Home
ASHIDA NUMERICAL 3 POLE DIFFERENTIAL RELAY
Contents
1. our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industrial Estate Thane W 400 604 INDIA Ref ADR133A_TX_R6 Issue 06 09 01 2012 Page 6 7 E mail sales ashidaelectronics com Web www ashidaelectronics com Type ADR133A ADR233A ADITYA Series Thermal Withstand Capacity x40 times the normal current for 3sec x2 Continuous Drawing Reference For Electrical Connection ACD01603 For Back Terminal Arrangement ACD01703 Model AM00204 AM00205 For Cabinet Type MAC00402 CSD V 120 150D For Isometric View MAC00403 Revision Note Revision Date 01 30 03 08 02 06 11 08 Description Add extra 3 Ann Contact in original as HF Operated R faulty and R operated Electrical connection drawing format change Minor type corrected 03 29 11 08 04 25 03 10 05 10 04 10 06 09 01 2012 LED indication information added and Type Test details deleted Back Terminal Arrangement Changed ADR233A specs added Addition of Drawout Model AM00204 xx x x xx x Photograph modified Note Due to our policy to upgrade our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industr
2. 01703 08 10 09 TITLE Back Terminal Arrangement Neumerical E Electronics Transformer Differential Relay ADR 133A ADR 233A Editi Sheet Pvt Ltd L Drawing__ Ref ACD01703 ane 7 J C EE E Scale NTS 1 2 3 L Drawing Format Changed 14 09 02 ooo it Cabinet Terminology Changed 19 12 08 ooo ooo CAB STYLE 120 CSD V 120 NON DRAWOUT CSD V 150D DRAWOUT PANEL CUTOUT REQUIRED FRONT VIEW MINIMUM GA FOR HOR MOUNTING MINIMUM GAP FOR VER MOUNTING Note 1 Front Bezel 160mm x 302 mm 2 Front Bezel Front Cover 166mm x 308mm 3 Box 136mm x 278mm amp Cutout 138mm x 282mm TOP VIEW ALL DIMENSIONS IN MM FINISH MATERIAL Perpaed by Checked by Approved by date Filename Date JD SG SMK MAC00402 29 12 08 TITLE MECHANICAL DETAILS ASHIDA Electronics FOR CSD VER CABINET Edition Sheet Pvt Ltd d Drawing Ref MAC00402 10F 1 B a a E S ad h Scale NTS 1 2 3 4 EE e OA FRONT VIEW REAR VIEW FINISH MATERIAL Perpaed by Checked by Approved by date Filename Date JD SMK SMK MAC00403 29 12 08 TITLE ISOMETRIC VIEW Fas ASHIDA Electronics FOR CSD VERTICAL CABINET Scale NTS a ae a ae a ee ee A
3. The relay is also having dedicated potential free contact for external ALARM This feature is very useful to give pre information to avoid any mal operation In such situation it uses the default setting and remains in protection mode 3 Working Principle and Design The ADR133A monitors HV and LV current of power transformer through respective CT The sample current values are processed by powerful DSP controller It converts these current samples into equivalent vectors and number of parameters such as RMS values of IHV and ILV and phases IHV represent HV current and ILV represent LV current Normally to match HV and LV CT ratio phase shift between two winding due to transformer vector group ICTs interposing CTs are needed In ADR133A ICTs are software selectable There are two separate ICT ratio and vector groups provided one for HV value and another for LV value After applying this corrective factor relay calculates operating and restraining signal from IHx and ILx IH1 and IL1 is HV and LV current after applying ICT correction factor x denote phase 1 for R 2 for Y and 3 for B Based on these settings the relay decides to operate or to restrain Operating Current Tox IHx ILx Restraining Current Ibx IIHxl 1 ILxl 2 Note Due to our policy to upgrade our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Ro
4. Type ADR133A ASHIDA NUMERICAL 3 POLE ADR233A DIFFERENTIAL RELAY ail Features Online display of Phase Current Differential ee Current Latching of fault current value High Speed operation 30ms at 5 times oaren Operation is based on fundamental frequency value Harmonics restrain for Transformer charging and CT saturation condition Cross harmonics restrain the relay will restrain all 3 Phases even if harmonic is detected in any one phase Programmable operating current Programmable Internal ICT Interposing CT ratio to match different transformers having different vector groups Programmable dual bias setting Wide setting range 10 50 for bias in steps of 5 Programmable 2 HRM restrain 10 80 e SCADA compatibility IEC60870 5 103 protocol Two Communication port 1 RS232 on Front and 2 RS485 at Rear For ADR233A relay only e Latching of Last 5 fault along with date and time stamp e 25 Cycle of disturbance record and 100 Event memory for ADR233A Applications e Two winding power transformers e Auto transformers e Biased differential protection for generators General ADR133A is member of Ashida Numerical Relay family Aditya Series designed to meet demand of low and medium transformer protection requirement It consists of all the basic function required for the protection of transformer such as harmonic restrain dual bias differential protection Note Due to our policy to upgrade our
