Home
Samsung 3.6 kWh All in One Installation Manual
Contents
1. Figure 5 10 Battery to BMS Connection As described in Subsection 5 4 fix the battery on the 3 6 kWh All in One then check the signal line of the battery part on the opposite side All of the cables can be stuffed in the corner of the enclosure They do not need to be bound with a cable tie The two shorter cables on the left can be stuffed near the tray BMS while the two longer cables on the right can be stuffed in the right corner of the enclosure Short cable D l d Long cable Figure 5 11 Cable Stuff Method 3 Finally connect the power cable line coming out from the battery with the battery power terminal in the middle Connect BATT A and BATT B 30 United Kingdom Eng 05 2015 Rev1 1 A Al lt N lt Figure 5 12 Battery Power Connection e BATT A Connector on the BDC side e BATT B Connector on the battery side United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 31 5 Electrical Connections 5 6 Closing the Front Case Cover NOTICE The LCD connector and ground are connected between the top left of the o front cover and the main body Be careful when you detach the front cover Make sure to connect the connector and ground before reassembling the front cover 1 Hold the front case cover with both hands
2. Figure 5 13 Front Cover Assembly process 1 2 Hang the product cover on the upper surface of the enclosure then push the product cover forward to close it 32 United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections Figure 5 14 Front Cover Assembly process 2 3 As shown in the figure use a tool such as a flat driver to fix the bolts into the four holes indicated in red circles Figure 5 15 Front Cover Assembly process 3 United Kingdom Eng 05 2015 Rev1 1 33 5 Electrical Connections Screwing Torque 1 4N m Figure 5 16 Front Cover Assembly process 4 34 United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 5 7 AMethod of Locking the Distribution Box Board The distribution board performs the following functions when it is connected to the INVERTER the PV and the Grid AC Grid block function external AC circuit breaker 230Vac 32A 10kA short circuit current rating DC block function DC disconnect switch must be fitted PV String1 block function external DC disconnect switch PV String2 block function external DC disconnect switch 650Vdc or more 15A or more Residual current device RCD Leakage current measure and block The Figure 5 17 shows the connection diagram on the distribution board The distribution box receives the DC input the PV string 1 and the PV string 2 from the solar energy m
3. f k j 3 f j f f j f Hak iil th z T TE 3 4 5 6 7 8 9 WM MH 12 13 14 15 16 17 18 19 2 3 z 3 po Figure 6 9 Forecast page 6 5 6 5 Notices You can check the notice message whenever there is an update or any other change in the service 6 5 6 6 Software Versions You can check the software version of the product on the monitoring page 48 United Kingdom Eng 05 2015 Rev1 1 6 Communication Connection ADAMS aj PCE HA PQS O TR A TSOA ESS tara ne BROOME 4 La hire Samar Sl i amor Fe Emi aires Erhi MHE tara check Rennie pasmaord City Tatephone Tiu mires weer di S01 Fa Rare Your akina EMS Version E2014_Vo0001 BMS Version B2014_v00001 Primar tale PCS Version P2014_VO0001 Foal 2P Gati Software Version at oni oe i 7 u itim T a kesas ema p aia p Pandai ia agp a Figure 6 10 Setting page 6 5 7 Mobile Service Customers who use Android or l Phone can use a smart phone to easily check the product status anytime anywhere To use the mobile service the customer must first register the membership through the webpage and use the ID and the password to log in tno CF Sunny E Friday May 16th 2014 12 00 Figure 6 11 Mobile service page United Kingdom Eng 05 2015 Rev1 1 49 7 Entering Initial Installation Information 7 Entering Initial Installation Information You can use the following procedure to enter the init
4. ss sssessossesseessesseessesssee 37 Figure 5 19 PV connector Female and PV line Male uu sssecessssssecscecestssscscesssssseseceseeseseeseees 38 Figure 5 20 Side cover OPENING eree eren Eara ra EEA AE OE EA E aiaia iaaii iaaiiai 38 Figure 5 21 PV connector connection MC4 connector connection sessesssseseesesseesessessesss 39 Figure 5 22 L and N AC line connection method s ssesssessessesssesseossesseeoseesscoseesseosseoseesseoseesseosee 39 Figure s23 Terminal BIOCK larai E EAEE E 40 Figure 5 24 Power Cable connection to the terminal block sssesssessssssessesssesssesseesseessesseessesse 40 Figure 5 25 Side view after side cover assembly sssesssessssesssesssesssessssessseesseesseesseroseroseeosseesseessee 41 Figure 6 1 Internet Connection essessessessessessesseoseoseeseeoseossoseeseessessessesseoscoscoscoseosecoseoscoseoseoseoseesseseesses 42 Figure 6 2 Energy Meter Wiring amp Setting For C2000M ssessessessessessessessesssesseosesseeseeseessessess 43 RIGUIFG 6 3 R3485 termal DIOCK sa ceesereheeteccecbecoccccupecteczccescatesex ceca derce veces dasceceveatexsex at sasusauacececseeccecsseies 43 Figure 6 4 COMMUNICATION terminal cezssssssssssszscsssssssssseszesesszeei men nnnnwnnnnuceaauee a amueeeie 44 Figure ons Login page uneia seh see a Aaa eee E NARR 45 Figure 6 6 Password initialization PAGE ssssesessesssessesssesseesseesssesseoseesseoseesseos
5. Table 9 9 Significant events list 78 United Kingdom Eng 05 2015 Rev1 1 10 Maintenance 10 Maintenance 10 1 Cleaning the Fan and the Cover NOTICE Qualified Person Only Refer to the following procedures and check the fan when error code E005 is shown If the fan is covered with dirty particles clean the fan as guided in this chapter Turn off the AC circuit breaker and the DC disconnect switch in the distribution box then separate the Photovoltaic MC4 connector from the connector located on the side of the 3 6 kWh All in One Figure 10 1 PV MC4 connector Removal of the Photovoltaic MC4 Connector Remove the side cover Make sure not to remove the front case cover United Kingdom Eng 05 2015 Rev1 1 79 10 Maintenance Figure 10 2 Side cover removal When the side cover is removed clean the fan by using a smooth brush paint brush or wet cloth Remove the fan connector Figure 10 3 Fan removal Clean the fan with a smooth brush or a wet cloth iy NOTICE fn Using compressed air may damage the fan f When cleaning the fan do not use compressed air It may damage the fan When the fan is cleaned assemble all the components in the in reverse order 80 United Kingdom Eng 05 2015 Rev1 1 10 Maintenance 10 2 Checking and Exchanging Various Components NOTICE
6. 7 4 2 Login amp ESS List menu Input your ID and password for engineers to see the list of ESS Main menu Search pa Peg i oas PAD 2 gt Co mm F ail h 7 Serial No Status City M N TESTBED 0009 Cheongju Warning AR0046003621147 b 23001X ni Welcome SAMSUNG SDI Energy Storage System ion Ji Figure 7 3 Engineer log in page 7 4 3 Adding New ESS Information 54 Click the main menu and select Add New ESS Enter the ESS information installation information and owner s information The data input includes the ESS UID service date installation date installer information phone number address city information national code These information data may differ according to the product model and product version Click the Submit button when all is completed Then a success message appears United Kingdom Eng 05 2015 Rev1 1 Add New Ess ESS Information Serial Hop D rics Tyee Product Model Hante Mitel Lamrcity 76 Erm Installation intormmaton Euibding Type Building Mame Haus _ 10407 Country City Adress PE iiei AROOOSS0502480 TEST Fathe Niederkirchiner Straie 6 7 Entering Initial Installation Information Littety Manne utse i Tarti Hame He M1 instaler Manmre instalki Contact ls hala ibon Company metalation LEANA i Date sae i Remark Owner into Cher Hane CAN
7. IP Address 2 103 95 122 Battery Operation Status Standby PV Power ow PCS Target Power watt 237 W Capacity 3 6 kWh Errors EMS Mode EMS local Auto PCS Mode1 PCS Mode2 Both Feed in Limit 100 Figure 7 7 ESS status detail information page United Kingdom Eng 05 2015 Rev1 1 57 7 Entering Initial Installation Information 7 4 6 Changing the Inverter s Output Setting On the menu select Control and ERM for the Operation Mode Then select NOP for the ERM Mode 1 BOTH for the ERM Mode2 and Inverter Power Limit for the ERM Mode 3 And then choose either 3 6 kW or 4 6 kW for Inverter Limit Click the ADD button to select the product s that you want to apply this change to z i i e T 4 m Control ete Control Set up Openeion diode TRM boa DRM ode ERM Motes inwractar Limit Target SOK i Langat Piati iat i Sieius City aratai Saria Hi ARDHSO0IEZIIAT ZHAN Figure 7 8 ESS output setup page Add all the products you want to control then click the Control Now button to start controlling them You can check all the changes made to ESS Information It may take about 5 minutes to update such changes to this item PCS Information No Operation PCS Mode PCS Mode Both PC Power watt 0 2 PCS Target Power watt 237 Max Inverter Power watt 3600 Figure 7 9 PCS information
8. On flammable construction materials In potentially explosive areas and In areas where highly flammable materials are stored Li lon battery energy storage is equipped within 3 6 kWh All in One The ESS within 3 6 kWh All In One provides a safe source of electrical energy when operated as intended and as designed A potentially hazardous circumstance such as excessive heat or electrolyte mist may occur due to improper operating conditions damage misuse and or abuse The following safety precautions and the warning messages described in this section must be observed If any of the following precautions are not fully understood or if you have any questions contact Customer Support for guidance The Safety Section may not include all regulations for your locale Personnel working with 3 6 kWh All In One must review applicable federal state and local regulations as well as the industry standards regarding this product All work on the ESS and electrical connections must be carried out by qualified personnel only 14 United Kingdom Eng 05 2015 Rev1 1 4 Installation 4 1 1 Dimensions and Weight Once the 3 6 kWh All In One system has been assembled its dimension is 1000 x 680 x 267mm and its weight is approximately 95kg The Figure 4 1 and Table 4 1 show the outer dimensions and the weight of the device after assembly respectively Figure 4 1 Dimension of All in One Battery Inverter Inc
9. Table 9 8 Single fault events list United Kingdom Eng 05 2015 Rev1 1 7 9 Problem Confirmation 9 2 Significant Events If a significant event is notified the system is set to stop operation If that is the case contact your installer to restore the system to normal operation Type Code Description Measures Significant E901 SPI Occurs on internal non communication COMMUNICATION between the INVERTER EVENT Contact the installer immediately E902 CAN Controller Occurs on non communication with the Area Network EMS COMMUNICATION When in operation the All In One System EVENT is converted to the Stand Alone mode Contact the installer immediately E903 SINGLE FAULT The protection device against hazards EVENT has a defect or a fault that can cause a hazard has occurred Contact the installer immediately Contact the installer immediately E904 CONTINUOUSLY 3 When INVERTER FAULT occurs three TIMES INVERTER consecutive times INVERTER HARD FAIL FAULT is considered to be occurred to stop the operation Contact the installer immediately E905 PV CROSS PV mis wiring for example P1 P2 or CONNECTION P2 P1 Permanent Fail Contact the installer immediately E906 Cell Over Voltage When exceeding Cell Max voltage Permanent Fail Contact the installer immediately E907 Cell Under Voltage When an abnormal decrease in Cell Min Permanent Fail voltage is reported Contact the installer immediately
10. 3 1 Package Removal and Tray Assembly 3 1 1 Removing the Enclosure Package As shown in the figure in this section remove the package components from the enclosure in the following order 1 Place the system on the installation location W 2 Open the upper part of the battery case CRU 3 Remove both sides of the cover in the front of the product Lk 8 United Kingdom Eng 05 2015 Rev1 1 3 Package Removal and Inspection 4 Lift the package N f NANNY COON Figure 3 1 Process for the enclosure package removal 3 1 2 Removing the Battery Tray Package As shown in the Figure 3 2 remove the package for the battery tray 1 Open the box cover of the product 2 Remove the buffers with a straight pull 3 Take out the battery tray by grabbing the handle and pulling it up Note The tray weighs approximately 45 kg so make sure to have at least two persons lift it Figure 3 2 Process for the battery package removal United Kingdom Eng 05 2015 Rev1 1 9 3 Package Removal and Inspection 3 1 3 Checking Components on the Packing List Once the product has been delivered refer to the figure Figure 3 3 and Table 3 1 identify the entire components included in the package and the correct number of the quantity listed in the table Packing List w Figure 3 3 Packing List Object Part Name Code No Quantity INVERTER ASSY S
