        ALLEN-BRADLEY DF1 INTEGRATION KIT FOR
         Contents
1.       5 BCC mismatch                  6 Size error  data block won t fit into table or string      7 EOT limit exceeded  no response to half duplex poll      8 TNS mismatch  transmit and receive transaction numbers don   t match    9 Too many NACK responses received         10 Could not acquire port                  11 Bad control symbol received  half duplex         Errors Reported by ioControl    Slave    Subroutine    These error codes will be returned by response string to the polling device as Extended Status Codes     06h Address doesn t point to something usable  bad address         OEh Command cannot be executed  bad command or function code         11h Illegal data type  bad file number                  Allen Bradley DF1 Integration Kit for ioControl Users Guide    ERROR REPORTING FOR ABMASTER SUBROUTINES       14 Allen Bradley DF1 Integration Kit for ioControl Users Guide    
2.     00 Success     no error        02 Cannot guarantee delivery  link layer  The PLC may not be responding        03 Duplicate token holder detected        04 Local port disconnected        05 Application layer timed out waiting for a response        06 Duplicate node detected        07 Station is offline        08 Hardware fault                 Error Codes Reported by the PLC    16 Illegal command or format  SLC File Number vs  File Type mismatch        32 Host has a problem and will not communicate        48 Remote node host is missing        64 Host could not complete function due to hardware fault        80 Addressing problem or memory protect rungs        96 Function disallowed due to command protection selection        112 Processor is in program mode        128   Compatibility mode file missing or communication zone problem        144 Remote node cannot buffer command        160 Not used        176 Remote node problem due to download        192 Cannot execute command due to active IPBs        208 Not used        224 Not used        240   Indicates an extended error code  See   PLC Extended Status Codes    on page 12                 Allen Bradley DF1 Integration Kit for ioControl Users Guide  EN     ERROR REPORTING FOR ABMASTER SUBROUTINES       PLC Extended Status Codes    61441 A field has an illegal value        61442   Less levels specified in address than minimum for any address        61443   More levels in address than system supports        61444   Symbol not fo
3.  Nokia Corporation  Sony is a trademark of Sony Corporation  Ericsson is a    trademark of Telefonaktiebolaget LM Ericsson           All other brand or product names are trademarks or registered trademarks of their respective companies or organizations     Allen Bradley DF1 Integration Kit for ioControl User s Guide       Table of Contents             GE EEE EEE EE 1  A REE A 1  AAA Ne ret 1   fe ala de 0 EEE O Cn 2  e la MOSER SE EE ia 2  Addressing Limitations             cccccescccceeneeesenseseneeeeeeateeetaeesenenesenanes 2   Fl 2  Installing Integration Kit Files a cia 2  joControl Configuration RE I NE cece 3  TN Ned 3   Witha Tag DADAS EEE EEE RE EE ERE 3  Ge 0 or ORRE 4  Data Highway Communication Wiring            arrrvvrnrrrnnerarernnrrrnnrennerkneenneenr 4  Data Highway COMICO vara eee anker 5  Direct Serial Communication WING EE a  Direct Serial A A 6   TAN 6   AB Typed Read   AB Protected Typed Logical Read           2 0 2 0 rererere 6  VS EEE EP ET 6  O A A R 6   AB Typed Write   AB Protected Typed Logical Write              oooooooooorronccronoco raso  8  KEENE ER TENNENE EEE EEE 3  A TE TS 8     re APRO UT EEE ERE ENN 9  DES EE a OE EN NE 9  Gs EEG 9  PA undere add O ee  9   FE   EEE r A E E EN E E A E E EN 10    PCI AC5 and AC5 User s Guide ii         Error Reporting for ABMaster Subroutines    2 0    cece cece ence eee e eee e seat seat raros  Error Codes Reported by the 1770 KF2 Module  Error Codes Reported by the PLC  PEC Extended  Statis an endda  Errors
