostat controls backup heat Only shown if ISU172   2 and ISU200   1   220 CPH for 1st 1 6 3   cph recommended for compressors  Stage Cool  1  2  4  5  6   other cycle rate settings  Compressor E Auto Discover  230 CPH for 2nd 1 6 3   cph recommended for compressors Only shown if ISU174   2   Stage Cool  1  2  4  5  6   other cycle rate settings  Compressor E Auto Discover  240 CPH for 1st 1 12 1   1 cph used for steam and gravity Only shown if ISU172   2 and ISU176   1 or higher   Stage 3   3 cph used for hot water system and high   Default varies based on types of heating   Conventional efficiency  9096 or better  furnaces  Heat or Auxiliary 5   5 cph used for standard fossil fuel forced  air  less than 80  efficient  systems  9   9 cph used for electric furnaces  2  4  6  7  8  10  11  12   other cycle rate  settings  E Auto Discover  250 CPH for 2nd 1 12 1   1 cph used for steam and gravity Only shown if ISU176   2 or for Heat Pump systems  Stage 3   3 cph for hot water systems and high with 2 stages of Auxiliary Heat   Conventional effi
67. t  is selected     27    VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    5  Press Up and Down keys to modify time and heat and  cool temperatures from this screen     NOTE  The Fan setting can be programmed for On  Auto  or  Circ for each period selected  See Fan Schedule sec   tion for more information     Press Leave key and repeat step 5    Press Return key and repeat step 5    Press Sleep key and repeat step 5    When complete  press Done key     Saving Changes     appears on the screen to indicate changes are being  saved to the day s  modified      9 0 wm    SAVING    CHANGES       LIII     To set a Program Schedule for the remaining days of  the week  repeat steps 1   9  Example  If Mon Fri was  selected first  go back and repeat steps 1   9 for Sat  and Sun        M19956    NOTE     10  To exit schedule without saving changes  press Cancel  key any time     Cancel a Schedule Period    Press Sched key    Press Edit key    Select the Day s  of the week desired    Press schedule period you want to cancel  Wake  Leave   Return or Sleep   Once selected  the period flashes   Press Cancel Period key     m PONS        v mon  v me I Y WED vm   Y FRI   SAT   SUN  OK TO PICK MULTIPLE DAYS i       r    oc    I  m Z ES    Ir LILI ZIZI  o    DONE WAKE    LEAVE   RETURN   SLEEP   CANCEL    M22446             6  The time  temperature s  and fan setting disappear  The  bar above the selected period is removed  indicating the  scheduled period was cancelled     NOTE  To reinstate a schedu
68. t Lockout Plus Droop   ISU 345   2    When the outdoor temperature is above the Auxiliary Heat  Lockout Temperature only the compressor operates  below the  balance point temperature  setup function 0360  only the fossil  fuel operates  Between the balance point temperature and  auxiliary heat lockout temperature the compressor will operate   However  the fossil fuel will turn on if the room temperature  droops below the selected droop temperature setting   compressor will be disabled     COMPRESSOR ONLY  W   71 AUX    z LOCKOUT  u COMPRESSOR 2   F     DROOP UPSTAGE TO   E FURNACE   n   8 BALANCE  a POINT   B       o    FURNACE ONLY       M23497  Fig  31  Balance Point with Auxiliary Lockout Temperature     AUXILIARY LOCKOUT FOR ELECTRIC HEAT BACKUP   Heat Pump systems with electric heat backup can select a  compressor lockout temperature  function 0350  and or  auxiliary heat lockout temperature  function 0360   When the  outdoor temperature is below the compressor lockout  temperature  only the auxiliary heat operates  When the  outdoor temperature is between the compressor and auxiliary  lockout temperatures  both the compressor and auxiliary heat  can operate     NOTE  System must have an outdoor temperature sensor     Heat Pump with Electric Auxiliary  Backup  Heat and    Outdoor Temperature Sensor   1  Choose correct heat pump application in Installer Setup  Number 0172    2  Choose Electric as Auxiliary  Backup  Heat Source in  Installer Setup Number 0200    3  Choose 
69. tain this temperature provided the  Dehumidification  70 99 70 F 99 F humidity setting is satisfied  This temperature  Away setting can not be set lower than the temperature  Temperature set in ISU 392   Setting                   68 0287   04    16       VISIONPRO   IAQ TOTAL HOME COMFORT SYSTEM    Table 3  Installer Setup Menu   Continued                                                           ISU  Parameter   Installer Setup Settings  Number Name  Factory Defaults Shown in Bold  Notes  394 Southern 65 Default   65  Set the desired humidity level to maintain within the  Dehumidification  40 70 40  70  relative humidity living space  Awa  Dehumidification  Setting  400 Ventilation control O No ventilation If ISU300   0  ISUA01 405 will not be shown   1 Ventilation on at all times  2 Ventilation on except during sleep period  3 Vent all with lockouts Not ASHRAE  4 Vent off sleep with lockouts Not ASHRAE  401 Number of 2 Default   2  bedrooms 1 6 1 6 bedrooms  402 Total house 10 Default   1000 sq  ft   Sq  Ft  10 50 1000 5000 sq  ft  in increments of 100  403 Ventilation CFM  160 Default   160 CFM  30 195 30 195 CFM in increments of 5  404 Max ventilation  50 Default   50  The thermostat will determine if ventilation is  percentage limit  30 60 3096   6096 meeting ASHRAE standard 62 2  The display will  100 unlimited show a P above the setup number if the setting  passes the ASHRAE standard  or F if it does not   Best practice is to move the setting down until F is  displayed