11. Qualified Person Only 10 2 1 Fuse Check Check the fuse when the device fails to work with significant error E9XX Do not perform Fuse Check when the device is working Check the fuse after turning off the DC disconnect switch and the AC circuit breaker Measure both ends of the Inverter PBA SJ92 01425A F3 BDC PBA SJ92 01426A JF1 to check the resistance value If the resistance value is open state Mega ohms or Infinite value perform PBA exchange 10 2 2 Input Output Terminal Check Check the input output terminal when the device fails to work with significant errors E9XX Check the input output terminal after turning off the AC circuit breaker and DC disconnect switch Do not perform the check when the device is working Measure the input output terminal with a multi meter PV1 input SJ92 01426A CN13 CN14 PV2 input SJ92 01427A CN13 CN14 Battery input CN17 CN27 AC output CN1 CN4 If the resistance value is in a short state close to 0 perform PBA exchange 10 2 3 DC Link Check Check the DC Link when the device fails to work with E102 Check the DC Link after turning off the AC circuit breaker and DC disconnect switch Measure both ends of the DC link PBA SJ92 01428A CN1 CN2 with a multi meter to check the resistance value United Kingdom Eng 05 2015 Rev1 1 81 10 Maintenance If the resistance value is in a short state perform PBA exchange 10 2 4 FAN Operation Check 82
12. Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event Table 9 2 Inverter protection list Measures While in progress battery discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event While in progress battery discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event While in progress battery discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event While in progress battery discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal 71 9 Problem Conf
13. 61 United Kingdom Eng 05 2015 Rev1 1 Table of Contents 8 3 3 Battery Discharge MOde cssesssssssssssssssscscsssssssssssssssssssssssssssesesesesesesseasacasacasasaeacnsesnenes 61 BAU ggg E A O 62 8 3 5 Forced Charge Mode Maintenance mode esessessessessessessesseoseossesseosesseoseoseeseeseeseese 62 8 3 6 Stand Alone Mode scececscscecscscscscscscscscesesessssssssssssssssssesesesecececececssacacasasacacacasacssessssseeses 62 8 3 7 Event Check ModE ssns OOOO 63 8 3 8 Application Download MOde ce esssssssesssecscsessssssesesssssesesesesesesessssesesescaesesesesseeseseeseeeaees 67 9 Problem Confirmatio sssiminnicisiiincnsianinsa sie eee 68 a GNIEN E a E E E IOTA O 68 9 1 1 INVERTER General Events Warnings seesseessssessessessessessessesssessessessesseoseoseoseoseeseeseeseesse 68 9 1 2 INVERTER General Events Protection ssesssessessessessessessessessesssessessesseoseoseoseoseeseeseeseese 69 9 1 3 Battery Discharge General Events ss sesessessessessessessessessesssessesseoseoseoseeseessessesesesseosesssees 71 9 1 4 PV General Events Protection ssessseseessessessessessesssessessessessesseoseoseoseeseessessesseoseeseessessees 73 9 1 5 System General Events Protection cccscscscssssssssssessssssssssssesesesssssesessesessscseseseseseees 74 IO PECA EVENS TO AAE 75 9 1 7 EMS COMMUNICATION EventS eessessesessessessesessessessessessesessesseseosesseseoseose
14. 63 Figure 8 14 Event occurrence DC link over voltage Protection ccsesssscscecesecsesceeeteseseeeees 63 Figure 8 15 Event occurrence PV string1 reverse CONNECTION ProteCtiON eeeeteteees 63 Figure 8 16 Event occurrence PV string2 reverse CONNECTION PrOteCtiON ee eeeseeeeeeeeeees 63 Figure 8 17 Event occurrence PV string over voltage protection ssessessesseessessessessessesssess 64 Figure 8 18 Event occurrence PV string Over current protection s seessessessssessessssessessessese 64 Figure 8 19 Event occurrence PV string2 over Voltage protection ssesssessesesesseessessesseesse 64 Figure 8 20 Event occurrence PV string2 Over current protection sessessssessesesseesessesseessess 64 Figure 8 21 Event occurrence Battery over voltage protection ssessessessesseeseessessessesseeseessess 64 Figure 8 22 Event occurrence Battery Over current protection esessssessessessssessessesesseeseesesse 65 Figure 8 23 Event occurrence On sequence Inverter DC link event ssesssessssssesssrssesssesseesse 65 Figure 8 24 Event occurrence On sequence Battery V I event ssessessssessessessssesseseesessseseesesse 65 Figure 8 25 Event occurrence Normal Inverter DC link event ssesssesssessesssesseesseessesssesseessesse 65 Figure 8 26 Event occurrence Normal Battery V I amp BDC DC link event eeseeeseeeeeeeees 65 Figure 8 27 Eve
15. All in One system is intended for residential use only The 3 6 kWhAll in One system should not be used for commercial or building The 3 6 kWh All in One system is designed for residential use It is a single phase grid connected system of solar energy sources and Li on Battery energy storage The 3 6 kWh All In One system uses solar energy power connected to the input output terminal installed on the side of the device in order to 1 charge the Li lon battery energy storage 2 provide a supply to the household load and 3 convert direct current DC electricity of the battery to alternating current AC to discharge as household single phase load or electric system This device should not be used for any purpose other than the purpose described in this installation manual Any substitute use of this device random change in any of its parts and use of components other than sold or recommended by Samsung SDI will nullify the product s guarantee For example Samsung Li lon battery energy storage should not be replaced by other manufacturer s battery storages For further information on proper use of this device contact the Samsung SDI Service line or visit at www samsungsdi com Wiring Schematic of Single Phase System for UK kWh ESS Meter i kWh Main Earth Bar Generation Meter 1 I l oO 1 pho I kWh i Utility Meter PV1 Array PV2 Array RS485 i a i Commu
16. Box Board sssessesssessoessesseessesseesssesseessesseesseoseessesss 35 United Kingdom Eng 05 2015 Rev1 1 i Table of Contents 5 7 1 AC Circuit Breaker and DC Disconnect Switch esessessessessessessessesseeseesseoseoseoseeseeseeseesse 36 5 7 2 RCD residual current device Leakage Circuit Breaker ss ssessessessesseeseessessessesseessesee 36 5 8 An Installation Method of Energy Meter Electrical Connection s ssesseessesseessesssessersseessesss 37 5 9 AConnecting Method of the DC Line from the PV esesesescsssesesesscsssssessescssssssseseseseaseees 37 COMMUNICATION CONMECTION sisessneissecissnceccdasscsesistucnssiscscnsicntecssatasessesinsasnccensncucees 42 OL NUNS COT NS ON eae E EEE EE E aeeie 42 O COO E r EE E EEE E OOT OOOO 42 6 1 2 CONNECTION Block Diagram ssessessessessseseessessessessesssessenseoseosesseoseoseoseoseeseessessesseoseessessessres 42 6 1 3 Connection Method es ssessessessessesseeseessessesseeseeseeneesseseoseoseosesseoseoseosseoseoseoseoseoseeseessessessees 42 62 Energy Meter CONNEC cca cacccescacsecerecyccurececsecuvssiensesseessessansssssnsossenssnssessannnce nr arera t AER n SEBESEN RS NEN 43 SRP N E s aE e CC E E E emrnannmnntes 43 6 3 Recommended Energy Meter List sssssssesssssssssssssesssssssscscscscscssscsessscsssssssssssssesssesessssssescecsees 44 6 4 The Communication Terminal eessesseseesessesseseesessesseosessesessesseneeseosesseneosessesseseoss
17. Log in page United Kingdom Eng 05 2015 Rev1 1 45 6 Communication Connection 6 5 5 Password Initialization A customer who forgets the password during use can initialize the password by using the password initialization menu on the homepage On the log in page select the Forgot your id or password menu and when the customer confirms the ID and the e mail address created during membership registration the initialized password is sent to the registered e mail address Request Forgotten Password i Forgot Your Password Password will be reset and sent to the email address that wa up in the employee profile for the Online ID entered above Figure 6 6 Password initialization page 6 5 6 Types of Service Offered After completing log in normal service is available This service currently provides such menu items as monitoring consumption reports ESS reports ESS forecasts and notices 6 5 6 1 Monitoring The operational status of the product is indicated You can check the current status of operation the customer s power consumption information and power generation amount information in real time You can also check event codes generated during run time on the monitoring page You can check the details of the event codes by clicking the exclamation marks which appear on the ESS icon If the Internet is not available the event codes cannot be checked 46 United Kingdom Eng 05 2015 Rev1 1 6 Communicatio
18. SDI in Chapter 6 3 on the following page The Figure 5 18 shows the electrical cable connection and the communication lines of the digital energy meter Depending on the product there are a Uni Direction meter and a Bi Direction meter For the uni direction meter two lines must be connected with one line in the export direction and the other in the import direction For the Bi Direction meter one line can be used Refer to the Figure 5 18 and the communication description in Chapter 6 to install the digital energy meter Grid All in One a Energy Meter Energy Meter ill Energy Meter Generation Tariff for ESS Export Tariff Figure 5 18 Electric cable connection for energy meter installation The end system of the used lead wiring may be different with the energy meter chosen Therefore refer to the energy meter manual A Connecting Method of the DC Line from the PV Refer to the Figure 5 19 for the PV module connection The lead wire coming from the PV module is connected to the distribution box For the structure of the distribution box refer to subsection 5 7 For the connection to the distribution box connect each to the terminals of the solar energy of PV1 PV1 PV2 and PV2 On the other hand connect the distribution box terminals with the main body terminals PV1 PV1 PV2 and PV2 of the 3 6 kWh All In One in proper order The lead wire thickness is presented shown in the following Table Fo
19. Search menu If you enter search keywords and click the Search button the current status of ESS is displayed ESS List gt Search A Serial No TESTBED Product Model Status All v Country Republic Of Korea Vv City Owner Name Owner Contact All SEARCH Serial No Status City ESS List gt Search v Run Error Serial No Status City TESTBED 0009 e Cheongju Waring AR004600362Z1147 e 23001X Comm Fail pera aa Figure 7 5 ESS status page 7 4 5 Changing Inverter s Feed In Setting Select Control on the menu select ERM for the Operation Mode and then select NOP for the ERM Mode 1 BOTH for the ERM Mode 2 and Feed in for the ERM Mode 3 Enter your desired value in Feed in and click the ADD button to select the product you want to apply this change to 56 United Kingdom Eng 05 2015 Rev1 1 7 Entering Initial Installation Information Control Control Setup Operation Mode ERM Model ERM Mode2 ERM Mode Feed tn Target SOCI 0 Target Power watt 0 Figure 7 6 Inverter feed in limit setup page Add all the products you want to control then click the Control Now button to start controlling them You can check all the changes made to ESS Information It may take about 5 minutes to update such changes to this item ESS Status oe et 5 01 15 05 52
20. Serial No W Device specific characteristics W Certification Lists W Warnings and Notification The model No of 3 6 kWh All In One system is defined as below ELSR362 00002 e ELSR Residential application e 36 Battery capacity x0 1kWh e 2 Battery capacity group Less than 10kW e 00002 product line number The model No of INVERTER power conditioning system is defined as below Mi SJ94 00108B e SJ battery for ESS e 94 Ass y e 00108 product number e B National Code UK The Type Label is shown in the Figure 3 5 12 United Kingdom Eng 05 2015 Rev1 1 SAMSUNG SDI ex System No ELSR362 00002 Inverter No SJ94 00108B a m A A Ty AC 3 Package Removal and Inspection MPPT Range 125V 500V Photovoltaic Max PY Current Module t odule Inpu Per String Isc py 15A 20A AC Nominal Power 4600W NU AC Nominal Voltage 230V 50Hz AC Frequency Battery Type AC Nominal Current 20A Battery Capacity f Nominal Voltage 3A Protection Degree Class IP21 1 IEC 62109 1 2 ER G83 2 ER G59 3 MADE IN KOREA Figure 3 5 Name Plate United Kingdom Eng 05 2015 Rev1 1 13 4 Installation 4 Installation 4 1 Selection of Installation Location Danger to life due to fire or explosion Danger to life due to high voltages Despite careful construction a fire can occur with electrical devices Do not install the 3 6 kWh All In One on the following locations
21. communication events liSt seeseesssessessessessesseessessessessesseoseoseoseeseeseeseeeesseeseeseessee 76 Tatle9 8 SINGIS FAUIE events Meteri E O O E N 77 Table 9 9 Significant events list sssesseessesseessesssesseesssesseosseoseossesseossesseensesseesseesseosseoseossesseesseoserseosee 78 Table 10 1 Replaceable parts list urinimin 85 Table 11 1 Technical Specifications c cccssssscscsesesssescsssessssssesesssesesesesesescsesescsesescsesessssssesesesesesesesesees 88 United Kingdom Eng 05 2015 Rev1 1 Table of Figures Table of Figures Figure 2 Te Connection DI GOT Alt renes set Soeccosesesesescscsvsvscsvevevececanentelutenecsosesesesesesosesosenosetes 4 Figure 2 2 Part View of Samsung All in One uu esesecsssececsssesscsssecsessccsssssscsessscsesssssesssecscsesseeseesees 6 Figure 3 1 Process for the enclosure package removall sse sssesssessseessersseesssersssesssessseesseessersseesss 9 Figure 3 2 Process for the battery package removal ccssssesessssssessessseesessssesssesscsssessesesessesseesseaes 9 ligure 33 Packing LAS acacia cece see EE EA 10 Figure 3 4 Process for the battery assembly ssesssessesssessesssesseessessseessesseessesseesseoseesseoseeoseosseosseosee 11 Figure 3 3 Name Platal eesseriisiseooriisinoiisioieb ion aea TREE E A 13 Figure 4 1 Dimension of All iN ONe ss ssssesssesssesssersseessersssersseeosseosseosseesserssersserosseosseoosseossers