5. ad No 21 Wagle Industrial Estate Ref ADR133A_TX_R6 Thane W 400 604 INDIA Issue 06 09 01 2012 E mail sales ashidaelectronics com Web www ashidaelectronics com Page 2 7 Type ADR133A ADR233A ADITYA Series Relay operate when Io is greater than pick up current setting and Tox gt S Ibx Where S set bias Slope 1 The relay supports dual bias characteristic The bias slop 1 is settable from 10 to 50 this is a normal bias characteristic The relay follows this characteristic till lx becomes equal to 2 Bias setting During heavy through fault due to CT saturation large difference current might generate which leads to mal operation of the relay To prevent this mal operation during such heavy through fault the relay is provided with dual bias characteristic In which after 2 Bias setting the relay changes it bias setting from set value to 80 automatically SLOP 1 SLOP 2 Ibias fxlref The relay is provided with differential high set protection where IHx ILx is greater than the preset value the relay will provide high set protection High set setting can be bypassed when it is not required The relay detects transformer charging condition from 2 harmonics contents If 2 harmonics are more than set limit then relay blocks tripping operation Similarly relay detects over excitation condition from 5 harmonics and restrain it operation Most of the relays are multifunction and having large number of s
6. ettings The ADR series relay is having big 4 line 20 character back lit LCD display and very strong user interface this makes very easy to manage the relay setting Note Due to our policy to upgrade our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industrial Estate Ref ADR133A_TX_R6 Thane W 400 604 INDIA Issue 06 09 01 2012 E mail sales ashidaelectronics com Web www ashidaelectronics com Page 3 7 Type ADR133A ADR233A ADITYA Series All settings are arranged in menus for easy understanding of parameter Maximum settings in one display The relay shows all the parameters such current before ICT current after ICT Primary current Bias and difference current Similarly relay latches fault current type of fault with date and time stamp If relay is upgrade to communication then it can provide full disturbance record in COMTRADE format for detail analysis 4 Current Transformer Requirement For high speed operation under all fault conditions the minimum current transformer knee point voltage should equal or exceed Vi gt 4 Ir A C Where Ir Either the maximum three phase through fault current as limited by the Tx impedance or the highset setting whichever is greater A The secondary winding resistance of each star connected CT C The CT Secondary loop lead resista
7. ial Estate Thane W 400 604 INDIA E mail sales ashidaelectronics com Web www ashidaelectronics com Ref ADR133A_TX_R6 Issue 06 09 01 2012 Page 7 7 is Rev No Revision note 01 Orginal Revision Org No cooo o SK YC 02 Revision As per Discussion on 217008 win cerca ono s B 10 S Auxiliary Voltage _ 44 D pa R 2 3 a 7 NO1 TRIP 1 C2 9 a AGE N02 TRIP 2 E om 8 R COM aa 14 HE OPERATED l la 3 R FAULTY HV SIDE 4 PCCM 12 R OPERATED f B CT HV LV SIDE NOTE REFER THIS DRAWING FOR BACK TERMINAL CONNECTIONS FINISH MATERIAL Perpaed by Checked by Approved by date Filename Date Scale JD SMK SMK ACD01603 08 10 09 NTS l Title BLOCK DIAGRAM FOR ELECTRICAL CONNECTION OF NUMERICAL ASHIDA Electronics 3 PHASE Tx DIFFERENTIAL PROTECTIOIN RELAY ADR 133A Edition Sheet y Drawing Ref ACD01603 i Re Aa L 1 2 3 4 Back Terminal Arrangement Numerical Transformer Differenital Relay Type ADR 133A ADR 233A Drawout Model AM00204 amp Non Drawout Model AM00205 Note 1 For Terminal numbers in the wiring diagram refer to relay back plate 2 Auxiliary supply to Terminals 10 amp 11 3 Contacts 1 2 amp 3 4 are potential free NO 4 RS485 PORT for ADR233A Drawout Model AM00204 amp Non Drawout Model AM00205 Dim MM FINISH MATERIAL Perpaed by Checked by Approved by date Filename Date JD SMK SMK ACD
8. nce for internal earth faults Note Due to our policy to upgrade our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industrial Estate Ref ADR133A_TX_R6 Thane W 400 604 INDIA Issue 06 09 01 2012 E mail sales ashidaelectronics com Web www ashidaelectronics com Page 4 7 Type ADR133A ADR233A ADITYA Series While Ordering Specify the following Information for ADR133A Relay Definition of Model No of Aditya Series of Relays AM XXX XX X X XX X Reserved for Future Use Auxiliary Supply PT Secondary 01 18 52Vdc 04 220 V ac 0 02 77 250 Vdc 05 60 Vdc 03 110 Vac 06 18 250 V dc CT Secondary 1 1 Amp 2 5 Amp 3 1 Amp 5 Amp Selectable Transformer Differential Relay o01 01 Relay with Fix CT Compatible with ACDF31H CSD V 120 001 02 Relay with Fix CT Compatible with ACDF31H with CSD V 120 1 2 Extra NO Contact fos Reserved o oo o S Joa Relay with selectable CT and draw out cabinet CSD V 150D 001 05 Relay with Selectable CT non draw out cabinet with 1 CSD V 120 3 one extra contact and wide setting range Relay with Selectable CT draw out cabinet with 3 CSD V 150D three extra contacts and wide setting range Relay with Selectable CT non draw out cabinet CSD V 120 with 3 three extra contact