70. the desired humidity level and temperature in the  living space while away for extended periods of time  See ISU  Numbers 390   394 for more information     co    FAN    Set Toy  IL  LI  l    Inside T T    AUTO j L    Ld   n    SYSTEM          Permanent    JA LLILIJISEA    M23521          1  Press Hold three times to enter the Southern Dehumidifi   cation Away Setting   2  These settings can only be changed in installer setup     Clean Thermostat Screen  The thermostat has a touch screen interaction  Follow these  steps to clean the screen without making thermostat changes   1  Press the Screen key  Thermostat locks out all touch  keys for 30 seconds to allow for cleaning     an OK TO    A         JILJ SCREEN             M19964    2  Use damp cloth slightly moistened with water or house   hold glass cleaner to clean the screen   3  Repeatthe above steps  as necessary     IMPORTANT  Do not spray any type of liquid directly on the thermo   stat itself  If using household glass cleaner  spray  cleaner on cloth  Then use a cloth to clean the ther   mostat screen     4  Press the Done key to return to the Home Screen and  normal operation     68 0287   04 30    Screen Locks    SCREEN LOC  set  7 7     LiL  Lv     Following  Schedule    ner  1    I2   pa      Humidity                ie   HOLD I5  B       M23509    Partially Locked Screen   When partially locked  the screen indicates Screen Locked for  5 to 7 seconds whenever the user attempts to press a key that  is locked  Pressin
71. the thermostat screen when Auxiliary Heat is activated     Calibration   C7089U 1006  C7189U1005 and VisionPRO   IAQ Comfort Sys   tems are factory calibrated and require no field calibration     Interstage Differential    VisionPRO   IAQ Comfort Systems operate with droopless  control  Once the thermostat senses that 1st stage is run   ning at 9096 capacity  the thermostat energizes 2nd stage     Mounting Means    VisionPRO  IAQ Comfort System  Thermostat mounts directly  on the wall in the living space using mounting screws and  anchors provided  Fits a vertical or horizontal 2 x 4 in  junc   tion box    THM5421C1008 Equipment Interface Module  EIM  mounts on  HVAC equipment or on a wall in the equipment room    C7089U1006 Outdoor Sensor  Mounts outside of living space  with mounting clip and screws provided    C7189U1005 Remote Indoor Sensor  Mounts directly on the  wall using mounting screws and anchors provided     Cover Plate   32003796 001 Cover Plate is used to cover marks left on the  wall by the old thermostat     Dimensions    VisionPRO  IAQ Comfort System  see Fig  1   THM5421C1008  see Fig  2   C7089U1006 Outdoor Sensor Mounting Clip  see Fig  3   32003796 001 Cover Plate  see Fig  4    C7189U1005 Remote Indoor Sensor  see Fig  5     WALLPLATE  Ha            3 3 8  86          i                   T       EN INSTALLING  HERNOSTAT       L 3 3 8  86            THIS WALLALATE MUST BE UJ  REPLACED Wi  A NEW                                                              
72. thern Dehumidification Away Setting     HOLD TEMPERATURE UNTIL  TEMPORARY HOLD     Holds temperature temporarily until the next scheduled period  time or until the time the user sets     1  Press Up or Down arrow next to the temperature you  want to adjust   Hold Temperature Until  time appears on  the screen  The Hold Temperature Until time defaults to  the start time of the next scheduled period     NOTE  The Time Up and Down arrows are shown for approx   imately seven seconds  Pressing on the screen time   where the Hold Temperature Until time is shown   allows the arrows to reappear     2  Press Up or Down arrow next to the Time key to set  desired time for the thermostat to resume schedule     pe    FAN     4    v     Inside Tl r1    AUTO l  L        L4    SYSTEM    5  IZ    Hold Temperature  uli o  IL  WI    IY Lg ev    72    JL     Humidity    L    SCHED   HOLD    CLOCK   SCREEN  CANCEL    M23506             3  Press the Cancel or Sched key to cancel  Hold  Temperature Until  and resume schedule     NOTE  Once    Hold Temperature Until  time is reached  the    thermostat shows  Following Schedule  on the screen  to indicate that  Temporary Hold  has ended     29    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    PERMANENT HOLD    Permanent Hold changes the temperature setting until  Permanent Hold is cancelled     1  Press Hold key   Permanent Hold  appears on the  Screen     2  Press Up or Down arrow next to the temperature you  want to set during  Hold      AUTO  v     S