22. it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event Table 9 3 Battery operation general events list 72 United Kingdom Eng 05 2015 Rev1 1 9 1 4 PV General Events Protection Type Code Description PROTECTION PROTECTION PROTECTION E301 ON SEQUENCE GRID OFF E302 ON SEQUENCE INV DC LINK EVENT E303 ON SEQUENCE PV V EVENT PROTECTION E304 NORMAL GRID OFF PROTECTION E305 NORMAL INV DC LINK amp PV EVENT PROTECTION E306 NORMAL PV V EVENT United Kingdom Eng 05 2015 Rev1 1 9 Problem Confirmation Measures PV generation mode is stopped by the protection event Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PV generation mode is stopped by the protection event Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PV generation mode is stopped by the protection event Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PV generat
23. result in a light injury if not avoided NOTICE This symbol indicates a hazardous situation which could result in damage to the property if not avoided This symbol indicates valuable tips for optimum installation and operation of the product United Kingdom Eng 05 2015 Rev1 1 1 1 About this Manual Number Description Direct current Alternating current Both direct and alternating current Three phase alternating current Three phase alternating current with neutral conductor Equipment protected throughout by double insulation or reinforced insulation Caution Risk of Electric Shock Caution Hot Surface 2 United Kingdom Eng 05 2015 Rev1 1 1 About this Manual Number Symbol Description In position of a bi stable push control Out position of a bi stable push control Input terminal or rating Output terminal or rating Bidirectional terminal rating Caution Risk of Electric Shock and Energy Storage Timed Discharge Caution Risk of Hearing Damage and Wear Hearing Protection Wear hearing protection Do not dispose of the inverter with household wastes For further information on disposal refer to the installation manual provided The CE Indication The relevant equipment complies with the requirements in the EC guidelines Table 1 1 Symbol Description United Kingdom Eng 05 2015 Rev1 1 3 2 Safety 2 Safety 2 1 Intended Use NOTICE The 3 6 kWh
24. 1 7 3 3 LAN Cable Connection between PC and SyStemM ssessessessessessessesseeseeseoseoseeseesseseess 51 7 3 4 SIM System Install Manager Connection ssessesssessessessessessessessessessseosesseoseoseoseesseseessees 51 7 3 5 Entering Setting ValUe e ssessessessessessessesseessessesseeseessensessesseosessesseoseoseosseoseoseoseoseosseseessesses 53 TE Web Page Connec arnon OOOO OOO 54 PAA WebPage COMMECTION jis cscscscscecscsccacasesnsnsaracacnesarazananazszanazataastnasnencaca en sneata coven susueneueneueseueseanas 54 LA CONS miso gl E Eees 54 7 4 3 Adding New ESS Information sesssscssssssssssssccsssssecscsssssssessescsssssesesesescsessssesesessseesees 54 74 4 Checking the Current Status Of ESS sesssssesssesesessssssssesscscsssssssesesssscsssssesessessseseees 56 7 4 5 Changing Inverter s Feed In Setting csssssssssssssesessssssssssssssesssssesesessssessessesesccscsceeses 56 7 4 6 Changing the Inverter s Output Setting s ssesseessessessessessessesseessessessessesseoseoseoseeseessessees 58 Bh Cy He A E A E A needs cet E E 59 8 1 Starting TAS SysteMssnssssnimma TETERE iS 59 8 2 Turning off the SySteM sseessesssesseessesseesseoseessseoseesseoseeoseosseoseesseoseesseoseeosseoseesseoseesseoseeoseosersseessessees 59 8 3 Descriptions of Operation Mode uu cscsssesssesesesesesesssesssessesesesesesesesescsescscscscscsesesesessesesesesesesesesesees 60 831 PV AUTO ModE ronis TONO 60 i a ea e
25. 1 23 xx Subnet mask 255 255 224 0 Default gateway 17 91 1 2 General You can get IP settings assigned automatically if your network supports this capability Otherwise you need to ask your network administrator for the appropriate IP settings O Obtain an IP address automatically Use the following IP address IP address 17 91 23 1 Subnet mask 255 255 254 0 Default gateway a7 9i 1 2 7 3 4 2 Connection URL e http 17 91 23 196 8000 7 3 4 3 Connection Screen MENU LIST Install Setting Menu Product Information IN Country United Kingdom installed PV 1 Power W Range 0 3300 W Operating Test thine E JE ala D S Aa a 3 Feed In Limit percentage er IP Server Port Output Max Power Smart Mode Basic Mode The Smart type is more advanced Algorithm A n Aut ft ft _ EMS S W V01 04 PRERE Feb 8 2015 ENG EMS HW V6 Smart Meter Selection Meter Type D0 Bi Direction 7 DO Meter Model Selection D0 Bi Feed In 10 C2000 Autometers a gt TEE Pees 1 247 C2000 meter only Press button of C2000 to 1 0 0 0 10 field Date Time Setting Fearon fa e Eo Fortrose fe J e Figure 7 2 Initial setup page 52 United Kingdom Eng 05 2015 Rev1 1 7 Entering Initial Installation Information 7 3 5 Entering Setting Value 7 3 5 1 S N e Enter shipment value from the factor
26. 1 Disassembly ieee rn ree eee re ee 91 12 1 1 Removing Electric CONNECTION cssssssssssssssssssssssssssssecssscscscscscscscsescscsessasasasasssassesesesssees 91 12 1 2 Disassembling the Main Body of 3 6 kWh All in One s sssssssessseesssesssesssesssessseeesseesseesss 91 122 TAA IMAG rssesssnssessnasanensansnnsessassansatanioeasnussecvecuro O OT 92 12a O A EEE NEEE 92 A DEOS ee A AAE OOTO 92 ERE A E O A A AO A E 93 United Kingdom Eng 05 2015 Rev1 1 iii Table of Tables Table of Tables Table 1 1 Symbol De SCription T eaaa E OOOO EA 3 Table 2 1 Part Description seesessesseseesessessesessessessesseseesessesseneosesseneeseosesseseesseseosesseneesessesseseosesseneeseosessesse 6 Maple 22 Base SpPeciica NONS a OO 7 Table 3 1 Component Description ssessesessesseseesessesseseesseseeseosesseseesesseseeseosesseneosesneosessenseseosesseseesesse 10 Table 4 1 Weight of All in One ss ssesssesseessesssessesssesseesseesseoseesseossesseosseoseessesseessersseosseoseessesseesseoseesseosee 15 Table 4 2 Specifications for anchor bolt oe eeesesesesesesesssssscsesescsescsesesescscseseseseseseseseseseeseseseseseeees 17 Maples Component DESPON sss aeescseseesecseoseneeeenn 23 Ranie s2 PEES in ne rs O 25 Table 5 3 Front Case Open Process ssesseseesesseseesessesseseeseeseesessesseseosesseseesessesseneosessessesseseesessesseseesesse 26 Table 5 4 Front and Rear view of All in ONnel ssesssesses
27. Check FAN operation when the device fails to work with E005 Check the FAN operation as frequently as possible Failure to do so may cause fatal damage to the device Perform PV Auto Mode to check whether both fans are working properly If the fans are not working properly contact the installer United Kingdom Eng 05 2015 Rev1 1 10 Maintenance 10 3 Battery Maintenance All work or service on the ESS and electrical connections must be supervised by personnel knowledgeable about batteries and the required precautions When replacing battery trays replace old ones with the same type and number of batteries or battery packs Check the type label or serial numbers model numbers on battery trays 40 minute standby period of time to complete discharging in the system before testing electrical parts inside the system Do not dispose of batteries in a fire The batteries may explode Do not open or damage batteries Released electrolyte is harmful to the skin and eyes It may be toxic A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when handling batteries Remove watches rings or other metallic objects Use tools with insulated handles Wear rubber gloves eye protection glasses and boots when working with the battery systems Do not lay tools or metal parts on top of batteries Disconnect charging source prior to connecting or discon
28. J94 00108B OB TRAY ASSY 2 Module ELPT362 00002 C 1 SCREW M4xL16 J81 01146 2 EXTENTION WIRE 3901 000819 3 EXTENTION WIRE 3901 000820 4 EXTENTION WIRE 3901 000821 5 CABLE TIE A Long B Short 6 JUMPER WIRE 3901 000859 Installation Quick Guide SJ68 02069B 1 Manual 3 EXTENTION WIRE may not be needed depending on the type of battery tray Table 3 1 Component Description 10 United Kingdom Eng 05 2015 Rev1 1 3 Package Removal and Inspection 3 1 4 Assembling the Battery Tray The Figure 3 4 shows the assembly process for the battery tray Refer to Clause 5 4 and assemble the battery tray as described in it Figure 3 4 Process for the battery assembly United Kingdom Eng 05 2015 Rev1 1 11 3 Package Removal and Inspection 3 2 Checking for damage in Delivery When opening the box that contains Samsung 3 6 kWh All In One system in it check for any possible damage caused in transit and ensure the correct number of the components therein If there is a scratch on the enclosure contact your local dealer for inspection and service 3 3 Identifying Samsung 3 6 kWh Allin One Attached on the enclosure of this product is the Type Label where the identity of this product is described For safe usage make sure that the following product information is indicated on the Type Label Mi Product Name W Device Type Model WE Serial Number
29. List Energy Meter Connector Table 5 2 Part List United Kingdom Eng 05 2015 Rev1 1 25 5 Electrical Connections 5 2 Opening the Front Case Cover 7 NOTICE The LCD connector and ground are connected between the top left of the front cover and the main body Be careful when you detach the front cover Make sure to connect the connector and ground before reassembling the front cover As shown in the Table 5 3 3 6 kWh All In One is delivered with the blue front case cover attached Remove the front case cover for electrical connections cS ESS f 0 QO e IAN I A lo SAMSUNG lo Front View Side View Turn the screws A B C and D 1 Pull the lower end turning 15 degree counterclockwise to assemble upwards Q 2 Push upward separate the front case e cover from the upper ring Table 5 3 Front Case Open Process 26 United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 5 3 The Overview of the Connection Area The Table 5 4 shows the inner structure of the 3 6 kWh All In One when the front case cover is removed Section 5 1 Inside Front View g BATTERY REGION A Battery connection terminal Inside Rear Vie
30. OVER FREQUENCY FAULT GRID TEN MINUTE AVERAGE FAULT RCMU Residual Current Monitoring Unit FAULT PV INSULATION FAULT ANTI ISLANDING FAULT FUNCTIONAL SAFETY FAULT 9 Problem Confirmation Measures The operation mode is terminated when a power system event occurs Restart 1 minute after the electric power system event is settled The operation mode is terminated when a power system event occurs Restart 1 minute after the electric power system event is settled The operation mode is terminated when a power system event occurs Restart 1 minute after the electric power system event is settled The operation mode is terminated when a power system event occurs Restart 1 minute after the electric power system event is settled The operation mode is terminated when a power system event occurs Restart 1 minute after the electric power system event is settled Turn off system power when the leakage current level is above standard level Check the leakage current level then restart or turn off to get back to the below standard level OFF Turn off system power if PV INSULATION RESISTANCE is at the standard level Restart after 3 minutes If the electric power system blacks out it automatically detects the state and turns off the All in One Restart after 3 minutes When the two MCU Micro Controller Unit measuring values are mismatched Restart after 3 minutes if no problem is found
31. SAMSUNG SDI ELSR362 00002 RES 3 6 kWh All In One Installation Manual CAUTION Do not operate with other components not approved by the ESS systems Connecting other products in parallel to Samsung SDI s products may result in abnormal operation The internet connection is required to use all functions of the ESS system If you have a problem please contact the installer The Specifications of the product may be modified without prior notice to improve product quality United Kingdom Eng 05 2015 Rev1 1 Table of Contents Table of Contents Table of Contents eee ene rae Se ee STR RT ae ee TR ey ee ee Oe RU AG ariiraa Eaa iv Me BU 5 vaca anasecicccenatecacdnccscstenadtascievcanntonsdane dcadexsavacttcecinasexeausetinecmtiesemaeticneal v 1 About this Manual cccccccccccccccccccccccccccccccccccccccccccccccccccccccccccccccccecccccccccccccces 1 LI Vaia RINGE ae E E OOOO OOOO OOOO 1 L2 TOET UD E E 1 1 3 Manual Storage seseeessessessessessessessesseessessesseoseoseoseeseeseesensesseoseosseoseoseoseoseoseoseoseoseoseoseesseseoseeseeseeserssess 1 A aaO U OEE A 1 Dig o E alot eens E S E N E E E E A E E E 4 DM nde UNS S eaa E 4 22 Sae PESCAUUOMNS serrera SETETE EEEE ie 5 2 3 Product OvervieW sssesessesessesessesessesessesesessesresesresessesesseseseesessesesscsesesoesessesrsseseesesoesesesesoesesoeoesesesesos 6 2341 Basic SpedicaloNnS esata escapades aE 7 23