4.  Reported by ioControl    Master    Subroutines  Errors Reported by ioControl    Slave    Subroutine       PCI AC5 and ACS User s Guide          Allen Bradley DF1 Integration  Kit for ioControl    Overview    Introduction    The Allen Bradley DF1 Integration Kit  Part   OPTOINTAB IOC  provides users of Opto 22 s ioControl  software  version 6 0 and above  an easy method of communicating with Allen Bradley drivers or  PLCs using the DF1 protocol  Opto 22 controllers can act as either a    master    or a  slave  device   They can be connected directly to the serial port on an Allen Bradley PLC or to Data Highway  networks using standard Data Highway interface devices     The kit includes a set of ioControl commands that can be used anywhere within an ioControl  strategy  These commands provide ioControl applications the ability to exchange floating point   integer  1 0  ASCII  or string data with Allen Bradley devices that support the DF1 protocol    The command set is made up of ioControl subroutines that transmit and receive serial messages  according to the DF1 protocol specifications in the Allen Bradley Data Highway Data Highway  Plus DH 485 Communication Protocol and Command Set  publication number 1770 6 5 16     Requirements    To implement an interface between an Opto 22 controller and an Allen Bradley device  you will  need     e     The Allen Bradley DF1 Integration Kit    e     An Opto 22 SNAP Ethernet based controller  SNAP PAC R series  SNAP UP1 ADS  SNAP LCE   SN
5.  a  In the Configure I O Units dialog box  click the Modules button and choose Serial Modules  from the pop up menu    b  For the module and port you are using  click the Status column and choose Enabled from  the drop down list  Change the serial settings as necessary  Click OK    Choose Tools   Send Configuration to I O Unit  Make sure that the correct 1 0 unit is   highlighted and that the Address List field shows the correct IP addresses to send the   configuration to  Also make sure Save to Flash is checked  Click Send     IMPORTANT  Make sure you save your configuration to flash  or your settings will be lost when power  is removed     Allen Bradley DF1 Integration Kit for ioControl Users Guide    INSTALLATION       Without a Tag Database    If you are not using a tag database  you must still configure the serial ports using ioManager     1     2  3   4    If ioManager is not already open  choose Start gt Programs  Opto 22   oProject      oManager   Click the Inspect button Bl or choose Tools Inspect   In the IP Address field  type the IP address of the I O unit or choose it from the drop down list     If you are connecting to the DH interface device using the serial port on the controller  click the  Communications button and choose Communication Port Control from the pop up menu    For the port you are using  click the Value column for Control Function For Communication Port  and choose None from the drop down list  Click Apply     If you are connecting to the DH inte
6. 000   the settings on the Data Highway  interface device for baud rate  parity  and number of stop bits must match the serial handle passed  to the subroutine  or the serial settings on the serial module  In addition  the following parameters  should be set for the Data Highway interface device s asynchronous port          Use BCC error check mode          Do not use imbedded response mode    e     Disable handshaking     e     Use full duplex     Direct Serial Communication Wiring    The cables used for connecting an Opto 22 controller to an Allen Bradley PLC serial port are specified  in the drawings below  The cable for a PLC5 requires a DB25 male connector on the PLC5 end    The cable for a SLC requires a DB9 female connector on the SLC end  Current Opto 22 controllers  use screw type terminal connectors     Opto 22 RS 232 serial connection to PLC5 11 channel 0     OPTO 22 RS232 PORT PLCS SERIAL PORT   Tx 1                         K   EZ amp L                         3   Ra a  gt    END 2         7  4  Je  6 JUMPERS  3 e    20    Allen Bradley DF1 Integration Kit for ioControl Users Guide    SUBROUTINES       Opto 22 RS 232 serial connection to SLC5 04 RS232 port     OPTO 22 RS232 PORT    Tx 1  Rx 2  GND 3    SLC SERIAL PORT    Ji    1 JUMPERS    J     6    Direct Serial Communication    Full duplex or half duplex mode can be used to communicate directly between an Opto 22  controller and an Allen Bradley slave device  Master Subroutines only support half duplex mode     
7. ALLEN BRADLEY DF1 INTEGRATION  KIT FOR ioCONTROL  USER S GUIDE    SNAP Simple I O     SNAP Ethernet I O     SNAP Ultimate I O       Form 1555 061003   October 2006    OPTO 22    43044 Business Park Drive   Temecula   CA 92590 3614  Phone  800 321 OPTO  6786  or 951 695 3000  Fax  800 832 OPTO  6786  or 951 695 2712  www opto22 com    Product Support Services  800 TEK OPTO  835 6786  or 951 695 3080  Fax  951 695 3017  Email  support opto22 com  Web  support opto22 com    Allen Bradley DF1 Integration Kit for ioControl User s Guide  Form 1555 061003   October 2006    Copyright    2005 2006 Opto 22   All rights reserved   Printed in the United States of America     The information in this manual has been checked carefully and is believed to be accurate  however  Opto 22 assumes no  responsibility for possible inaccuracies or omissions  Specifications are subject to change without notice     Opto 22 warrants all of its products to be free from defects in ma    terial or workmanship for 30 months from the    manufacturing date code  This warranty is limited to the original cost of the unit only and does not cover installation  labor  or  any other contingent costs  Opto 22 1 0 modules and solid state relays with date codes of 1 96 or later are guaranteed for life   This lifetime warranty excludes reed relay  SNAP serial communication modules  SNAP PID modules  and modules that   contain mechanical contacts or switches  Opto 22 does not warrant any product  components  or parts no