73. time     NOTE  Calendar can also be set in the Installer Setup     1  Press the arrow keys to set the year  month and day   2  Press the Done key     SET CURRENT DAY   SET MONTH                              DONE                  USE ARROWS TO SET YEAR AND TIME  M22424    3  Press the arrow keys to set the current time   4  Press the Done Key     68 0287   04    VISIONPRO  IAQ TOTAL HOME COMFORT SYSTEM    USE ARROWS TO SET YEAR AND TIME                                              M22425    INSTALLER SETUP    Auto Discover is available when the TH9421C thermostat is  connected to an EIM  The EIM communicates information to  the thermostat  Thermostat settings can be specified using the  up and down arrow keys on the screen or set to Auto Discover     Using Auto Discover    Some Installer setups are defaulted to Auto Discover  If not  defaulted  the installer can change the option to Auto Discover   however  it is always important that the installer verify that the  auto discovered values are correct for the system that is  present     When using the thermostat with an equipment interface  module  Auto Discover will discover factory default settings  and will not receive communications as to proper system  settings  The equipment interface module is preprogrammed at  the factory as a one heat one cool product and the thermostat  will    auto discover  those settings  The equipment interface  module will be reprogrammed when the installer manually  changes the configuration in t
74. to Dehumidification   Nothing  DHM1 and DHM2 open   Y   and G    Auto Ventilation VNT1 and VNT2 Close VNT1 and VNT2 Close None  Heat or Em Heat Humidification HUM1 and HUM2 Close NA None  Heat or Em Heat Dehumidification VNT1 and VNT2 Close  NA None  Heat or Em Heat Ventilation VNT1 and VNT2 Close NA None  Cool Humidification NA Nothing  None  Cool Dehumidification NA DHM1 and DHM2 close    None  Cool Dehumidification NA DHM1 and DHM2 open   Y   and G   Cool Ventilation NA VNT1 and VNT2 Close None                           Humidification only operates in heating or when last call was for heating      gt  Dehumidification only operates in cooling or when last call was for cooling      Must be set up in installer setup  ISU 379  for dehumidification with air conditioning    d Installer setup  ISU 406  must be setup for Ventilation in high humidity or nothing will happen     Only with whole house dehumidifier     Multi Stage Heat and Cool Control  In a multi stage system  while maintaining setpoint  several  factors affect when the next stage energizes  such as load  conditions  environmental conditions  P   control  and home  insulation  The next stage energizes when the thermostat  senses the previous stage is running at 9096 capacity  This  operation is droopless control     User Setup    Follow these steps to enter the User Setup     1  Press and release the System key              Following  Schedule    2o     Humidity        cue   HOLD  i      SCREEN                      M
75. uto Discover  530  Adaptive 0 Conventional  Table 8  User Setup Menu  Intelligent 1 Adaptive  Recovery  User 540  Number of 2 2 Periods  Setu User Setup   Periods 4 4 Periods  No  Name Settings 640  Clock Format 12  12 Hour  120  Date  Year 20 24   24 Hour  Upper  21 670  Keypad 0 Unlocked  130 Date  Year 01 99 Default   06 Lockout 1 Partial Locked  Lower  2 Full Locked  140  Date  Month   1 12  Select number that represents current  calendar month   Default   06 R A  150 Date  Day  1 31  Select number that represents current PROG MMING  calendar date   Default   15 i  160 Schedule 4 Seven day programmable Preprogrammed Settings  Options 0   jNon programmable Table 9 shows default program settings   165 Restore Default  0 No  Schedule 1 Yes  280  Continuous 0 Backlight not on continuously   Backlight Thermostat backlight comes on with 2  9 each key press  i wi Table 9  Default Program Settings   1 Backlight is on continuously     320  Temperature  0 Fahrenheit temperature display Schedule Setpoints Fan  Indication 1 Celsius temperature display Period Time Heat Cool Setting  Scale  330  Daylight Saving 0 Disabled Wake 6 00AM  70  F  21  C   78  F  25 5 C  Auto  1 Enabled  US 1987    o o o o  2 Enabled  US 2007  Leave 8 00AM  62  F  16 5  C  85  F  29 5 C    Auto  400  Ventilation 0 No ventilation Return 6 00PM  70  F  21  C   78  F  25 5 C   Auto  control 1 Ventilation on at all times   e e o e  2 Ventilation on except during sleep Sleep 10 00PM  62  F  16 5  C  82  F  28  C  
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
LD303 - Smar  F250 PONTOON WAKEBOARD TOWER  Sony DVP-NS755V DVD Player  mars 2010 charte de la participation PLH  Nextbook Premium 7 Google Play Operating Instructions  強度判定について  SMC Networks SMC7908VoWBRA User's Manual  Flow Loop User`s Manual  I. 安全編  courrier ci-joint (05/06/2008)    Copyright © All rights reserved. 
   Failed to retrieve file