32. Tbe Contact Lier Address Figure 7 4 New ESS add page Information Serial No Device Type Battery No Product Model Capacity Building Type Building Name Country City Address1 Address2 Utility Name Tariff Name Installer Name Installer Contact Installation Company Installation Date Remark Owner Name Owner Contact United Kingdom Eng 05 2015 Rev1 1 Description Enter the serial number of ESS Select a type of ESS e g AIO is RES Enter the serial number of battery Enter the model code of ESS e g AIO is ELSR362 00001 Enter battery capacity e g AIO is 3 6 Select a type of building Enter building s name e g Jack s Home Select the country Select the city where ESS is located Enter the address of location Enter the address of location Select the utility for the customer Select the tariff for the customer J Enter the installer s name or company name Enter the installer s contact information including the company information Enter the installer s company name Select the installation date Enter a something important to remark Enter the owner s name Enter the owner s contact information 55 7 Entering Initial Installation Information Information Description Owner Address Enter the owner s address Table 7 1 Registration Item list 7 4 4 Checking the Current Status of ESS Click the main menu and select the ESS List Enter the
33. United Kingdom Eng 05 2015 Rev1 1 4 Installation 4 2 Mounting Instructions Figure 4 5 Anchor Bolt Screw Drill Drill Tensile Shear ee L S D L1 Used depth capacity Capacity Min Max Max Fveni2 100 60 17 so 17 ssimm 3200 aA 3400 fl Table 4 2 Specifications for anchor bolt United Kingdom Eng 05 2015 Rev1 1 17 4 Installation 1 Select the drill proper for specifications for drilling specifications 2 Remove the dust from the hole then separate the nut and the washer to insert both the bolt and the cap 3 Set the product in place assemble the washer and the nut to the bolt and then use the spanner to fasten the nut 7N m Required tools for installation iOm Figure 4 6 A Flat head driver for the front cover knob larger than 10mm i Figure 4 7 The Plus head driver No 2 for the tray the side cover and grounding Figure 4 8 A spanner for fastening use 18 United Kingdom Eng 05 2015 Rev1 1 Figure 4 9 A fork lifter with height of 85 200mm United Kingdom Eng 05 2015 Rev1 1 4 Installation 19 5 Electrical Connections 5 Electrical Connections NOTICE The 3 6 kWh All In One system can be damaged by static discharge Before you touch a c
34. a GOMANG VS PV UAV SILC L ivcivsessassusonsvceseessvusonsssunassnnesnnnnaz7snussansannnnazD E EE 7 3 Package Removal and Inspection ccccccssscccssssccccsssccccsssccccssscccsssssccssssccsssess 8 3 1 Package Removal and Tray ASSEMDI scscssssssssssssssssssssssssssssesssessssssssssescscsesesesesescscassesssesesesesees 8 3 1 1 Removing the Enclosure Package cssssssssssssssssssssssssscsssssssssssssssssssssssssssssesessseseseescecaees 8 3 1 2 Removing the Battery Tray Package ccsesssssssssssssssssssssssscscsssssssssssssssssssssssssesessseseseseesees 9 3 1 3 Checking Components on the Packing LiSt esssessessessessessessessesseessesseoseoseoseeseeseeseese 10 3 1 4 Assembling the Battery IN AY ssieannaannncnnnmmancnnnnnnmmnnnnnnianmeannmarers 11 3 2 Checking for damage iN Delivery esesesscssssesesecscscsssecscsssssssssssscscsssesesesscsssssesesseasssseseeseseseaesees 12 3 3 Identifying Samsung 3 6 KWH All IN One wu esesessssesesesecscscsssssscssssssseseescscassesesssscscassssessessaceees 12 A metalt Oi ccicecesetaceconctivctnccsiantnscehuntacatiusdarccbecdnecseanteveutesteautiwsdaustbectuesvamncecesiustecaes 14 4 1 Selection of Installation Location sessssesesessssesesesessesesesesesessesesesessesesesesesseseseseesesesesesesessesesesesosss 14 4 1 1 Dimensions and WEIGNL cssssssscscscscscscsesssssssssssesesesesssessssescscsesesescsesssssssssssesssesesesesees 15 4 1 2 Ambient Cond
35. ct stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process United Kingdom Eng 05 2015 Rev1 1 9 Problem Confirmation Type Code Description CURRENT PROTECTION 9 1 3 Battery Discharge General Events Type Code PROTECTION E201 PROTECTION E202 PROTECTION E203 PROTECTION E204 United Kingdom Eng 05 2015 Rev1 1 Description ON SEQUENCE GRID OFF ON SEQUENCE BATT STATUS EVENT ON SEQUENCE INV DC LINK EVENT ON SEQUENCE BATT V amp BATT EVENT Measures because a significant PROTECTION event has occurred
36. cy PV to Grid European efficiency Max efficiency Protective Device DC disconnection device for PV Ground fault monitoring grid monitoring General Data Dimensions W H D Weight Protective class I Il II Degree of protection Max permissible value for relative humidity Operating temperature Storage temperature Noise emission Over voltage category Features Display Communication Energy management system Certificates and approvals 95 when power is 4600W 95 5 ee Custom LCD LAN RS485 IEC 62109 1 IEC 62109 2 ER G83 2 ER G59 3 It can be set 3600W or 4600W by software when installing Table 11 1 Technical specifications United Kingdom Eng 05 2015 Rev1 1 5 00 3 00 VY O A a 200 5 fo 1 00 0 00 20 30 40 50 60 Ambient temperature C Figure 11 1 Derating Curve System Efficiency Curve poly 250wp mono 270wp System Efficiency Battery SOC 60 Solar gt Battery Grid 86 00 84 00 sen WSs T g 82 00 78 00 76 00 74 00 72 00 500W 1000W 1500W 2000W 11 Technical Specifications Vmpp 395V poly 250wp Vmpp 370V mono 270wp Figure 11 2 Power efficiency curve of System United Kingdom Eng 05 2015 Rev1 1 70 89 11 Technical Specifications 90 efficiency 100 0 95 0 90 0 85 0 80 0 75 0 Efficiency curve of PV Generation poly 250wp mono 270wp 5 System Efficiency Curve So
37. e The total length of RS485 Cable is 100m or less RS 485 RS485 A ofe o en Server DO Purchase SO FDIN SO FDIN amp SOHPUSH LE SO PUSH baaa Pulse output 10 imp kWh 100ms Modbus output Autometers v 6 aa 6 7 Q Li Figure 6 2 Energy Meter Wiring amp Setting For C2000M 6 2 1 2 Connection terminal 14 RS485 A RS485 B 47 42 0 8 38 10 0 5 alee 9 Figure 6 3 RS485 terminal block Use a torque screwdriver of 0 9 1 2N m to tighten the screws on RS485 A and RS485 B United Kingdom Eng 05 2015 Rev1 1 43 6 Communication Connection 6 3 Recommended Energy Meter List Company Model Interface _ Direction 2 CARLO GAVAZZI EM112 DIN AVO 1 X S1 X RS485 X It is strongly recommend meter Table 6 1 Recommended Meter List 6 4 The Communication Terminal Communication terminal e Bi directional Energy Meter It must be connected with RS485 A RS485 B connector J RS485 A B Figure 6 4 Communication terminal MM Uni
38. e generating process A displayed warning message automatically disappears as soon as the issue is resolved When protection level events occur the product stop the generating process The process may automatically resume as long as the issue is resolved 9 1 1 INVERTER General Events Warnings Type Code Description WARNING E001 GRID UNDER VOLTAGE E002 GRID OVER VOLTAGE E003 BATT UNDER VOLTAGE E004 BATT OVER VOLTAGE E005 FAN WARNING 68 Measures When the system voltage drops below standard level This is the overall voltage current warning message with no special change in the sequence The warning message disappears on reversion to the normal state When the system voltage rises above standard level This is the overall voltage current warning message with no special change in the sequence The warning message disappears on reversion to the normal state When the battery energy voltage drops below standard level This is the overall voltage current warning message with no special change in the sequence The warning message disappears on reversion to the normal state When the battery energy voltage drops above standard level This is the overall voltage current warning message with no special change in the sequence The warning message disappears on reversion to the normal state When the Fan operation is abnormal This is the overall Fan warning message with no special change in the seque
39. e of 100N And the end of outer cable surface should be within 10 mm below the end of protrusion Figure 5 24 Power Cable connection to the terminal block Use the screw to close the side cover and conform to the torque value of 1 2 1 8 Nm United Kingdom Eng 05 2015 Rev1 1 Figure 5 25 Side view after side cover assembly United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 41 6 Communication Connection 6 Communication Connection 6 1 Internet Connection 6 1 1 Components e Wired Router not provided in the product package e RJ45 general LAN Cable not provided in the product package 6 1 2 Connection Block Diagram LAN Common carrier Router ESS Common Carrier m RJ45 LAN RJ45 LAN Cable Cable Figure 6 1 Internet Connection 6 1 3 Connection Method As shown in Subsection 6 4 on the communication terminal part plug the RJ45 LAN Cable between the LAN terminal and the Router 42 United Kingdom Eng 05 2015 Rev1 1 6 Communication Connection 6 2 Energy Meter Connection 6 2 1 RS485 Interface 6 2 1 1 Components RS485 Meter Twist paired RS485 Communication Cabl
40. eeceues 24 Figure 5 5 Side VIEW csssssscecssssssscsscscsccsesesecsesesesscecscsesesesscscsesesesesscscsesssscucscsesesesecucscseseseeecucecseseenceeseaes 25 IRIQUIFE 5 62 Rear ISIC VW eer eo aE mae eee eS 28 Figure 5 7 Battery Tray Rear View issezzessscscscscccacececaczcececscsen shcacansusasasasnenesac anes anc cc coca deeeuveeunssueueueuniaeets 28 iFigure 5 8 Battery COMMECHION es aoee a E E EEE AE EA EAA 28 Figure 5 9 Battery Docking description sree aan 29 Figure 5 10 Batterylo BMS GOANSCUON iie E TEE 30 Figure 5 11 Cable Stuff Method sssessssscscsssssscsssssssssssssssssecessssecessesecessesesessesessesecessesececsesecesaeseces 30 FIGUIrE S 12 Ballery POWer GOMMeCUIO MN iann e E EEEE E E eseienaniads 31 Figure 5 13 Front Cover Assembly process 1 ssesssesseessesseesseoseesseoseessseoseesseoseesscosseoscossroseossesseessee 32 Figure 5 14 Front Cover Assembly process 2 essssssssssscscscessssssecssscsssesscscesessesecsssceceesesceeeseeceesesees 33 Figure 5 15 Front Cover Assembly process 3 ssssssssssscscscsssssesesssscsssesssssesessesssesececeeseseeesseeeeeeesees 33 Figure 5 16 Front Cover Assembly process 4 ssssssssssssscssesssesesscscscsessssceseesesesesececeeseseeeeeeeeeesesees 34 Figure 5 17 Distribution box CONNECTION diagram s sssesseessesssessesssesseessersseoseesseesseoseesseoseesseese 35 Figure 5 18 Electric cable connection for energy meter installation
41. eesseosseoseosseesseoseesseesee 46 Roure 67 MONTONG a OI Sesasteccedeccdecescsecesesesseseies ENRERE A aA A A 47 Figure 6 8 Consumption report page essssesesessessesesesseseseesessossoseseseesesresessosesesseseososessoseseesessesessesesess 47 United Kingdom Eng 05 2015 Rev1 1 vV Table of Figures yi IFigure 69 Forecast page Iaa EEEE EEEREN 48 ICU ONO 10 SOUL Page eona Eaa otbeceunccacveveveveveverrvaien uae 49 Figure 6 11 Mobile Service pagel sssssssecscssssssssececscsssssecsssssssssesecsssssssssssesscssasssssensacsesesecessacsesesees 49 Figure 7 CLIN ET ea ee eE EERE cecececeseceucucucezezazazaeaesbseubenasasasasaasesavavasnesesebnaradcceccecece 51 Figure 7 2 Mitia Setup page s easacceceseresececenesansrsnsss CEEA E OOOO 52 IFig re 7 3 Engineer log page f iissioninisenianiiiiiiin A 54 PIQUE 7A NOW ESS ACC aC S lrs ae feuesanescavcneasaincaeacseaeanncesancncsutseuaussusencecevontusenstenres 55 Figure 7 5 ESS Status Page uu ssssssssssssssssscscsssssssssssssssssssesssssssssesessssssssscsesceescssecesesessssssssseececeseseseesees 56 Figure 7 6 Inverter feed in limit setup PAGE cesesesssesesesesscsesssesscscsssssesessescsssssesecscsessasseseeneassees 57 Figure 7 7 ESS status detail information Page csssssssssecsssssscscssssssessssssssseesssssesssessessssseessseseeseees 57 REIGNS 7 8 55 OLIN E setup page cacao E E 58 PIQUE 7297 PES MOa O A Cie E EA 58 Figure 8 1 Initial indication scre
42. en ON power On ss ssssssesseessesseessessseessesssesseoseeoseesseoseesseoseesseesee 59 Figure 8 2 Standby state indication screen before the EMS COMMANA eseseseeeeseeeeeeeeeees 59 Figure 8 3 PV generation battery charge Load use sell remaining amount eee 60 Figure 8 4 PV generation battery discharge Load use buy shortage amount eeeeeeee 60 Figure 8 5 PV generation Battery standby Load use sell remaining AMOUNT 60 Figure 8 6 PV generation Sell remaining aMount ssssesesseessesssessesssesssesseesseesersseesseoseesseoseessesse 61 Figure 8 7 PV generation BUY shortage amount es esesessssesececsceseseeeessssscssescececsescseceeeceeseseeeeees 61 Figure 8 8 Battery discharge Load use ss ssesssesseessesseessesseessersscesseoseesscoseesseoseesscossesscosseesseoseesseose 61 Figure 8 9 Battery discharge Load use Buy Shortage amount sssssssssessesssesssessesseesssesseesseose 61 Figure 8 10 Indication screen ON Standby MOde sesssssssesssessesseessesssesssesseessesssesseesseossesseoseesseesee 62 Figure 8 11 Indication screen on Forced charged Mode sssssssssscscscssessescsssecsesssssscsceeseseeeeees 62 Figure 8 12 Indication screen on stand alone model esesseessesssrssesssesseessessseesereseesseoseesseoseesseese 62 Figure 8 13 Event occurrence Grid RMS over current protection sssessesesesseessesseesseessesssesse