8. AP UP1 D64  SNAP UP1 M64  with 6 0 or later firmware    e A PC running ioControl software  version 6 0 or later     e A serial cable you provide to connect the Opto 22 controller to either the Data Highway  interface device or the serial port of an Allen Bradley PLC     Allen Bradley DF1 Integration Kit for ioControl Users Guide EE    IOCONTROL ARCHITECTURE       ioControl Architecture    ioControl Implementation  The Allen Bradley DF1 Integration Kit consists of a set of ioControl subroutines     The    Master    subroutines for the PLCS family support the Typed Read  Read Block  and Typed Write   Write Block  commands  In addition  the PLC5    Slave    subroutine implements the Typed Read   Read Block  and the Type Write  Write Block  commands  For the SLC family of PLCs  the commands  Protected Typed Logical Read and Protected Typed Logical Write have been implemented in both  the    Master    and    Slave    subroutines  All these commands have been implemented to the element   word  level of addressing     Addressing Limitations   The integration kit has the following PLC addressing limitations          The integration kit does not support reads or writes of individual bits    e     The integration kit does not allow reading and writing to PLC file numbers 2  4  5  or 6     e     The integration kit will not read or write to any PLC data files that have a file type other than  integer  float  1 0  ASCII  string  or binary     e The ioControl subroutines will access only 
9. Data Highway       Element Plus Asynchronous  RS 232 C or RS 422 A  Interface Module  Half duplex only   File Type   1   Integer  Output or Input  2   Floating Point  3   Binary  4   ASCII  5   String   Element 8 If accessing Input  File No  1  or Output  File No  0  on the SLC processor  use this element    for the Sub Element Number  0 or 1  within the file of the slave device   Only used with File Numbers 0 and 1 on the SLC 5                 Integer 32 Table  Integer 32 Values    This table is the data that will be read from the PLC   Float Table  Floating Point Values    This table is the data that will be read from the PLC     String Table  String Values    This table is the data that will be read from the PLC   For ASCII data only  the first two characters in each table element will be used     Comm Handle  Communication Handle     ser  lt port number gt   lt baud rate gt   lt parity gt   lt data bits gt   lt stop bits gt    e     Port Number  0 or 1   e     Baud Rate  115200  76800  57600  38400  19200  9600  4800  2400  1200  300  e Parity  n  o  or e  none  odd  or even    e     Data Bits  7 or 8   e     Stop Bits  1 or 2       tcp  lt IP address gt   lt port number gt   e     IP Address  Address of the Snap Brain the Serial Module is attached to   e     Port Number  Port number of the Serial Module    Slot 0  22500 and 22501   Slot 1  22502 and 22503   etc    Slot 15  22530 and 22531             TNSValue  Integer 32 Values     This variable keeps track of the TNS Va
10. Subroutines    AB Typed Read   AB Protected Typed Logical Read    Description    AB Typed Read reads a block of data from a PLC 5 data file  AB Protected Typed Logical Read reads a  block of data from an SLC 500 data file     Parameters    Parameter Table  Integer 32 Values     Enter the parameter table name in the field next to the prompt PARAMETER TABLE when calling the    subroutine     Element 0    Destination address of the slave device  PLC 5  00 77 Octal        Element 1    File Number within the slave device        Element 2    Indicates the Starting Element Number within the file of the slave device    If accessing an Input or Output file  use this element to indicate the position of the I O module   Example  If you have an input module in position 1  Element 2 should be set to 1 when trying  to access the input or output file from that module        Element 3    Starting Table Element Number in the associated ioControl table where source data to be  written to the slave device is stored        Element 4    Number of elements to copy        Element 5          Amount of time in seconds that this subroutine will wait for a reply from a slave device           ES Allen Bradley DF1 Integration Kit for ioControl Users Guide    CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       Communication Mode   Element 6 0   Full Duplex or Point To Point mode    1   Half Duplex or Multidrop mode        Holds the Station Number of the Allen Bradley 1770 KF2 Data Highway or 