9. products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industrial Estate Ref ADR133A_TX_R6 Thane W 400 604 INDIA Issue 06 09 01 2012 E mail sales ashidaelectronics com Web www ashidaelectronics com Page 1 7 Type ADR133A ADR233A ADITYA Series The ADR133A is designed using high speed micro DSP which sample all three phase current through CT connection The high speed micro controller samples this current through a 12 bit A D converter The micro controller performs powerful Digital Algorithms to find out Amplitude of current signal then this value is used for protection and metering function All measurement is tuned to fundamental frequency Each input current is also displayed on 20 x 4 LCD display for metering 1 Protection Functions The ADR133A gives maximum benefit cost ratio The ADR133A gives all the advantages of numerical relay at affordable cost Following is summery of different protection functions provided by relay ANSI IEC Protection Functions 87 Dual Bias Differential Protection 2 Supervision Function 2 1 Self supervision The relay continuously keeps track on its internal hardware and software and the moment it detects any failure of any component it give message on LCD display as error code details of error code are available in Users manual
10. rain HF setting 100 to 2000 in steps of 100 Definite time Differential High Set setting without harmonic restrain for backup HF NRST 1000 to 2000 in steps of 100 Definite time delay for Differential High Set setting without harmonic restrain for backup for HF NRST 0 04 to 1 00 sec in steps of 0 02s Vector group compensation for HV winding Vector group compensation for LV winding VH Yy0 Yy2 Yy4 Yy6 Yy8 Yy10 Yd1 Yd3 Yd5 Yd7 Yd9 Yd11 YdyO and Ydy6 VL Yy0 Yy2 Yy4 Yy6 Yy8 Yy10 Yd1 Yd3 Yd5 Yd7 Yd9 Yd11 YdyO and Ydy6 Output Contact 2 NO for Trip 1 NO for Relay Operated 1 NC for Relay Faulty 1 NO for HF Instantaneous Operated Operational Indicators Flags Operating Time Green LED indicates Power ON Red LED indicates Relay Pickup Self Reset SR type Red LED indicates Fault condition Hand Reset HR type Green LED indicates output close relay contact closer Programmable as HR or SR Less then 30ms at 5 Times of rated current value Burden on CTs Less than 0 2VA Burden on Aux Supply Less than 10VA on any supply Control Contacts Contact Rating for Trip Contract 2 NO contacts SR are given for Trip amp Annunciation Trip Duty Make and Carry for continuous 5A Make and Carry for 0 5 sec 30A Make and Carry for 3 sec 15A Note Due to our policy to upgrade
11. s and wide setting range Ordering information AJD RJ 1 3J 3JA Example ADR133A AM 002 05 3 0 06 0 Type ADR133A with wide setting and Non drawout case and extra contact Auxiliary Supply 18 250 V dc CT sec 1 5 Amp ADR233A AM 002 05 3 0 06 2 Type ADR233A with wide setting and Non drawout case and extra contact communication port RS232 amp RS485 Auxiliary Supply 18 250 V dc CT sec 1 5 Amp Note Due to our policy to upgrade our products constantly we reserve the right to supply products which may vary slightly from that indicated above ASHIDA ELECTRONICS PVT LTD Plot No A 308 Road No 21 Wagle Industrial Estate Ref ADR133A_TX_R6 Thane W 400 604 INDIA Issue 06 09 01 2012 E mail sales ashidaelectronics com Web www ashidaelectronics com Page 5 7 Technical Specifications Type ADR133A ADR233A ADITYA Series Sr No Specification Particulars Aux Supply 18 250VDC or 77 250VDC To be specified while ordering CT Inputs Suitable for CT secondary 1Amp 5Amp 1 Amp 5 Amp Selectable Operating Current 10 to 100 adjustable in steps of 5 Bias Bias setting is adjustable 10 to 50 in steps of 5 2 Harmonics Restrain 10 to 80 settable in steps of 5 Instantaneous Differential High Set setting with harmonic rest
Download Pdf Manuals
Related Search
Related Contents
le peuple valdotain 1978 06 02 n22 Deck Box Coffre pour terrasse Arcôn deTerraza rapport d`enquête ferroviaire r07t0110 déraillement en voie IBM 8271 User's Manual Xerox MO3102Y6-1 User's Manual APC Leak Sensor Extension Cable - 20 ft (6.1 m) Plantons le décor - Parc naturel régional de l`Avesnois 取扱説明書 サンフラワーシード UP750OUI Manuale d`uso K01-U425006 Copyright © All rights reserved.