43. er per string Max input voltage Min input voltage Initial input voltage MPPT voltage range Max input current per string Max input short circuit current for each MPPT Max inverter backfeed current to the array Number of independent MPPT trackers Number of DC inputs pairs for each MPPT Connection type Battery Data DC Battery capacity Battery voltage range nominal voltage Battery Max current Battery nominal current Discharge of depth Battery technology Nominal DC DC power DC DC converter technology Grid Data AC Rated power at 230V 50 Hz Max apparent power Nominal voltage range Rated power frequency range Max current Max over current protection Max allowed current for fuse protection Inrush current Max output fault current Adjustable power factor range Feed in phases connection phases United Kingdom Eng 05 2015 Rev1 1 11 Technical Specifications 3600 UK 4600 UK 6 6 kWp 3 3 kWp 550V 125 V 150V 125 V 500 V 15A 20A Negligible MC4 3 6 kWh 48 0 V 65 9 V 60 V 46 3A 33 3A 90 6000 cycles Li lon 2 0 kw Isolated 3 6kW 4 6 kW 5 kVA 230 V 184 V 264V 50 H2 47 5 Hz 51 5 Hz 16A 20A 30A 32A 68 6 A peak 100 us 420 A peak 4 ms 0 95 1 0 95 1 1 87 11 Technical Specifications 88 Total Harmonic Distortion Total harmonic factor of the output current with total harmonic factor of the AC voltage lt 2 and AC power gt 50 of the rated power Efficien
44. eseosesseneoseosesseseesess 44 OS HOMEPIQE crsa EEEE E O 45 oar S og N oE E E EERS AAEREN 45 O2 MON STAD ooecorirseroriirisriiiisi erisso i iss iE EEEO 45 6 5 3 Membership Withdrawal uu sssssssssssescscscscscsessssssssssesescscsesesessssssesescsescsesesesesessseeseseeees 45 CO Oi 45 6 5 5 Password lnitialization ssessessessessesseesseseessesseeseeseessessesseoseosesseoseoseoseosseoseoseoseoseeseessessessees 46 656 Typesolservice Oi a cstasccsasrscsxansavasansasnannasasansincoosnsasssannonsuenensensnosnsnseeneioineceremnemenreneteee 46 6 5 7 MOb Ile Servite essssssssssssssssssssssssesecscscscscscscscsescscscssssssssssscassssesesescsescscscsesesesescsescseseacacess 49 Entering Initial Installation Information ccccccccsssssccssssssscccccssssccccessscscoes 50 7 1 Information Input Administrator 0 esesesesesesesesesesesscscsesesesescscscsescsescsesesesesesesessesesesesesesesesesees 50 7 2 System Information input stage ssesssessesssesseessesseessessseesseoseessesseesseoseeoseosseoseenseosseossroseossroseessessees 50 7 3 PC Direct Connection and Local Setting ValUe ssesseessessessessessesseessessessessessesseoseoseeseeseessesse 50 7 3 1 PC Direct Connection FIOW ssessessessessessesseeseeseessessesseessesseoseoseosesseoseoseoseoseeseesseoseeseeseeseesses 50 7 3 2 Inserting Jumper Wire es seesesessesesseseseeseseeseseoseseeseseeneseoseseseenesroseseoseseoseseeseseesesessesesreseseeeesee 5
45. ficant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant 69 9 Problem Confirmation Type Code Description Measures E110 BATT OVER 70 PV STRING1 OVER VOLTAGE PROTECTION PV STRING1 OVER CURRENT PROTECTION PV STRING2 OVER VOLTAGE PROTECTION PV STRING2 OVER CURRENT PROTECTION BATT OVER VOLTAGE PROTECTION The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The produ
46. g Schematic of Single Phase System for UK i kWh Main Earth Bar Generation Meter a kWh Utility Meter PV1 Array PV2 Array RS485 L N I Communication 6 40 4 4 4 DC Disconnection Switch I Line 9 V Ay AC Citcuit Breaker O i I AC Grid Line Samsung SDI ESS 3 6kWh All in One Example for switchboard wiring on a TN S network for on grid Figure 5 1 Electrical connections As shown in the Figure 5 2 Figure 5 2 PV connections the 3 6 kWh All In One uses the two independent channels of the PV Input PV1 PV1 PV2 PV2 They are used independently for running the maximum power from the sources of PV1 and PV2 Two channels are recommended for independent use for the two PV Inputs Make sure not to connect one PV string in parallel with the two independent PV inputs PV1 PV2 Refer to 3 6 kWh All In One Solar energy input connection in the Figure 5 2 A PV string must not be commonly connected to the two input terminals of the All in One system That is make sure not to connect the split wiring from one PV string output with the two independent PV inputs PV1 PV1 and PV2 PV2 Refer to the PV String connection method in the Figure 5 2 X PV modules shall have an IEC61730 Application Class A rating or equivalent United Kingdom Eng 05 2015 Rev1 1 21 5 Electrical Connections Figure 5 2 PV connections 22 United Kingdom Eng 05 2015 Rev1 1 5 Elect
47. he maximum cell voltage goes below the limit value When the minimum cell voltage is below Warning level Automatically returns to normal when the minimum cell voltage goes above the limit value When the minimum cell voltage is below Protection level thus terminating the system Automatically returns to normal when the minimum cell voltage goes above the limit value When the maximum cell temperature is above Warning level Automatically returns to normal when the maximum cell temperature goes below the limit value When the maximum cell temperature is above Protection level thus terminating the system Automatically returns to normal when the maximum cell temperature goes below the limit value When the minimum cell temperature is below Warning level Automatically returns to normal when the minimum cell temperature goes above the limit value When the minimum cell temperature is below Protection level thus terminating the system Automatically returns to normal when the minimum cell temperature goes above the limit value 75 9 Problem Confirmation Type Code Description Measures WARNING E509 CELL VOLTAGE When the imbalance of the Cell voltage is IMBALANCE above the limit value PROTECTION Returns to normal when the imbalance of the Cell voltage is below the limit value PROTECTION Returns to normal when the imbalance of the Cell voltage is below the limit value WARNING E511 AFE AFE initial
48. he communication connection line and the external electrical cable are removed from the battery and product Remove the front case cover of the enclosure as described in Chapter 5 Separate an electrical connection connector of the battery BATT A Connector on the system side BATT B Connector on the battery side United Kingdom Eng 05 2015 Rev1 1 91 12 Disassembly Separate the four signal lines which connect the battery to the Tray BMS Lay the main body down to ensure that the tray knob is visible Work with at least two persons Overweight Unfasten the screw on the battery tray to remove it from the main body Lift the battery tray to separate it from the main body Place the main body and the battery tray on the packing box This process is the reverse order of the installation process 12 2 Packaging Make sure to pack the 3 6 kWh All in One in the original box If you have to pack in the box other than provided by Samsung SDI consider the minimum weight of 95 kg The main body must go into the box completely 12 3 Storage Store 3 6 kWh All One at a temperature ranging from 20 to 60 C 12 4 Disposal 92 If the battery or the product life has expired the regulations for the disposal of electronic products in that region must be followed and if it is not possible send them to Samsung SDI The address is indicated in the contact information Chapter 13 United Kingdom Eng 05 2015 Rev1 1 13 Con
49. he output cable is connected with the connector and four BMS and the signal cables come out from the battery module BMS connector Battery r g connector Y Figure 5 8 Battery Connection 28 United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 4 With the main body laid down make sure to have at least two persons hold the tray and lit it up As shown in the Figure 5 9 the battery module must be docked to ensure that the end guide faces the leg of the exterior case of the main body When docking the battery make sure not to have the battery cable caught on the battery frame After docking the battery fasten the screws to fix the tray and the main body Make sure to have two persons lift the battery tray Use a torque screwdriver of 1 2 1 8N m to tighten the screws on the battery tray End guide Figure 5 9 Battery Docking description United Kingdom Eng 05 2015 Rev1 1 29 5 Electrical Connections 5 5 Inner Wiring Connection Power and Signal Wire Connection for BMS 1 The Figure 5 10 shows the lead of the battery tray As shown in the figure two short lines and two long leads come out from the battery Plug four cable lines on the Tray BMS into the upper BMS socket Plug the two long lines on to the right side of the BMS then plug the short two lines on to the left side of it ee ee i a N
50. ial installation information and to monitor the operational information of this system appropriately on server 7 1 Information Input Administrator You have to use a laptop or a smart phone to enter the installation information 7 2 System Information input stage e 1 Step Direct Connection to PC gt Input Local Setting Value e 24 Step Connection to Web Page gt Input Webpage Setting Value 7 3 PC Direct Connection and Local Setting Value 7 3 1 PC Direct Connection Flow e System Off Status Insert Jumper Wire Connect PC LAN cable System AC on PC Direct Connection Input Setting Value System off Remove Jumper Wire Connect Internet LAN Cable 50 United Kingdom Eng 05 2015 Rev1 1 7 Entering Initial Installation Information 7 3 2 Inserting Jumper Wire Figure 7 1 Jumper 7 3 3 LAN Cable Connection between PC and System 7 3 3 1 LAN Cable Type e UTP cable category 5E e 1 1 direct cable 7 3 4 SIM System Install Manager Connection 7 3 4 1 To enable direct communication between the computer and the All in One change the TCP IP settings on the computer as shown below e Seton your laptop Control Panel Network and Sharing Center Change adapter settings Local Area Connector Properties Internet Protocol Version 4 TCP Ipv4 United Kingdom Eng 05 2015 Rev1 1 51 7 Entering Initial Installation Information IP address 17 9
51. ion mode is stopped by the protection event Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PV generation mode is stopped by the protection event Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PV generation mode is stopped by the protection event Wait until the event message disappears After the event message is removed it 73 9 Problem Confirmation Type Code Description Measures automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event Table 9 4 PV general events protection list 9 1 5 System General Events Protection Type Code Description Measures PROTECTION E401 Peci RE When the switch temperature is high Protection Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant PROTECTION event E402 OVER CURRENT Occurs on INVERTER hardware protection TZ FAULT Wait until the event message disappears After the event message is removed it automatically returns
52. irmation Type Code Description Measures If it is not removed until the time limit is reached it is converted to a significant event PROTECTION E0205 NORMAL GRID While in progress battery OFF discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PROTECTION E206 NORMALBATT While in progress battery STATUS EVENT discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PROTECTION E207 NORMALINV DC While in progress battery LINK EVENT discharged charged operation is terminated through the protection function Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event PROTECTION E208 NORMALBATTV_ While in progress battery amp BATT amp BDC discharged charged operation is terminated DC LINK EVENT through the protection function Wait until the event message disappears After the event message is removed
53. ischarger Tray BMS Cooling Fan Carrying handle Table 2 1 Part Description Input Output terminal MC4 2set and Grid connection terminal L N PE 6 United Kingdom Eng 05 2015 Rev1 1 2 Safety 2 3 1 Basic Specifications 3600 UK 4600 UK PV Data DC Max input total power Max input power per string Max input voltage Min input voltage lnitial input voltage MPPT voltage range pA Max input current per string 15A Battery Data DC Grid Data AC PMoxcunent SSS dCSCSa SCS pA Max allowed current for fuse protection It can be set 3600W or 4600W by software when installing Table 2 2 Basic Specifications 2 3 2 Grounding the PV Inverter The PV inverter complies with the local requirements for grounding the PV inverter Samsung SDI recommends connecting and grounding the PV inverter s frame and other electricity conducting surfaces in such a way that there is continuous conduction in order to achieve maximum protection for systems and persons And the PV inverter s DC pole and DC pole are not permitted to be grounded United Kingdom Eng 05 2015 Rev1 1 7 3 Package Removal and Inspection 3 Package Removal and Inspection Included in this box are a battery and printed circuit board and the entire weight amounts to 95 kg Therefore special care must be taken in handling Make sure to have at least two persons deliver and remove the package