11. Tree under the Subroutines Included folder   When you have added all the subroutines you need  they are ready for use in your strategy     Configuring Serial Ports    With a Tag Database  If you are using a tag database  follow these steps to configure the serial ports     1     2  3   4    If ioManager is not already open  choose Start   Programs   Opto 22   ioProject    gt ioManager    Open the existing tag database or create a new one by choosing File   New    Double click the I O Units folder on the Strategy Tree    In the Configure 1 0 Units dialog box  highlight the 1 0 unit s name in the list and skip to step 6    or click Add to add a new I O unit    Enter a name and description  In the Type drop down list  choose your controller by its part   number  In the Address field  enter the IP address of your controller  Click OK    If you are connecting to the DH interface device using the serial port on the controller    follow these steps to configure the serial port    a  Still in the Configure I O Units dialog box  click the Communications button and choose  Communication Port Control from the pop up menu    b  Click to put a check mark in the Used box    c  Forthe port number you are using  click the Value field for Control Function for  Communication Port  From the drop down list  choose None    d  Click OK    If you are connecting to the DH interface device using a SNAP serial communication module on   the I O unit  follow these steps to configure the serial module   
12. alues    File 8 of the subroutine     Comm Handle  Communication Handle      ser  lt port number gt   lt baud rate gt   lt parity gt   lt data bits gt   lt stop bits gt     Port Number  0 or 1   Baud Rate  115200  76800  57600  38400  19200  9600  4800  2400  1200  300  Parity  n  o  or e  none  odd  or even    Data Bits  7 or 8   Stop Bits  1 or 2          tcp  lt IP address gt   lt port number gt     IP Address  Address of the Snap Brain the Serial Module is attached to   Port Number  Port number of the Serial Module    Slot 0  22500 and 22501   Slot 1  22502 and 22503   etc    Slot 15  22530 and 22531       Error Handle  Integer 32 Values    Any error codes that the subroutine encounters will be    passed back to the strategy through this variable     File Types    The file type argument used with the    Master    subroutines allows the read and write commands  to handle each kind of data properly  It is set by storing the proper value in element 8 of the     PARAMETER TABLE    used with each call to a subroutine  The following table shows what    file type value to use for each PLC file type   File Types Used With AB Master Subroutines                   1 Integer  Output  or Input   2 Floating point   3 Unsigned integer   4 ASCII   5 String             10   Allen Bradley DF1 Integration Kit for ioControl Users Guide       CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       Error Reporting for ABMaster Subroutines    Error Codes Reported by the 1770 KF2 Module
13. len Bradley 1770 KF2 Data Highway or Data Highway Plus  i Asynchronous  RS 232 C or RS 422 A  Interface Module  Half duplex only     File Type   Flament 8  1   Integer  2   Floating Point  3   Binary  4   ASCII  5   String                 Integer 32 Table  Integer 32 Values    This table is the data that will be written to the PLC   Float Table  Floating Point Values    This table is the data that will be written to the PLC     String Table  String Values    This table is the data that will be written to the PLC  For ASCII data   only the first two characters in each table element will be used     E  Allen Bradley DF1 Integration Kit for ioControl Users Guide    CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       Comm Handle  Communication Handle     ser  lt port number gt   lt baud rate gt   lt parity gt   lt data bits gt   lt stop bits gt    e     Port Number  0 or 1   e     Baud Rate  115200  76800  57600  38400  19200  9600  4800  2400  1200  300  e     Parity  n  o  or e  none  odd  or even    e     Data Bits  7 or 8   e     Stop Bits  1 or 2       tcp  lt IP address gt   lt port number gt   e     IP Address  Address of the Snap Brain the Serial Module is attached to   e     Port Number  Port number of the Serial Module    Slot 0  22500 and 22501   Slot 1  22502 and 22503    etc   Slot 15  22530 and 22531             TNSValue  Integer 32 Values     This variable keeps track of the TNS Value  Transaction Value   after the subroutine has closed  Add a numeric 