54. itions and TemperatureS seesessesseseesessesseseesessessessessesessesseneesesseseeseesess 15 4 1 3 Minimum ClearanCe e ssesssesessesessesesseseesesserssessesesesessesessesessesessesreseseeeeseseeseseesesoesesesesseseses 15 4 1 4 Position LOCATION Selection esesessesessesessesessesessesesessesessesrssesreseseeseseeseseesesosossesesesoeseses 16 AZ MOUNDO MEI UON S secs ava cec cae eeeec cen caceascaccacecicsecasacucsaceascsccaseeseseusansceueaccoesensacnseaencsnsaencatece 17 5 Electrical Connections ssssssssscssssssssssesessssssosossssssosososososososososssssssssssssssssossssoso 20 5 1 The Overview of Electrical COnnectiOn sssesesessesesesesessesesesesssessesesesessesesesosoesesesossssesesesosesseseses 21 5 2 Opening the Front Case COVES cscssssssssssssssssssssssssssssssssscscscsesescscsessseseacscscscsssssssesesseseescscsesesesess 26 5 3 The Overview of the Connection Af a ssssesesessssesesesessesesesesesessesesesessesesesessesesesessesesesesesessseses 27 5 4 Battery Installation e essessessessessessessesseossessesseoseoseeseeseesesseoseoseoseoseosseoseoseoseoseoseoseoseeseessessesseoseesseseees 28 5 5 Inner Wiring Connection Power and Signal Wire Connection for BMS ss sesessesssesseessesse 30 5 6 Closing the Front Case COVER scscsosssssasassasnannanseannnnnnsssnestssssnsosnsasasasanonosavonansnsasszaneesevedsaanaassenenssnanananes 32 5 7 A Method of Locking the Distribution
55. ization failure INITIALIZATION Restored to normal mode on AFE initialization success PROTECTION E512 AFE AFE communication failure INITIALIZATION WARNING E513 CELL Occurs above the standard battery cell TEMPERATURE temperature SENSOR 1EA PROTECTION E514 CELL Occurs above the standard battery cell TEMPERATURE temperature SENSOR 2EA PROTECTION E510 CELL VOLTAGE When the imbalance of the Cell voltage is IMBALANCE above the limit value Table 9 6 BMS general events list 9 1 7 EMS Communication Events Type Code Description Measures WARNING E601 INVERTER Turn off and restart the system COMMUNICATION Reconnect the communication line EVENT between the EMS board and the DSP board WARNING E602 ETHERNET Disconnect and reconnect the LAN EVENT Turn off and restart the Router Make sure that the DHCP server function of Router is activated Turn off and restart the system WARNING E603 ENERGY METER Make sure that the Meter device is properly EVENT selected Disconnect and reconnect the DO cable Turn off and restart the system WARNING C128 Ethernet Error Make sure that the Ethernet communication port and wire connected properly Table 9 7 EMS communication events list 76 United Kingdom Eng 05 2015 Rev1 1 9 1 8 Single Fault Events Type Code WARNING E705 E706 E708 E709 E710 Description GRID UNDER VOLTAGE FAULT GRID OVER VOLTAGE FAULT GRID UNDER FREQUENCY FAULT GRID
56. lar Grid e e eee m _ Gas m 10 20 30 50 100 Load 4 6kW Vmpp 395V Poly 250wp EU N 95 36 Vmpp 370V mono 270wp EU N 94 21 Figure 11 3 Power efficiency curve of PV Generation United Kingdom Eng 05 2015 Rev1 1 12 Disassembly 12 Disassembly 12 1 Disassembly Risk of injury due to the heavy weight of the 3 6 kWh All in One Make sure to have at least two persons move this system Lethal hazards may be caused by high voltages in the 3 6 kWh All in One Lethal hazards may be caused by voltage spikes if the positive and negative terminal of the battery are shorted by conductive metals Stand by for 40 minutes to complete discharging in the system When transporting the All In One system with packaged type units remove the battery tray from the All In One system and transport them separately 12 1 1 Removing Electric Connection Push down the DC disconnect switch in the distribution box Push down the AC circuit breaker in the distribution box Stand by for 40 minutes to complete discharging in the system Remove the AC connection terminal in the main body of the 3 6 kWh All in One Remove the PV connection terminal in the main body of the 3 6 kWh Allin One Remove the communication cable from the 3 6 kWh All in One Remove the energy meter 12 1 2 Disassembling the Main Body of 3 6 kWh All in One Check to make sure that t
57. line Remove the LAN communication cable To complete discharging in the main system wait for 40 minutes Remove the front case cover of the enclosure as described in Chapter 5 Separate the battery electric connection connector BATT A Connector on the BDC side BATT B Connector on the battery side Separate the four signal lines which connect the battery to the Tray BMS Lay the main body down to ensure that the tray knob is visible Work with at least two persons Weight over 95 kg Unfasten the screw on the battery tray to remove it from the main body Lift the battery tray to separate it from the main body Place the main body and the battery tray on the packing box This process is the reverse order of the installation process United Kingdom Eng 05 2015 Rev1 1 10 Maintenance 10 4 The List of Replaceable Parts The Table 10 1 shows the list of parts replaceable for maintenance of this system For the parts other than presented here please refer to the application notes linked on the SAMSUNG SDI website or contact the installer or the service center Part Name Manufacturer Part number Li lon Battery Tray SAMSUNG SDI No a Staubli Group Fan1 Minebia manufacturing 4710KL 04W B59 E00 company 4 Minebia manufacturing 4710KL O4W B59 E00 company Table 10 1 Replaceable parts list 10 4 1 Li lon Battery Tray The Li lon battery module can be replaced if it fails to work properly The 3 6 kWh syste
58. lude case Total Table 4 1 Weight of All in One 4 1 2 Ambient Conditions and Temperatures Identify a proper installation location to install and remove the device easily at any time This device must be located within reach distance The ambient temperature of the installation location will range from 10 C to 40 C 4 1 3 Minimum Clearance This device is required to maintain a minimum clearance distance for the safe installation of the product Refer to the Figure 4 2 to secure enough space and keep a distance of 0 1m from the wall 1m in the front of the device 1m and 0 3m on each side and 0 3m on top United Kingdom Eng 05 2015 Rev1 1 15 4 Installation 0 3m C ESS I o 1 0m 0 7m 0 3m 1 0m 01m SAMSUNG _ It can be set 3600W when installing Figure 4 2 Minimum Clearance for All in One 4 1 4 Position Location Selection As shown in the Figure 4 3 install the device on a flat surface Front back left right gradient within 0 5 To allow for natural ventilation the side of the system must be kept away from the wall about 0 3m at least Make sure not to have foreign substances and objects stuck in the blowing fan ventilation entrance and exit sides o SAMSUNG H in 4 2 pe ag e l R es gt DLAI TT FT OT Figure 4 3 Restriction for the surface gradient 16
59. m uses a battery tray with a 2 battery module manufactured by SAMSUNG SDI When you have to replace the battery module please contact SAMSUNG SDI and provide the item s name and the serial number of the 3 6 kWh All In One system Figure 10 4 Li lon Battery tray manufactured by SAMSUNG SDI United Kingdom Eng 05 2015 Rev1 1 85 10 Maintenance 10 4 2 PV Connector The PV connector can be replaced when it is damaged The PV connector used in the 3 6 kWh All In One system consists of a PV stick with male female parts manufactured by Multi Contact AG c o Staubli Group Figure 10 5 PV Connector MC4 10 4 3 FAN1 amp FAN2 86 In the All in One System FAN1 and FAN2 provide air circulation to maintain and regulate the system temperature The fans can be replaced when they reach the end of their operational life span or fail to work properly If that is the case the installer or the maintenance personnel will identify its cause of malfunction and will replace it The replacement method may depend on the local maintenance conditions The manufacturer s name and the model number of the fan are as follows Minebia Manufacturing Company DC FAN MOTOR 4710KL 04W B59 E00 For further details please refer to the Maintenance Manual or contact SAMSUNG SDI Service The contact address is described in Chapter 13 United Kingdom Eng 05 2015 Rev1 1 11 Technical Specifications PV Data DC Max input total power Max input pow
60. n Connection Samsung SDI F RS nC Energy Storage System O Figure 6 7 Monitoring page 6 5 6 2 Consumption Report The household power consumption information collected during energy meter linkage is provided In particular such information on as the household type the size and the number of family residents is collected according to the customer s approval You can use these data to identify various types of statistics and comparative analysis data Consumption Report May Cus E Consumption vrerirw MORE March igi ary 210kWh 3 212kWh s 210kWh 25 2 25 4 25 2 Mp Pownce Aerrage Gommenption 23 350kWh GOOD 42 0 Figure 6 8 Consumption report page United Kingdom Eng 05 2015 Rev1 1 47 6 Communication Connection 6 5 6 3 ESS Report On the ESS Report page you can check various types of data generated through ESS operation You can also use the ESS Report to check the amount of energy charged or discharged and other data comparisons with the solar energy production amount or the power sales amount 6 5 6 4 ESS Forecast In the ESS Forecast menu the generation amount forecast information and the guide for optimized operation can be checked through the algorithm mounted on the product ESS Report Load vs ESS Discharge vs PV x Load PV ESS Charge ESS Discharge Sales MAY 16 2014 MAY 16 2014 Load 680Wh PV 300Wh ESS Discharge 350Wh rT Wh I
61. nce The warning message disappears on United Kingdom Eng 05 2015 Rev1 _ Type Code Description 9 Problem Confirmation Measures S ee reversion to the normal state When the battery connection is abnormal E006 BATT CONNECTION WARNING This is the connection warning message with no special change in the sequence The warning message disappears on reversion to the normal state Table 9 1 Inverter general events warning list 9 1 2 INVERTER General Events Protection Type PROTECTION Code E101 Description GRID RMS OVER CURRENT PROTECTION DC LINK OVER VOLTAGE PROTECTION PV STRING1 REVERSE CONNECTION PROTECTION PV STRING2 REVERSE CONNECTION PROTECTION United Kingdom Eng 05 2015 Rev1 1 Measures The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a significant PROTECTION event has occurred Wait until the event message disappears After the event message is removed it automatically returns to normal If it is not removed until the time limit is reached it is converted to a significant event The product stops the generating process because a signi
62. necting battery terminals Determine if the battery is inadvertently grounded If that is the case separate battery from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit 10 3 1 Checking Battery Problem When you check the event message as noted in Chapter 9 check whether it is a significant event that informs the battery system Chapter 9 2 significant event E901 E910 If itis a significant event contact the installer or the maintenance personnel If it is a significant event message related to the failure exchange the battery However battery exchange is permitted only to the qualified personnel The battery exchange procedure is as described in Chapter 10 3 2 United Kingdom Eng 05 2015 Rev1 1 83 10 Maintenance 10 3 2 Battery Exchange Procedure 84 Separate the e electrical Communication connection line as guided below before the battery exchange For electrical connection of the main body turn off the AC circuit breaker and the DC disconnect switch in the distribution box to remove the power For the MC4 connector connected to the Photovoltaic source separate the male terminal from the female terminal Remove the AC cable connected to the terminal block in the AC
63. neration battery charge Load use sell remaining amount Figure 8 4 PV generation battery discharge Load use buy shortage amount Figure 8 5 PV generation Battery standby Load use sell remaining amount 60 United Kingdom Eng 05 2015 Rev1 1 8 Operation Test 8 3 2 PV Only Mode This mode enables the solar energy to be generated However the battery charge discharge does not operate Amaximum of 4 6kW or less of solar energy generation power can be sent to the LOAD and the system based on the EMS decision Figure 8 6 PV generation Sell remaining amount Figure 8 7 PV generation Buy shortage amount 8 3 3 Battery Discharge Mode This mode permits of no solar energy generation Battery discharge is only available on this mode Based on the EMS decision the battery discharge power can be sent maximum 2kW or less only to the LOAD Figure 8 8 Battery discharge Load use Figure 8 9 Battery discharge Load use Buy shortage amount United Kingdom Eng 05 2015 Rev1 1 61 8 Operation Test 8 3 4 Standby Mode This is the standby mode before converting to operation mode PV Auto PV Only Battery discharge mode Conversion to the operation mode PV Auto PV Only Battery discharge mode is made by the EMS decision Figure 8 10 Indication screen on Standby Mode 8 3 5 Forced Charge Mode Maintenance mode In this mode solar energy generation is not used but the power continuo
64. nication i 6 d S Line AS AC Citcuit Breaker aie Vee a a Gale DC Disconnection Switch AC Grid Line Samsung SDI ESS 3 6kWh All in One Example for switchboard wiring on a TN S network for on grid Figure 2 1 Connection Diagram 4 United Kingdom Eng 05 2015 Rev1 1 2 Safety 2 2 Safety Precautions High voltages in power conditioning circuits Lethal hazard of electric shock or serious burns All work on the PV modules inverters converters and battery systems must be carried out by qualified personnel only Wear rubber gloves and protective clothing protective glasses and boots when working on high voltage high current systems such as INVERTER and battery systems Li lon battery energy storage system ESS inside When assembling the system do not intentionally short the positive and negative terminals with metallic object All work on the ESS and electrical connections must be carried out by qualified personnel only The ESS within 3 6 kWh All In One provides a safe source of electrical energy when operated as intended and as designed A potentially hazardous circumstance such as excessive heat or electrolyte mist may occur due to improper operating conditions damage misuse and or abuse The following safety precautions and the warning messages described in this section must be observed If any of the following precautions are not fully understood or if you have any question
65. nnection between the All in One system and the distribution box is made to the terminals of the solar energy PVdso1 PVdso1 PVdso2 and PVdso2 of PV1 PV1 PV2 and PV2 On one hand the main body terminals PV1 PV1 PV2 PV2 and the distribution box terminals are connected in proper order On the other hand for the lines coming from the AC GRID Land N leads are connected to the distribution board LG NG The lines coming out from the LGO PGO of the distribution board are be connected to the Land N terminals of the All in One System RCD residual current device Leakage Circuit Breaker This product can cause a DC current in the external protective earthling conductor Where a residual current operated protective RCD or monitoring RCM device is used for protection in case of direct or indirect contact either an RCD or RCM of Type A or Type AC is only available on the supply side of this product Description AC current sensitive AC current sensitive and pulse current sensitive Table 5 6 RCD Leakage circuit breaker description United Kingdom Eng 05 2015 Rev1 1 5 8 5 9 5 Electrical Connections An Installation Method of Energy Meter Electrical Connection The electrical installation method of the digital energy meter energy meter must comply with installation method provided by the digital energy meter manufacturer However the digital energy meter must be selected as recommended by Samsung
66. nseseoseeseoseoseseeseose 76 OA SMOE Fat Vii 05 c5 sce sce ccseccecececececacacsrtnesmnacn namo 77 92 SONCA EVON S opererer ereere EE EE EEE SEa aaa 78 TO MAGN INCE sisid iae araia 79 10 1 Cleaning the Fan and the Cover arsrranrnrrrririirinri rrna n iE EEEE 79 10 2 Checking and Exchanging Various Components ssessessesssessessessessessesseessessessesseoseoseoseeseeseesse 81 1021 FUSE CNS CU s aececasecscncncecacaceraroreconosssancsty AO O OOO OOA 81 10 2 2 Input Output Terminal CHECK ecscsessssesssesescscsescsesesessssssssssesesssesesessssssesessseseeeeees 81 1023 my BS a S a rrr NNN SERRE EEEE 81 10 2 4 FAN Operation CHECK sscssasavecensnonansnensnvavenenvavienny09euvsnssiiiss s es sewsvn ev aiaiaiasnsasasasansssnasasasavendanee 82 103 Battery MaintenaCE oien ever ce cree caverta eraeeieeis 83 10 3 1 Checking Battery Pre lenin cssssssrsrrrsrsrinriniinrrrrr nirin iaaa ERE 83 10 3 2 Battery Exchange Procedure ssssssssssssssssssssssssssssssssssssssssssscseseescsescssssssssasssseseseseseeesees 84 10 4 The List of Replaceable Parts 0 esesesesssssssssssscssscscscscscsesesesesesesesssssesesesesesessesesesesescscacsesescacaeees 85 WAT CRONE EA NA eee EA AEE EEE ee 85 1042 PY CONNECIO nsona EEAO ARESE EN ESE emery 86 1043 TEIN Vea i ccc case cece cc cece cece ecccce sent vacscccce ec ccce sac cacececcozscec an iecac sues cuseuesouseneseuseseansenseannensitecs 86 TL Technical SOGCITICANIONS sssrin 87 TZ DISASS CUNO Y nna a A 91 12
67. nt occurrence On sequence Inverter DC link event ssesssessssssesserssesssesseesse 66 Figure 8 28 Event occurrence Normal Inverter DC link amp PV event ss sssessssssesssessesssesseesse 66 Figure 8 29 Event occurrence Temperature protection sessssessssessssesessesesessessrsesreseseosessssesessese 66 Figure 8 30 Event occurrence Over Current TZ Fault ssesssessssssesssesseessessscoseesseossesseesseoseesseose 66 Figure 8 31 Events occurrence temperature sensor CONNECTION error s ssessessessessesseesssses 66 Figure 8 32 Event occurrence PV mis wiring seessessessessessessessessessscsscssesseoseoseoscoseosseseeseessessesssesses 67 Figure 8 33 Event occurrence SPI COMMUNICATION EVENT ss ssessessessessesseeseeseesseoseeseeseeseessessees 67 Figure 8 34 Event occurrence Single fault event es ssssssssesssesssessseesseessseesseesseesseroseeoseeosseesseesse 67 Figure 8 35 Event occurrence Continuously 3 times Inverter fault ssesssssssesssesssessseesseessse 67 Figure 8 36 Indication screen on Application Download Mode ssessessessesseessessessessesseeseessess 67 Figure 10 1 PV MC4 connector uu estssssesessscsesesesecesscccscecscscsesesesesesesesesesesesesesececscncececececscsescscacaees 79 Figure 10 2 Side cover removal sciuiiennnnuinniciinnnwanunwmanunemuaauauninuuaanints 80 FIG UT TOFS Fan removal 25 cas adesereccs AAAA 80 Figure 10 4 Li l
68. odule The power grid and the house load are connected to the AC power L N PVdso2 PV String 2 gt gt gt PVdso1 PV String 1 PVdso1 4 L LG Distribution Board Grid Figure 5 17 Distribution box connection diagram The PV string 1 and the PV string 2 must be each connected to the distribution box terminal as shown in the distribution board connection diagram Make sure that the string numbers match correctly For example do not connect a PV string 1 to a PV string 2 United Kingdom Eng 05 2015 Rev1 1 35 5 Electrical Connections 5 7 1 5 7 2 36 AC Circuit Breaker and DC Disconnect Switch The circuit breaker populated on the distribution board varies depending on the installer Follow the installation standards to install a circuit breaker satisfying the voltage the current specification of the Grid and the PV The cables presented in the Table 5 5 are recommended for use Standard Short circuit current rating AC circuit breaker 230Vac 32A 10kA minimum DC disconnect switch 650Vdc 15A or more Ba Area Insulation Color code 600V or more Green with yellow lines PV 700V or more Black Table 5 5 Circuit breaker DC Disconnection Switch and power line specification As illustrated in the Figure 5 17 the distribution box connection diagram the co
69. omponent inside the 3 6 kWh All in One ground yourself by touching PE or a grounded object When handling with the Li lon Battery Tray for the 3 6 kWh All in One you must wear the following personal protective equipment High voltage rated rubber gloves Safety goggles or other protective eye equipment 40 minute standby period of time to complete discharging in the system before testing electrical parts inside the system Follow the guidelines below when handling the Li lon Battery Tray Do not intentionally short circuit the positive and negative terminals with a metallic object Do not remove the cap on the terminals If the cap is removed avoid contact between the metals and the battery terminals Do not damage the screw thread Do not use seriously scarred or deformed battery Dispose immediately according to proper regulations Do not damage sheath of cable and connectors 20 United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections 5 1 The Overview of Electrical Connection The 3 6 kWh All In One has two solar energy inputs PV1 PV2 3 3 kW per string is the maximum output for each PV input The AC output of All in One is connected to the Home Load and the Grid Between the Home Load and the Grid the Digital Energy Meter is placed for power metering The AC circuit breaker and DC Disconnect switch in the distribution box are installed between the All in One for safety reasons Wirin
70. on Figure 8 23 Event occurrence On sequence Inverter DC link event Figure 8 24 Event occurrence On sequence Battery V I event Figure 8 25 Event occurrence Normal Inverter DC link event Figure 8 26 Event occurrence Normal Battery V I amp BDC DC link event United Kingdom Eng 05 2015 Rev1 1 65 8 Operation Test Figure 8 27 Event occurrence On sequence Inverter DC link event Figure 8 28 Event occurrence Normal Inverter DC link amp PV event Figure 8 29 Event occurrence Temperature protection Figure 8 30 Event occurrence Over Current TZ Fault Figure 8 31 Events occurrence temperature sensor connection error 66 United Kingdom Eng 05 2015 Rev1 1 8 Operation Test Figure 8 32 Event occurrence PV mis wiring Figure 8 33 Event occurrence SPI communication event Figure 8 34 Event occurrence Single fault event Figure 8 35 Event occurrence Continuously 3 times Inverter fault 8 3 8 Application Download Mode Figure 8 36 Indication screen on Application Download Mode United Kingdom Eng 05 2015 Rev1 1 67 9 Problem Confirmation 9 Problem Confirmation Checking event codes is available on the website https myess samsungsdi com If the Internet is not available the event codes cannot be checked 9 1 General Events The general events contain warnings and protection The warning level events does not stop th
71. on Battery tray manufactured by SAMSUNG SDl sssessssssssesssesssesssessseesseessse 85 IFigare 10 5 PV COMMECTOI IM GA assesses tesa asta asec cca saris sess sass sate ts deta O 86 United Kingdom Eng 05 2015 Rev1 1 Table of Figures Vere TE Te Deratino C Ca OO 89 Figure 11 2 Power efficiency Curve Of System ccssssssscessssssecsssssecessssessssesessssecessesecscsssecessesecessees 89 Figure 11 3 Power efficiency curve Of PV Generation ssseesssesssesssessseesseesseessseessersseeoseeosseesseessee 90 United Kingdom Eng 05 2015 Rev1 1 vii 1 About this Manual 1 About this Manual 1 1 Valid Range This is the installation manual for the 3 6 kWh All In One system Please read this installation and user manual carefully before installing and operating the 3 6 kWh all in one system It contains important safety instructions The warranty will be void if you fail to follow the instructions in this manual 1 2 Target Group This installation manual applies only to the Samsung 3 6 kWh All in One 1 3 Manual Storage The user manual and installation manual can be downloaded from the product download section at https myess samsungsdi com The specifications of the product can be changed for improvement without notice Also the software can be updated automatically without notice over the Internet 1 4 Symbols Used Symbols Meaning This symbol indicates a hazardous situation which could
72. page 58 United Kingdom Eng 05 2015 Rev1 1 8 Operation Test 8 Operation Test 8 1 Starting the System After completing the installation turn on the AC circuit breaker and the DC disconnect switch installed in the distribution box See the Section 5 7 Check the system check message on the front LCD screen Figure 8 1 Initial indication screen on power on After finishing the system check check the system the PV and the battery status Figure 8 2 Standby state indication screen before the EMS command You will receive the command from the EMS to convert to operation mode For individual operation mode screen refer to 8 3 If there is an event message received refer to 8 3 7 8 2 Turning off the System To turn off the system push down the manual AC circuit breaker and the DC disconnect switch in the distribution box United Kingdom Eng 05 2015 Rev1 1 59 8 Operation Test 8 3 Descriptions of Operation Mode This system is composed of six modes PV Auto PV Only Battery discharge Standby Maintenance forced charge and Stand alone The event check status should not be considered as any specific mode 8 3 1 PV Auto Mode Both solar energy generation and battery charge discharge are available The solar generated power is charged or discharged to the battery based on the EMS decision A maximum of 4 6kW or less can be sent to the LOAD and the electric power system Figure 8 3 PV ge
73. r the connectors PV1 PV1 PV2 and PV2 between the distribution box and the 3 6 kWh All In One input the following types of connectors are used MC4 connector PV Stick Photovoltaic connector PUSH IN connection United Kingdom Eng 05 2015 Rev1 1 37 5 Electrical Connections 38 Figure 5 19 PV connector Female and PV line Male The Table 5 7 shows the lead wire standard for the PV The thickness 6mm of the lead wire is recommended for the 3 6 kWh All in One PV Insulation Color code 600V or more Green with yellow lines 700V or more Black Table 5 7 Wire Standard After opening the side cover perform the PV and AC connection Refer to the contents below Disassemble the screw to open the side cover poz Se See eS ee ee ee 223 322 a we Foi fs 4 K o Za Figure 5 20 Side cover opening The Male product is connected to the lead wire coming from the distribution box in the PV side and the Female part is attached to the All in One system The two products are properly docked when connected together After opening the side cover perform the PV and AC connection United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections Figure 5 21 PV connector connection MC4 connector connection In the All in One System the AC power input output por
74. rical Connections As shown in the Table 5 1 the input output power cables correspond to the AC DC input output specifications for this system Recommended cables for the 3 6 kWh All in One Area Insulation Color code Object Part List w pos oO O o ___ Bateryside connector GATTS BAER fH oe C BD_BM Board battery management PN SJ92 01405A BATTERY BD_CAP Board CAP PN SJ92 01428A INVERTER Battery Tray bottom view BATTERY Battery Tray top view BATTERY E I O Electrical I O part INVERTER Table 5 1 Component Description United Kingdom Eng 05 2015 Rev1 1 23 5 Electrical Connections 24 The Figure 5 3 shows the overall drawing of the 3 6 kWh All in One Please refer to the figure of the drawing for installation and maintenance moO Eee o o o EEE Figure 5 4 Rear Inside View United Kingdom Eng 05 2015 Rev1 1 5 Electrical Connections ae SMC Figure 5 5 Side View Part