14. lue  Transaction Value   after the subroutine has closed  Add a numeric variable  Integer 32 Value  to your strategy   This is required by the DF1 protocol  Only one variable per strategy is required     Error Code  Integer 32 Values     Any error codes that the subroutine encounters will be  passed back to the strategy through this variable     Allen Bradley DF1 Integration Kit for ioControl Users Guide    SUBROUTINES       AB Typed Write   AB Protected Typed Logical Write    Description    These subroutines write a block of data to a PLC data file  Cannot write to Input or Output files   file number 0 or 1      AB Typed Write writes a block of data to a PLC 5 data file  AP Protected Typed Logical Write writes a  block of data to a SLC 500 data file     Parameters    Parameter Table  Integer 32 Values                             Element 0  Destination address of the slave device  PLC 5  00 77 Octal   Element 1  File Number within the slave device   Element 2  Indicates the Starting Element Number within the file of the slave device     Starting Table Element Number in the associated ioControl table where source data to be  Element 3  E ae  written to the slave device is stored   Element 4  Number of elements to copy   Element 5  Amount of time in seconds that this subroutine will wait for a reply from a slave device   Communication Mode   Element 6  y    0   Full Duplex or Point To Point mode   1   Half Duplex or Multidrop mode   Element 7  Holds the Station Number of the Al
15. rface device using a SNAP serial communication module on  the I O unit  click the Communications button and choose Serial Modules  In the Serial Module  Number field  choose the modules position on the rack  Change the serial settings as necessary   Click Apply    Click the Status Write button  Under Operation Commands  select Store Configuration to Flash   Click Send Command     IMPORTANT  Make sure you save your configuration to flash  or your settings will be lost when power  is removed     Data Highway Communication Wiring    The cables used for connecting an Opto 22 controller to a Data Highway interface device are  specified in the drawings below  The cables require a DB25 female connector on the Data Highway  interface end  Current Opto 22 controllers use screw type terminal connectors     Opto 22 RS 232 serial connection to DH interface device     DH INTERFACE    SNAP SCM 232 OPTO 22 RS232 PORT  Snap UIO  and  Snap LCE  ASYNCHRONOUS PORT  o 3  2  a2 2  Sl CS   4   J   6 JUMPERS  5      20    e  Allen Bradley DF1 Integration Kit for ioControl Users Guide    CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       Opto 22 RS 422 serial connection to DH interface device     SNAP SCM 485 422 DH INTERFACE   ASYNCHRONOUS PORT  40R 8 1  6 14  7 25  2 16  3 18  4   Nan   6 JUMPERS  5 1    20    Data Highway Communication    In order to communicate on the Data Highway network with an Opto 22 controller and a Data  Highway interface device  for example  KF module or DL2
16. t manufactured by  Opto 22  for these items  the warranty from the original manufacturer applies  These products include  but are not limited to        OptoTerminal G70  OptoTerminal G75  and Sony Ericsson GT 48                see the product data sheet for specific warranty    information  Refer to Opto 22 form number 1042 for complete warranty information     Cyrano  Opto 22 FactoryFloor  Optomux  and Pamux are registered trademarks of Opto 22  Generation 4  ioControl  ioDisplay     ioManager  ioProject  ioUtilities  mistic  Nvio  Nvio net Web Porta  OptoOPCServer  OptoScript  OptoServer  Opto Terminal  OptoUtili  SNAP Simple 1 0  SNAP Ultimate 1 0  and SNAP Wireless LAN 1 0    ActiveX  JScript  Microsoft  MS DOS  VBScript  Visual Basic  Visua  trademarks of Microsoft Corporation in the United States and oth      OptoConnect  OptoControl  OptoDisplay  OptoENETSniff   ies  SNAP Ethernet 1 0  SNAP 1 0  SNAP OEM 1 0  SNAP PAC   are trademarks of Opto 22     C    and Windows are either registered trademarks or  er countries  Linux is a registered trademark of Linus    Torvalds  Unicenter is a registered trademark of Computer Associates International  Inc  ARCNET is a registered trademark of       Datapoint Corporation  Modbus is a registered trademark of Schneider Electric  Wiegand is a registered trademark of Sensor  Engineering Corporation  Nokia  Nokia M2M Platform  Nokia M2M Gateway Software  and Nokia 31 GSM Connectivity  Terminal are trademarks or registered trademarks of