75. s contact Customer Support for guidance see chapter 13 The safety section may not include all regulations for your locale personnel working with 3 6 kWh All In One must review applicable federal state and local regulations as well as the industry standards regarding this product This product is intended to be used for PV source inputs and residential home grids AC 230V If not used as intended the protection provided by the equipment may be impaired This device is designed appropriate for two PV string structure Therefore the PV string 1 and PV string 2 must be connected to PV input 1 and PV input 2 respectively Do not split one PV string output for connecting it into the PV input terminal 1 and input terminal 2 United Kingdom Eng 05 2015 Rev1 1 5 2 Safety 2 3 Product Overview The All In One system includes the PV inverter battery charger discharger Li lon battery and EMS The basic operating modes consist of PV generation mode PV generation charge discharge mode The operation mode of this product is automatically determined by the EMS algorithm RARER m a 66 66 So t Figure 2 2 Part View of Samsung All in One No Description Lion battery INVERTER PV inverter and battery charger d
76. serssersseress 15 Figure 4 2 Minimum Clearance for All in Onel sssessssssssesssesssessseesseessseesseessersseesssessseesseesseesseesssessss 16 Figure 4 3 Restriction for the surface gradient ccsssssssessssesessesssssssssscsssssessssesessssesecseseseeseessecees 16 Figure 4 4 Spanner for fastening anchor nuts sse sssesseesssesssessseesseessseesseesseroseeosseesseesseesssessereseessss 17 Figures S ANO BON eei OEEO A 17 Figure 4 6 A Flat head driver for the front cover knob larger than 10MM ssesssesssesssesssessse 18 Figure 4 7 The Plus head driver No 2 for the tray the side cover and grounding 18 Figure 4 8 A spanner for fastening USE ccsessssssesesesscsssssssesessssssssessescssssseseseseacsssesessesesssesseseseassees 18 Figure 4 9 A fork lifter with height Of 85 200MIM e sssessssesssesssesssesssessseessseesseesseesseroseeoseeosseesseessee 19 RIG Une 5211 EI SCUICallsCO MIVGCEIOMNS secs sos ca cases case sccrescescaacescenesteaseuswossbessesessceasnseneseneqscseccsosnienscseussesnienseanals 21 Figure 522 PV CONNEC UOS be ccestscsesestecsccescucuccccccecccencescerexasasasasasasasencnce R 22 Figure 5 3 Front Inside View sscscssssssssscscsssssssecssssessssssecsessessssssesscssassesesecassesesecsessasscsesececssassesesees 24 Figure 5 42 Rear Inside VIEW seisteccensescscesescananacaxescaxensesssscevasssacasescsvessen ce sescsvacsunsadecveseesceuauacecencesesauseeden
77. ssessesssesseesssesseessesseensesseesseoseenseoseeoseosseesseosee 27 Table 5 5 Circuit breaker DC Disconnection Switch and power line specification 36 Table 5 6 RCD Leakage circuit breaker description sesssessessessessessessessesseessessessesseoseoseoseeseeseessees 36 Table 5 7 Wire Standard essessessessessessessesseessessesseoseesseseessesseoseoseoseoseoseesseoseoseoseoseoseeseeseeseseoseoseoseesse 38 Table 6 1 Recommended Meter List ssssssssssssssssssssesssscssscscscssssessssssssssssssesssssssesesecsssesescsesseces 44 Table 7 1 Registration Item list ss ssessessessessesseeseeseessessesseeseeseessessessessesseosesseoseeosessesseoseoseoseeseeseeseesses 56 Table 9 1 Inverter general events warning list sssessessessessessessessesseessessessesseoseeseesseseessessessessessses 69 Mable 9 2 Averter Protection ST ann R 71 Table 9 3 Battery operation general events list ssessessssssessessessessessesseessessessessessesseoseoseoseeseeseessees 72 Table 9 4 PV general events protection list ssessssssessessessessessesserssessessessesseoseoseeseeseessensesseoseeseessee 74 Table 9 5 System general events protection list ss ssesssessessessessessessesserssessessessessesseoseoseoseeseessessess 74 Table 9 6 BMS general events list sn nsessessessosseeseeseessesseeseeseessessensesseosessessesseoseossessesseoseoseeseeseeseesses 76 Table 9 7 EMS
78. tact 13 Contact W Address Oskar Messter Str 29 85737 Ismaning Munchen Germany W E Mail esseuservice samsung com For technical problems or inquiries for use please contact the installation company To receive customer support the following information is required 1 Product type ELSR362 00002 2 Serial Number ARO0460036Z1 A 3 PV module type and configuration 4 Option equipment Energy Meter Model Name United Kingdom Eng 05 2015 Rev1 1 93 PSiMSUNGd SAMSUNG SDI United Kingdom Eng 05 2015 Rev1 1
79. ted Kingdom Eng 05 2015 Rev1 1 6 Communication Connection 6 5 6 5 1 6 5 2 6 5 3 6 5 4 Homepage Any customer who has purchased this device can use a web browser https myess samsungsdi com or a smart phone to check its current operation status and receive various Statistical information on operation in the house or remotely Service Terms This service is provided only when the device is connected to the Internet and specific services may require additional information only after approval from the customer Membership To use this service you must register for membership through our homepage During membership registration the member s information such as ID password name and the address are collected and additional data may also be collected to provide statistical J information upon customer s approval Membership Withdrawal For a customer who does not want to use this service membership withdrawal is available through the personal information modification menu on the homepage Log In Log in to the homepage through the ID and the password generated through membership registration You can monitor the product online only when you are logged in Also if a log in ID error or a password error occurs five consecutive times access is blocked for 10 minutes for security reasons and access is permitted after this waiting period of time YN LOGIN We DE ren Ayre Ae ane CAS Ae Figure 6 5
80. to normal If it is not removed until the time limit is PROTECTION E403 TEMPERATURE When the temperature sensor connection is SENSOR abnormal Wait until the event message disappears After the event message is removed it automatically returns to normal PROTECTION E404 PV MIS WIRING When the PV mis wiring states is abnormal Wait until the event message disappears After the event message is removed it automatically returns to normal Table 9 5 System general events protection list reached it is converted to a significant event 74 United Kingdom Eng 05 2015 Rev1 1 9 1 6 BMS General Type WARNING PROTECTION WARNING PROTECTION WARNING PROTECTION WARNING PROTECTION Events Code E501 E502 E503 E504 E505 E506 E507 E508 Description OVER VOLTAGE PROTECTION CELL OVER VOLTAGE PROTECTION CELL UNDER VOLTAGE PROTECTION CELL UNDER VOLTAGE PROTECTION CELL OVER TEMPERATURE PROTECTION CELL OVER TEMPERATURE PROTECTION CELL UNDER TEMPERATURE PROTECTION CELL UNDER TEMPERATURE PROTECTION CELL United Kingdom Eng 05 2015 Rev1 1 9 Problem Confirmation Measures When the maximum cell voltage is above Warning level Automatically returns to normal when the maximum cell voltage goes below the limit value When the maximum cell voltage is above Protection level thus terminating the system Automatically returns to normal when t
81. ts are not plug type They are designed to connect to external devices using screws When connecting the cable to the Land N sockets in the Terminal block the ring terminal is attached to the end of the cable for connection to the main body terminal The Figure 5 22 shows the connection method of the AC part Use the ring terminal M6 for locking Use a torque screwdriver of 2 4 3 0N m to tighten the screws on Land N AC line We recommend the cable composed of two power cords and one PE cord and have insulation cover which contains all three cords as in the figure Each cord shall be 6mm and the diameter of the cable shall be approximately 18mm7 Make sure that the PE cord is longer than other live cords of the cable so that the PE cord will not be affected by the pulling force The PE terminal is connected from the inside of the product to the frame ground of the enclosure Land N AC line connection method Figure 5 22 L and N AC line connection method United Kingdom Eng 05 2015 Rev1 1 39 40 5 Electrical Connections The Figure 5 23 shows the structure of the terminal block Ax0 8 B 0 5 Lhe 14 5 5 Pr Figure 5 23 Terminal Block After that tie the cable to the mount using the cable tie B larger one which is included as an accessory to the tie mount You should tight the tie such that there will not be any slip when you pull the cable with the forc
82. usly flows from the electric power system to the battery Figure 8 11 Indication screen on Forced charged Mode 8 3 6 Stand Alone Mode When the All In One is disconnected from the energy meter or the power conversion system is disconnected from the energy management system EMS the All In One system enters into the Stand Alone Mode The system operates in a PV only mode Figure 8 12 Indication screen on stand alone mode 62 United Kingdom Eng 05 2015 Rev1 1 8 Operation Test 8 3 7 Event Check Mode This mode stops solar energy generation and put it in standby mode as an event occurs Figure 8 13 Event occurrence Grid RMS over current protection Figure 8 14 Event occurrence DC link over voltage protection Figure 8 15 Event occurrence PV string1 reverse connection protection Figure 8 16 Event occurrence PV string2 reverse connection protection United Kingdom Eng 05 2015 Rev1 1 63 8 Operation Test Figure 8 17 Event occurrence PV string1 over voltage protection Figure 8 18 Event occurrence PV string1 over current protection Figure 8 19 Event occurrence PV string2 over voltage protection Figure 8 20 Event occurrence PV string2 over current protection Figure 8 21 Event occurrence Battery over voltage protection 64 United Kingdom Eng 05 2015 Rev1 1 8 Operation Test Figure 8 22 Event occurrence Battery over current protecti
83. w BATTERY a INVERTER REGION A Inside Front View Inside Rear View On the front part of the inside of the system the INVERTER circuit is blocked by the safety shield thus leaving the space for battery installation Region A available The BMS circuit board is shown on the upper part of the Battery region in which the four battery connector is located A battery power connection terminal is shown on the lower part of the device On the rear part the INVERTER shield is shown but other connection terminals are not Table 5 4 Front and Rear view of All in One United Kingdom Eng 05 2015 Rev1 1 27 5 Electrical Connections 5 4 Battery Installation 1 As described in Subsection 5 2 remove the front case and lay the main body of the system on a flat surface with the inside rear view faced upward When you lay down the system make sure to have at least two persons work together for safety Figure 5 6 Rear Inside View 2 Prepare the battery tray to dock the battery on the main body and have at least the two persons work together because the battery weighs much The Figure 5 7 shows the battery tray seen from the enclosure The knobs are located on the battery tray plate and the battery is located on the opposite side of the knob enclosure Knob Figure 5 7 Battery Tray Rear View 3 As seen in the Figure 5 8 of the battery tray t
84. y a subsequent modification is not available 7 3 5 2 Region e Select a city and enter the city name for installation on the menu 7 3 5 3 PV Install Value e Enter installation capacity of each PV string Enter by typing by hand 7 3 5 4 Sever IP amp Port e Enter as basic value e Perform any modification for relevant issues only 7 3 5 5 Energy Meter Selection Meter Type RS485 7 3 5 6 Date Time setting Enter the current date and time 7 3 5 7 Save and Restart Save onto the system after all the procedures above are completed 7 3 5 8 Grid Feed in Limit Regulation Setting For some countries that have a regulation for the grid feed in limit the device allows the installer to set up a limit value You can select the required limit value in the Feed in Limit Percentage on the set up screen The selectable values is 0 60 70 80 90 and unLimited The term unlimited means that is that there is no grid feed in limit 7 3 5 9 Changing the Inverter s Output Setting You can set maximum output value of Inverter It can be either 3 6 kW or 4 6 kW United Kingdom Eng 05 2015 Rev1 1 53 7 Entering Initial Installation Information 7 4 Web Page Connection 7 4 1 Web Page Connection Open an Internet browser of your laptop or smart phone then enter the designated address Then the system information input page pops up Input URL https myess samsungsdi com engineer main do or https 112 106 12 149 engineer main do
Download Pdf Manuals
Related Search
Related Contents
OIL PUMP CATALOG Avaya one-X™ Deskphone Edition for 9640 IP Telephone User Guide profibus-dp master module 2 (eh-rmp2) application Mode d`Emploi 10. Conversion d`un prix de vente (déduction faite du bouquet) de 1 Fisher-Price K3420 User's Manual Philips 8P4831C Projection Television User Manual 24011 - Truper Industries de la machinerie (sauf électrique) au Québec Copyright © All rights reserved.
Failed to retrieve file