17. the least significant 16 bits of any ioControl table  or variable  The Allen Bradley PLCs are 16 bit devices     e     Only one master can access the slave subroutines at a time     e     When the numbers are negative  the upper 16 bits will be set to 1 within the ioControl table  to keep the numbers consistent with the PLC     Installation    Installing Integration Kit Files  Insert the Optolntegration CD to run the SETUPEXE program     The setup wizard will create the folder Program Files Opto 22 Allen Bradley DF1 Integration Kit for  ioControl  This folder contains all the subroutine and support files for the integration kit  as well as  example ioControl strategies     NOTE  Integration kit documentation is in PDF format  If you don t already have Adobe Acrobat Reader  installed  you will need it to view and print the supporting document  After installation is complete   you will have the option of installing Acrobat Reader     Allen Bradley DF1 Integration Kit for ioControl Users Guide    CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       ioControl Configuration    To use the integration kit with an ioControl strategy     1   2     Start ioControl and open the strategy that you intend to use with the integration kit     For each subroutine you intend to use with your ioControl strategy  choose  Configure   Subroutine Includes  Click the Add button and use the browser to select the  subroutine file   ISB extension      The subroutine appears in the Strategy 
18. und        61445   Symbol is of improper format        61446   Address doesn   t point to something usable        61447   File is wrong size        61448 Cannot complete request  situation has changed since the start of the command        61449   Data or file is too large        61450   Transaction size plus word address is too large        61451 Access denied  improper privilege        61452   Condition cannot be generated  resource is not available        61453   Condition already exists  resource is already available        61454   Command cannot be executed        61455   Histogram overflow        61456 No access        61457   Illegal data type        61458   Invalid parameter or invalid data        61459   Address reference exists to deleted area        61460 Command execution failure for unknown reason        61461 Data conversion error        61462   Scanner not able to communicate with 1771 rack adapter        61463   Adapter cannot communicate with module        61464   1771 module response was not valid        61465   Duplicated label        61466   File is open  another node owns it                 61467   Another node is the program owner        Allen Bradley DF1 Integration Kit for ioControl Users Guide    CHAPTER 1  ALLEN BRADLEY DF1 INTEGRATION KIT FOR IOCONTROL       Errors Reported by ioControl    Master    Subroutines           1 Received packet was too short    2 Received packet was too long    3 Unknown symbol received in packet         4 Reply timeout   
19. variable  Integer 32 variable  to your strategy   This is required by the DF1 protocol  Only one variable per strategy is required     Error Code  Integer 32 Values     Any error codes that the subroutine encounters will be  passed back to the strategy through this variable     AB Slave    Description    The AB  Slave subroutine is used to make an Opto 22 controller communicate like a PLC5  or SLC processor     Operation    Create a new chart and ensure the appropriate slave subroutine call is the last command in the chart   Start and stop the subroutine by starting or stopping the associated chart     Each subroutine monitors a serial port for AB message traffic and supports PLC files 0  1  3  7  and 8  by using five ioControl numeric tables to hold the data  These five tables are passed by parameter  to the subroutine  The AB_Slave subroutine requires a dedicated chart in ioControl     Parameters    Slave Address  Integer 32 Values    lndicates the address the slave subroutine will respond to   If using a DH  interface device  this address must match the node ID number of the interface device     File 0   Output  Integer 32 Values     File 0 of the subroutine   File 1   Input  Integer 32 Values    File 1 of the subroutine     Allen Bradley DF1 Integration Kit for ioControl Users Guide EN    PILE TYPES       File 3   Binary  Integer 32 Values     File 3 of the subroutine     File 7   Integer  Integer 32 Values     File 7 of the subroutine     File 8   Float  Floating Point V
    